Balboa Water Group BP100G2 User manual

Template 56377 10-05-12 1
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
BP100G2 Tech Sheet
Customer: Balboa Water Group
Part Number: 59267 5.5kW 800 Incoloy
59268 4.0kW 800 Incoloy
Custom Box Overlay
Box Overlay Part Number N/A
UL System Model For 5.5kW: BP1-BP100G2-BU
For more information
PLEASE VISIT
UL System Model For 4.0kW: BP1-BP100G2-BS
Software Version ID: M100_230 V48.0
Software Version: 48.0
File Name: BP100_48.0_BP100G2.hex
Configuration Signature: F402B0EF
Eng. Project Number: 5205
Control Panels (See later pages for more information):
spaTouch™2 Any version (version 2.0 or later required for bba™2 fully integrated functionality)
Icon spaTouch™ Any version (version 3.36 or later required for bba™2 fully integrated functionality)
Menued spaTouch™ Any version (version 2.8 or later required for bba™2 integrated functionality)
TP900 Version 3.1 and later (Version 3.13 or later required for bba™)
TP800 Version 3.1 and later (Version 3.13 or later required for bba™; version 4.11 or later required for bba™2 integrated functionality)
TP600 Version 2.7 and later (Version 2.12 or later required for bba™/bba™2 On/O control via menu)
TP400T US Version 2.7 and later (TP400T CE may be used) (Version 2.12 or later required for bba™/bba™2 On/O control via menu)
TP400W US Version 2.7 and later (TP400W CE may be used) (Version 2.12 or later required for bba™/bba™2 On/O control via menu)

Template 56377 10-05-12 2
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
Part # EPN Date Originator Changes Made
59267
59268
5205 05-01-19 BWG Generic BP100G2 system, supporting most of the Setups the BP100 board can do with a pump expander board.
System Revision History
bba™ & bba™2 (Balboa Bluetooth Amp) connection is documented seperately.
bba™ is integrated into graphic display panels (TP800, TP900 and spaTouch™). With TP600/TP400, use the “BT” entry on the menu to toggle bba™ power On/Off.
bba™2 is integrated into graphic display panels (TP800, TP900 and spaTouch™). With TP600/TP400, use the “BT” entry on the menu to toggle bba™2 power On/Off.

Template 56377 10-05-12 3
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
Power Requirements:
240VAC, 50/60Hz*, 48A, Class A GFCI-protected service (Circuit Breaker = 60A max.),
4 wires [hot, hot, neutral, ground]
120/240VAC, 50/60Hz**, 16/40A, Class A GFCI-protected service (Circuit Breaker = 20/50A max.) -- Setups 3 & 4 Only
3 or 4 wires [hot, hot (optional), neutral, ground].
**NOTE:
The above 120V spec is only when using a wall-mount GFCI / breaker.
If using a GFCI cord, the breaker is 15A and so the service is limited to 12A.
*BP systems automatically detect 50Hz vs 60Hz. However, power frequency (50Hz vs 60Hz) is just one of many differences between North American (UL) and CE power, and it is
because of these other differences that different BP systems must be used for UL vs CE territories. Also, there are a few countries that use CE power but 60 Hz (such as South
Korea) which need CE systems, and a few countries that use UL power but 50 Hz which need UL systems.
Basic Functions Setup 1 - 4
HiPot Testing Note:
Disconnect slip terminal with green
wires from J6 prior to performing
HiPot test. Failure to disconnect may
cause a false failure of the test.
Reconnect terminal to J6 after
successful completion of HiPot test.

Template 56377 10-05-12 4
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
System Ouputs:
Pump 1 240VAC* 2-Speed 12A max 15-minute timer (30-minute timer for P1 Low in non-circ Setupa 2 & 4 only)
This is the heater pump in Setups 2 & 4.
Must deliver 20 GPM through heater
1-Speed in Setups 1 & 3
Pump 2 240VAC 1-Speed 12A max 15-minute timer
Unused in Setups 3 & 4
Circ Pump 240VAC* 1-Speed 2A max Programmable Filtration Cycles + Polling
This is the heater pump in Setups 1 & 3.
Must deliver 20 GPM through heater
Ozone 240VAC* .5A max Slaved to Circ Pump in Circ Setups and to Pump 1 Low in Non-Circ Setups
Spa Light 10VAC On/Off 1A max 240-minute timer.
A/V (Stereo) 120VAC Hot 3A max Always on
Heater 5.5kW @ 240VAC (approx 1.4kW @ 120VAC)
4.0kW @ 240VAC (1.0kW @ 120VAC)
*Pump 1, Circ Pump and Ozone must be the same voltage.
With 120VAC power input (for Setups 3 & 4 only), Pump 1, Circ pump and Ozone must all be 120V. See wiring diagram for rewiring instructions.
Basic Functions Setup 1 - 4

Template 56377 10-05-12 5
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
Wiring Diagram
Hardware Setup
OPTIONAL 120VAC CONFIG
FOR SETUP 3 & 4 ONLY
WIRING SHOWN IS FOR A 120VAC-ONLY SYSTEM
(1.25kW @ 120VAC HEATER)
FOR A 240V HEATER, MAKE THE FOLLOWING CHANGES:
1. TB1 MUST BE WIRED WHT-1, BLK-2, RED-3
2. MOVE J46 AND J38 WIRES FROM AREA 3 TO AREA 1
3. MOVE J24 JUMPER TO THE 240V POSITION
4. CHANGE F3 FUSE BACK TO 0.1A SLO-BLOW
5. PUT J31 JUMPER ON 2 PINS
A3
A2
SWITCHES #2 & #3
SHOULD BE SET TO OFF
WHEN SYSTEM IS
CONFIGURED AS 120VAC.
OFFON
PUMP 1, OZONE, AND CIRC MUST ALL BE 120V IN THIS CONFIGURATION.
WHT
GFCI
BLK
GRN
WITH
GFCI
CORD,
SERVICE
IS 12A
MAX.
16A
SERVICE
REQUIRES
WALL-MOUNT 20A
GFCI / BREAKER.
TB1
1
2
3
1
2
J4
J8
J18
J51
J1
J27
J10
3
J20
J10
J12
J88
J52
J38
AV
J46
PUMP1
CIRC
OZONE
J24 JUMPERS MUST BE IN
120V POSITIONS AS SHOWN
HERE WHEN HEATER IS
CONFIGURED AS 120VAC.
J31 J31 JUMPER MUST BE ON
1 PIN WHEN HEATER IS
CONFIGURED AS 120VAC.
J31
J31 JUMPER MUST
BE ON 2 PINS
WHEN HEATER IS
CONFIGURED AS 240VAC.
J24 JUMPER
MUST BE IN
240V POSITION
AS SHOWN HERE
WHEN HEATER
IS CONFIGURED
AS 240VAC.
120V 120V
240V
J24
120V 120V
240V
J24
F3 0.16A SLO-BLOW
F3 FUSE MUST BE REPLACED BY A
0.16A SLO-BLOW FUSE (SUPPLIED
WITH PACK) WHEN HEATER IS
CONFIGURED AS 120VAC. SAVE THE
ORIGINAL 0.1A FUSE IN CASE THE
HOMEOWNER WANTS TO CONVERT BACK
TO A 240VAC HEATER.
F3 0.1A SLO-BLOW
F3 FUSE MUST
BE RESTORED
TO THE 0.1A
SLO-BLOW
FUSE WHEN
HEATER IS
CONFIGURED
AS 240VAC.
WHT
BLK
RED
1
2
3
LOCATION DEVICE VOLTS MAX AMPS FROM TO
J9 2/1-SP PUMP 1 240V** 12A MAX
J46
AREA 3
J19
CIRC PUMP
240V**
2A MAX
J21
OZONE
0.5A
CIRC AND OZONE LINE 1 CONNECTION
J51, J52
AREA 2
J33 TV / AV 120V 3A J38
AREA 1
J11 & J13 HEATER 240V 5.5 kW
J15 SPA LIGHT 10V 1A
**PUMP 1, CIRC AND OZONE ALL MUST BE THE SAME VOLTAGE.
SENSOR A
SENSOR B
5.5 kW HEATER
TORQUE RANGE FOR HEATER
CONNECTIONS: 30 TO 35
IN. LBS.
EXPANDER X-P
J3
PUMP 2 K1
J6
J2
W12
EXPANDER X-P
LOCATION DEVICE VOLTS AMPS FROM TO FROM TO
J6 PUMP 2 240V 12A W12 AREA 3 J3 J55
GFCI-PROTECTED CIRCUIT REQUIRED
L2
(RED)
N/A L1
(BLK)
N
(WHT)
WHT
BLK
RED
GRN
TORQUE RANGE
FOR TB1: 27-30IN.LBS.
ALL UNUSED SWITCHES SHOULD BE OFF
8
7
6
5
4
3
2
1
OFF POSITION
S1 SWITCH #ON POSITION
*SWITCH # 6 SHOULD BE SET TO OFF UPON FINAL INSTALLATION.
NOTE: SWITCH A7 MUST BE OFF WHEN USING GRAPHIC
PANELS (TP800, TP900, OR SPATOUCH FAMILY).
TBD
STANDARD MENUS
STORE SETTINGS*
SPECIAL AMPERAGE RULE OFF
1 MIN HTR COOLDOWN (ELEC)
DON’T ADD 2 HS PUMPS W/HTR
DON’T ADD 1 HS PUMP W/HTR
TEST MODE OFF
TBD
SIMPLIFIED MENUS
MEMORY RESET*
SPECIAL AMPERAGE RULE ON
5 MIN HTR COOLDOWN (GAS)
ADD 2 HS PUMPS WITH HEAT
ADD 1 HS PUMP WITH HEAT
TEST MODE ON
NOTE: SWITCH A7 SHOULD BE
OFF IF USING WIFI, SINCE
WIFI DOESN’T SUPPORT
SIMPLIFIED MENUS.
INSTEAD OF
SETUP #2,
THIS SYSTEM IS
CONFIGURED IN
SETUP #:
1 FILTERS + POLLING 1-SPEED 1-SPEED °F
2 NONE 2-SPEED 1-SPEED °F
3 FILTERS + POLLING 1-SPEED NONE °F
4 NONE 2-SPEED NONE °F
SETUP # CIRC PUMP PUMP 1 PUMP 2 TEMP SCALE
FOR SUPPLY CONNECTIONS,
USE CONDUCTORS SIZED ON THE
BASIS OF 60°C AMPACITY BUT
RATED MINIMUM OF 90°C.
CONNECT ONLY TO CIRCUITS PROTECTED BY A CLASS A GFCI.
A DISCONNECTING MEANS MUST BE INSTALLED WITHIN SIGHT FROM
THE EQUIPMENT AND AT LEAST 5 FEET (1.52 M) FROM THE
INSIDE WALLS OF THE POOL, SPA, OR HOT TUB.
USE COPPER CONDUCTORS ONLY.
EMPLOYER UNIQUEMENT
DES CONDUCTEURS DE CUIVRE.
#6 AWG MIN. WIRE= 90°
F4 1A SLO-BLOW
F5 1A SLO-BLOW
F3 0.1A SLO-BLOW
TB1
1
2
3
K5 K1
K2 K4K3
F6 30A 250VAC
T1
J16
J17
J23
SERIAL
J5
REMOTE
RELAY
BOARD
J28 AUX FRZ
J35 MAINJ34 MAIN
K7
K12
120V 120V
240V
J24
J9
PUMP 1
J19
CIRC
J21
OZONE
J33
A/V
1
2
J4
J8
J18
J55
J3
J6
J51
J1
J27
J110
J13
HEATER 1
J2
J7
3
J20
J10
J12
J88
J22
ON
S1
J31 J30
J109
J15
LIGHT
J52
J46
J38
J11
HEATER 2
TP (MAIN) PANELS
J34 OR J35
TOTAL OUTPUT AMP DRAW NOT TO
EXCEED MAX INPUT RATING OF SPA
05-01-19
BP100G2 PN 59267
USE EARTH GROUND CONNECTIONS
AS INDICATED INSIDE SYSTEM ENCLOSURE
1
8
WIFI
TRANSCEIVER
J34 OR J35

Template 56377 10-05-12 6
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
Setup Reference Table
Setup # Circ Pump Pump 1 Pump 2 Temp Scale
1Programmable Filtration + Polling 1-Speed 1-Speed °F
2None 2-Speed 1-Speed °F
3Programmable Filtration + Polling 1-Speed None °F
4None 2-Speed None °F
System (and any replacement board) is shipped
in Setup 2

Template 56377 10-05-12 7
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
Test Menu Access (S1, Switch 1 ON) Service Technician ONLY.
DANGER! HIGH VOLTAGE WILL BE ACCESSIBLE! SERVICE TECHNICIAN ONLY!
While the system is running, move DIP Switch 1 (on S1 on the Main circuit board) to ON.
The system will enter Test Mode.
Moving DIP Switch 1 to OFF will exit Test Mode.
To Change Software Setups:
While in Test Mode, press the indicated icons to move from screen to screen.
ON
1
10
S1
Changing Software Setups with spaTouch™ Icon-Driven Panels
Once on the Setup Selection screen, press the Up or
Down icon to select the desired Setup Number, then
press the Check Mark icon to confirm and to have
the spa restart.
After the system restarts, you may see a message
that “The settings have been reset”; this is normal
after changing Setups with DIP Switch 6 in the OFF
position. Press “Clear” to dismiss this message.
The example screens shown here are from the
spaTouch 1 Icon-Driven Panel, but the screens
on the spaTouch 2 Panel are similar. The main
difference is that the spaTouch 2 display is
wider.
ON
1 6
S1
As soon as Switch #1 is placed
in the ON position, the temperature will show
“T” after it instead of F or C, indicating the
System is in Test Mode

Template 56377 10-05-12 8
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
Test Menu Access (S1, Switch 1 ON) Service Technician ONLY.
DANGER! HIGH VOLTAGE WILL BE ACCESSIBLE! SERVICE TECHNICIAN ONLY!
While the system is running, move DIP Switch 1 (on S1 on the Main circuit board) to ON.
The system will enter Test Mode.
Moving DIP Switch 1 to OFF will exit Test Mode.
Software Setups
Under the TEST Menu, the Setup screen will allow changing the
Setup from 1 to any number established by the Manufacturer.
Changing the Setup may require wiring changes as well.
Changing Software Setups with TP800 / TP900 / spaTouch™ Menued Panel
Set: 104°F
8:32 PM
Ozone
Filter 1
Spa
Shortcuts
Settings
Test
High Range
102°F
Ready in Rest Mode
Heating
ON
1
10
S1
Test
Back
68.143%
Setup
A/B Temps
Fault Log
Timeouts
Temp Limit
1
Off
Normal
Yes
Note: The Timeouts and Temp Limit
selections should NEVER be changed.
They are for safety agency testing
purposes only.

Template 56377 10-05-12 9
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
Changing Software Setups with TP600 / TP400
Test Menu Access (S1, Switch 1 ON) Service Technician ONLY.
DANGER! HIGH VOLTAGE WILL BE ACCESSIBLE! SERVICE TECHNICIAN ONLY!
While the system is running, move DIP Switch 1 (on S1 on the Main circuit board) to ON.
The system will enter Test Mode.
Moving DIP Switch 1 to OFF will exit Test Mode.
Software Setups
Under the TEST Menu, the Setup screen will allow changing the Setup from 1 to any number established by the Manufacturer.
Changing the Setup may require wiring changes as well.
You will have 1 minute to complete the setup change after you manually exit Priming Mode. (Once familiar with the process,
the Setup change should take less than 15 seconds.)
ON
1 6
S1
As soon as Switch #1 is placed
in the ON position, the temperature will show
“T” after it instead of F or C, indicating the
System is in Test Mode
When the panel displays RUN PMPS PURG AIR, press any Temperature button ONCE to exit Priming Mode.
You should see “---T” where the T indicates the system is in Test Mode.
Continued on Next Page.
READY RANGE
READY RANGE
or

Template 56377 10-05-12 10
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
Changing Software Setups with TP600 / TP400 Continued
Again, You will have 1 minute to complete the setup change after you manually exit Priming Mode.
Immediately after exiting Priming Mode, press this sequence of buttons: Warm*, Light, Warm, Warm, Warm, Warm. Continue to press Warm until the diplay
shows the Setup Number (S-01, S-02, etc.) you want to switch to. When the correct setup number is showing, press Light once, and the system will reset,
using the newly-selected Setup from that point on.
Move DIP Switch 1 to the OFF position to take the spa out of Test Mode. °F or °C will replace °T.
Using a permanent marker, write the Setup number on the Setup label mounted inside the system lid (right). This is very important to any service
person in the future who may need to replace a circuit board or system and needs to change the Setup on a replacement part while in the field.
NOTE: Changing the Setup may require wiring changes as well - refer to the wiring diagram or wiring diagram addendum.
THIS SYSTEM IS
CONFIGURED AS
SETUP #
Indicates Flashing or Changing Segment
Key
A temperature button, used for “Action”
Light or dedicated “Choose” button, depending on control panel configuration
Indicates Alternating or Progressive Message - every 1/2 second
Waiting time - varies depending on function
05/12/09
Main Menus with Test Mode (S1 ON) Details
SET
SET
The System will reset and go into Priming Mode if the Light Button
is pressed while anything other than the current setup is flashing.
If there is no change to the Setup Number (S-01, S-02, etc.),
the display returns to the SETP screen.
Several Setups can
exist in in this string
A dash (--) indicates the current Setup.
SET
SET SET
SET SET
SET SET
While the Set Temperature is
still flashing, press Light
TEST will now appear in
the LCD first.
SET RANGE
Main Screen
READY RANGE FLTR1
Main Screen
READY RANGE FLTR1
SET
Approx.
5 sec.
or
Approx.
5 sec.
or
SET
SET
SET
SET
When set to ON, Panel will display
alternate readings from
Senor A and Sensor B
on Main Screen
Displays Fault Log
*If the Control Panel does not have a Warm (Up) button, but
rather a single Temp button, use the Temp button in place
of the Warm button in the instruction above. (The flow chart
assumes a single Temperature Button.)
Note: The Timeouts and Spa O/H
selections should NEVER be changed.
They are for safety agency testing
purposes only.

Template 56377 10-05-12 11
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
Expansion Features
Control Connection Default Fuse
Relay 1 (J5) 1-Speed Pump 2 None (uses main board 30A fuse)
Equipment Expansion

Template 56377 10-05-12 12
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
Fixed-fuction DIP Switches
A1 Test Mode (normally Off).
A2 In “ON” position, add one high-speed pump (or blower) with Heater.
A3 In “ON” position, add two high-speed pumps (or 1 HS Pump and Blower) with Heater.
A5 In “ON” position, enables Special Amperage Rule B. See Special Features section under Configuration Options for functionality with your system.
In “OFF” position, enables Special Amperage Rule A.
A6 Persistent memory reset (Used when the spa is powering up to restore factory settings as determined by software configuration).
A2 and A3 work in combination to determine the number of high-speed devices and blowers that can run before the heater is disabled. i.e. A2 and A3 in the ON position will
allow the heater to operate with up to 3 high-speed pumps (or two HS Pumps and Blower) running at the same time. Heat is disabled when the fourth high-speed pump or
blower is turned on.
Note: A2/A3 all off = No heat with any high-speed pump or blower.
Assignable DIP Switches
A4 In “ON” position, enables a 5-minute cooldown for some gas heaters (Cooling Time B).
In “OFF” position, enables a 1-minute cooldown for electric heaters (Cooling Time A).
A7 In “ON” position, Simplified Menus on TP400/TP600. Do not use graphic panels (TP800, TP900, or spaTouch™ family) with Simplified Menus.
In “OFF” position, Regular Menus on TP400/TP600. This setting is compatible with all panels.
Undesignated switches are not assigned a function.
DIP Switch Functions
ON
1
8
S1

Template 56377 10-05-12 13
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
Jumper Definitions
J109 GFCI Test/Trip Enable/Disable
Note: This feature must be enabled in software as well.
J30 Do Not Use
J31 Jumper on 1 pin when heater voltage is 120V
Jumper on 2 pins when heater voltage is 240V
J24 Jumper on center two pins (240V) when heater voltage is 240V.
Two Jumpers installed; one on left 2 pins and one on right 2 pins (120V) when heater voltage is 120V.
Warning!
Setting DIP switches or jumpers incorrectly may cause abnormal system behavior and/or damage to system components.
Refer to Switchbank illustration on Wiring Configuration page for correct settings for this system.
Contact Balboa if you require additional configuration pages added to this tech sheet.
J109
J31
120V 120V
240V
J24

Template 56377 10-05-12 14
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
Replacement Parts
PCBA:
Main PCBA: 59269
Expander PCBA: 59232
HEATER(s):
Heater: 58421 5.5kW 800Inc
58426 4.0kW 800Inc
Temp Sensor Kit: 30344KIT 12-inch sensor
30382KIT 24-inch sensor
FUSES:
Part Number Amperage Location
30136 30A F6
26983 1A F4, F5
24514 0.1A SLO F3 when using 240V heater
26982 0.16A SLO F3 when using 120V heater

Template 56377 10-05-12 15
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
BP100 Configuration Options
General Features
Feature Default
Pump 1 in Filter Cycle (Circ Only) No
Pump 1 Low Timer 30 Minutes Applies in non-circ Setups (configurations) only
General Pump Timer 15 Minutes
Blower Timer 15 Minutes
Mister Timer 15 Minutes
Light Timer 240 Minutes
Circ (when enabled) Programmable + Polling
Circ Pump can be set with the following functions:
24 hr – 24 hr w/3° shutoff – Acts like P1 Low (filters, polls, etc. - Requires a single-speed P1)
Cleanup Cycle 30 Minutes Between 30 and 240 minutes 30 Minutes
- or OFF
Cleaup as Preference setting Yes Yes, No N/A
Ozone With Heater Pump* Always, Filters/Cleanup Only N/A
Ozone Suppression OFF Between 30 and 120 min. 1 Minute
- or OFF
Pump Purge 60 Seconds Between 30 and 600 seconds 5 Seconds
Blower Purge 30 Seconds Between 5 and 300 seconds 5 Seconds
Mister Purge 5 Seconds
Purge Type Serial - Pumps at lowest speed
* The heater Pump can be either a Circ Pump or Pump 1 Low.

Template 56377 10-05-12 16
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
BP100 Configuration Options
Temperature Features
Feature Default Options Increment
Temperature Display °F °C, °F
All temperatures must be specified in °F. The system converts °F to °C dynamically. If Celsius is required for default settings, choose a desired °C value that (after rounding) cor-
responds to a Fahrenheit value.
°C 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
°F 39 41 43 45 46 48 50 52 54 55 57 59 61 63 64 66 68 70 72
°C 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
°F 73 75 77 79 81 82 84 86 88 90 91 93 95 97 99 100 102 104
Hi-Range Min. Set Temp 80°F Between 50 and 80°F 1°F
Hi-Range Max. Set Temp 104°F Between 60 and 104°F 1°F
Hi-Range Default Temp* 100°F Between 50 and 104°F 1°F
Lo-Range Min. Set Temp 50°F Between 50 and 80°F 1°F
Lo-Range Max. Set Temp 99°F Between 60 and 99°F 1°F
Lo-Range Default Temp* 70°F Between 50 and 99°F 1°F
Freeze Threshold 44°F
Freeze Type Rotating - Pumps at Lowest Speed
Temp Lock Type Temp + Settings
*May be changed by end-user (if enabled)

Template 56377 10-05-12 17
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
BP100 Configuration Options
Time Features
Feature Default Options Increment
Time Format* 12 Hour 12 Hour, 24 Hour N/A
Filter 1 Start Hour* 20:00 (8:00 PM) 00:00 to 23:00 1 Hour
Filter 1 Duration* 2 Hours Between 15 Min and 23:45 15 Minutes
-or continuous
Filter Cycle 2 Default* OFF OFF, ON N/A
Filter 2 Start Hour* 08:00 (8:00 AM) 00:00 to 23:00 1 Hour
Filter 2 Duration* 15 Minutes Between 15 Min and 23:45 15 Minutes
-or Continuous, or Disabled
Light Cycle Disabled Disabled, Enabled N/A
Light Cycle Default* OFF OFF, ON N/A
Light Cycle Start Hour* 21:00 (9:00 PM) 00:00 to 23:00 1 Hour
Light Cycle Duration* 15 Minutes Between 15 Min and 04:00 15 Minutes
-or or Disabled
Cooling Time A 1 Minute
Cooling Time B 5 Minutes
*May be changed by end-user (if enabled)

Template 56377 10-05-12 18
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
BP100 Configuration Options
Reminder Features
Feature Default Options Increment
Reminders Shown* Yes Yes, No N/A
Check pH OFF See Reminder Period Note 1 Days
Check Sanitizer OFF See Reminder Period Note 1 Days
Clean Filter 30 Days See Reminder Period Note 1 Days
Test GFCI OFF See Reminder Period Note 1 Days
Drain Water 100 Days See Reminder Period Note 1 Days
Change Cartridge OFF See Reminder Period Note 1 Days
Clean Cover OFF See Reminder Period Note 1 Days
Treat Wood OFF See Reminder Period Note 1 Days
Change Filter 365 Days See Reminder Period Note 1 Days
Reminder Periods can be set between 7 and 180 days. In addition, 365 days can be chosen.
Each reminder can be turned OFF individually.
*May be changed by end-user (if enabled)

Template 56377 10-05-12 19
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
Special Features
Feature Default Options Increment
Special Amperage Rule A No Limitation 1 Pump
Special Amperage Rule B No Limitation 1 Pump
1 to 7 pumps can run on high speed together.
Blower can be allowed or suppressed when number of pumps selected is reached.
“No Limitation” does not restrict pump or blower operation.
DIP Switch 5 is used to choose Special Amperage Rule 1 or 2.
Drain Mode Disabled Disabled, Enabled N/A
Demo Mode Disabled
GFCI Trip Enabled Disabled, Enabled N/A
Automatic GFCI Test Disabled Disabled, 1-7 Days 1 Day
When GFCI Test is Enabled, the Auto-Test can be set between 1 and 7 days from startup
Ozone Slaved to Heater Pump Yes
Yes, No N/A
Dual Voltage Heater Always Input Voltage 4°F Temperature Delta N/A
Safety Suction Disabled Disabled, Enabled N/A
Menu Style Standard Menus when DIP switch A7 is OFF.
Simplified Menus when DIP switch A7 is ON..
BP100 Configuration Options

Template 56377 10-05-12 20
Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 b2,
Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. © Copyright 2009 Balboa Water Group.
59267_59268_A 05-13-19
TP900 Panel Configuration
Button Layout Table
Button
#
Setup 1 Setup 2 Setup 3 Setup 4
1N/A N/A N/A N/A
2Jets 1 Jets 1 Jets 1 Jets 1
3Jets 2 Jets 2 Light Light
4Light Light Invert Invert
5Invert Invert (Circ Icon) Undefined
6(Circ Icon) Undefined Undefined Undefined
7Undefined Undefined Undefined Undefined
8Undefined Undefined Undefined Undefined
9Undefined Undefined Undefined Undefined
10 Undefined Undefined Undefined Undefined
11 N/A N/A N/A N/A
12 N/A N/A N/A N/A
13 Jets 1 Jets 1 Jets 1 Jets 1
14 Jets 2 Jets 2 Undefined Undefined
15 Light Light Light Light
16 Invert Invert Invert Invert
A Circ Icon will appear when a Circ Pump is configured
Spa Screen
2 3 4 5
6 7 8 9 10
Shortcuts Screen
16
1514
13
13
14 15
16
This manual suits for next models
2
Table of contents
Other Balboa Water Group Control System manuals