DETAIL OF GAS FEED REGULATOR THROTTLE VALVE
WITH DUNGS SERVOMOTOR
A Gas throttle valve position reference index
B Gas modulation servomotor
AB
STARTING UP AND REGULATION WITH METHANE
1) If not already done at the moment of connecting the burner
tothegaspipeline,itisindispensabletocarryoutapurge
oftheaircontainedinthepipeline.Asaprecaution,spe-
cial care should be taken and doors and windows should
be opened. Open the pipe union on the pipeline situated
near the burner and then open a little the gas cut-off cock
(or cocks). When the characteristic odour of gas can be
smelled,closethecut-offcock.Waituntilthegaspresentin
roomhasdispersed,andthenreconnecttheburnertothe
gaspipeline.Subsequently,re-openthegascut-offcock.
2) Check that there is water in the boiler and that the sy-
stem’s gate valves are open.
3)Check,withabsolutecertaintythatthedischargeofcom-
bustion products can take place freely (boiler and chimney
lock-gates should be open).
4) Make sure that the voltage of the electric line to which the
burneristobeconnected,correspondstothatrequiredby
the burner and that the electrical connections (motor and
principle line) have been prepared to match the voltage ra-
ting available.Also check that all the electrical connections
carried out on the spot are in accordance with our electric
wiring diagram.
5) Make sure that the combustion head is long enough to
enterthefurnacetotheextentspeciedbytheboilerma-
nufacturer. Check that the device which regulates the air
on the combustion head is in the position considered ne-
cessary for the fuel delivery required (air passage betwe-
en the disk and the head should be considerably reduced
whenthefueldeliveryisreduced;ontheotherhand,when
thefueldeliveryisfairlyhigh,theairpassagebetweenthe
disk and the head should be relatively open). See Chapter
“AirRegulationontheCombustionHead”.
6)Applyamanometerwithanadequatescale(iftheentityof
pressure forecast allows it is preferable to use a column
ofwater instrument, donotuse a pointerinstrument for
moderate pressure) to the pressure plug on the gas pres-
sure switch.
7) With the switch (1) (see page 33) on the burner’s con-
trolpanelinthe“o”positionandthemainswitchinserted
check,bymanuallyclosingtherelay,thatthemotorrotates
intherightdirection.Ifitdoesnot,exchangetheplacesof
two cables of the motor’s supply line in order to invert its
sense of rotation.
8) Now insert the switch on the command panel. The con-
trolboxreceivesvoltageinthiswayandtheprogrammer
turns on the burner as described in Chapter “Description
of Operations”. To adjust the burner see the “MPA 22”
electronic cam instructions in the attached manual code
0006080905.
9)After adjustingthe “minimum”, (P1) bringthe burner to-
wardsmaximumviathecontrolsontheMPA22keypad.
(see MPA 22 electronic cam instructions in the attached
manualcode0006080905).
10) We recommend that you carry the out combustion tests
with the appropriate instrument at all intermediate
points in the modulation range (from P1 to P9); also check
thegasowdeliveryrateviathemeter.
Itisessentialtocheck,withasuitableinstrument,thatthe
percentage ofcarbonmonoxide (CO)presentinthe
fumesdoesnotexceedthelimitsetbyregulationsatthe
timeofinstallation.”
11) Now check automatic mode working of the modulation
(see “MPA 22” electronic cam instructions in enclosed
manual code 0006080905). In this mode the equipment
receives the signal from the electronic modulation adjuster
RWF40,iftheburnerismodulatingversion,orfromthe
thermostat or the pressure switch second stage if the bur-
ner is progressive two stage.
12) The air pressure switch has the job of bringing the con-
trolboxtoasafetyshutdowniftheairpressureisnotat
thecorrectvalue.Therefore,theairpressureswitchmust
be regulated in such a way as to intervene by closing the
contact (foreseen to by closed while working) when the
airpressureintheburnerhasreachedasufcientlevel.
The pressure switch is self-controlled and therefore it must
close the contact (fan stops and consequently there is an
absenceofairpressure intheburner)ifitdoesnot,the
controlboxwillbeinserted(theburnerremainsatastad-
still).Itmustbespecied thatifthecontactisnotclosed
duringworking(insufcientairpressure),thecontrolbox
willcarryoutitscycle,buttheignitiontransformerwillnot
be inserted and the gas pilot valves will not open. Conse-
quently,theburnerwillgoto“shutdown”.Checkthatthe
air pressure switch functions properly with burner at mini-
mumdelivery,increasetheregulatingvalueuntilitreaches
intervention point and the burner should go to shut down.
Tounblocktheburner,pressthespecialpush-buttonand
returnthepressureswitchregulatortoasufcientvaluein
ordertomeasuretheairpressureexistingduringthepre-
ventilation phase.
13) The pressure switches which control the gas pressure
(minimumandmaximum)havethejobofstoppingthebur-
ner functioning when the gas pressure is not within the va-
luesspecied.Fromthespecicfunctionsofthepressure
switches,itisevidentthatthepressureswitchcontrolsthe