Section
4Installation
4.0 Gage Mount Installation
The LTM-Series can be mounted to the side of a
brackets and stainless steel hose clamps. When
mounting the transmitter to an LG series gage the
active sensor region of the probe should fall within
the centerline of the process connections on the
gage. If the transmitter’s deadband region is inside
the centerline of the process connections the
transmitter will not output an accurate
measurement because the active region of the
probe is too short. When placing an order for a
transmitter to accompany an existing gage it is
important to indicate the style of the gage, the
temperature, and the center-to-center dimension.
Calibration of the probe is factory set to the
center-to-center dimensions provided; however a
re-ranging may have to be performed to match the
probe to the desired control room specifications.
See Section 7.1 “Change Range” for more details.
4.1 Standalone Installation
The LTM-Series standalone transmitter comes
equipped with a ¾” mnpt compression fitting,
mounted approximately 6.00” below the electronics
housing. The fitting is placed in this area to ensure
the transmitter is calibrated in the sensor tubes
active region. Refer to the standalone drawings for
a visual description of the transmitter features.
Optional configurations are available upon request
(2” mnpt, flanges, etc…). The magnetic float used in
the stand-alone unit is designed to travel up the
sensor tube with the change in fluid level. If build-
up of process or contaminates should restrict the
movement of the float, the transmitter sensor tube
will have to be cleaned or the float may have to be
replaced with one that has a larger inside diameter.
The floats are designed to match the pressure and
specific gravity for the process being measured and
come in various materials ranging from stainless to
kynar. The magnetic float can be changed out at any
time to accommodate the processes being
measured. The float stop, located at the bottom of
the transmitters, can be removed to allow the float
to slide off the sensor tube.
4.2 General Installation Guidelines
The basic steps to installing the LTMs are:
1. Inspection of equipment: Inspect the parts
that are listed on the packing slip. Make sure
nothing appears to be damaged such as a
broken glass from the level indicator assembly
(flippers), damaged float, or a damaged
transmitter. Please file a claim with the
shipping company immediately if it is believed
the shipment has arrived damaged and be
prepared to provide pictures.
The sensor probe of the transmitter
SHOULD NOT BE BENT, BOWED, OR KINKED in
any way or the transmitter will not work (will
most likely go into fail mode).
The following is a depiction of damaged probes:
Figure 8. All damaged sensor probes
7
Babbitt LG series level gage using special mounting