BAREL HFXE LED User manual

Barel reserves the right to change technical specifications without further notice Page 1of 7
HFXE LED
Combined LED DRIVER and EMERGENCY INVERTER
for Ex-ENVIRONMENT
Barel AS
Revision 1
Date 23.04.2021
www.barel.no/
CONTENT
1General.................................................................................................................................................2
1.1 Manufacturer......................................................................................................................................... 2
1.2 Applications........................................................................................................................................... 2
2Approvals..............................................................................................................................................2
3Technical data.......................................................................................................................................3
3.1 Product range ........................................................................................................................................ 3
3.2 Mechanical data .................................................................................................................................... 3
3.3 Expected lifetime................................................................................................................................... 4
4Installation............................................................................................................................................4
4.1 Schedule of limitations .......................................................................................................................... 4
4.2 Electrical connection ............................................................................................................................. 5
4.3 Battery................................................................................................................................................... 5
4.4 Operation............................................................................................................................................... 5
4.5 Cable...................................................................................................................................................... 6
5What to do if.........................................................................................................................................7

Barel reserves the right to change technical specifications without further notice Page 2of 7
1General
These operating instructions apply to the product listed in 3.1. Barel reserves the right to change
technical specifications without further notice. Unauthorized copying or modification of this
content is not permitted.
1.1 Manufacturer
Barel AS
Havneveien 8
9917, Kirkenes, Norway
Phone: +47 789 70 070
www.barel.no/
E-mail: [email protected]
1.2 Applications
State of the art technology is utilized to increase efficiency and long lifetime.
These components are suitable for use in explosive gas atmospheres like:
- Oli industry On- & offshore installations, gas stations, fuel reservoirs, oil tankers
- Chemical industry Production plants
2Approvals
-QAN/QAR 0470 Nemko 01ATEX452Q/
NO/NEM/QAR08.0001/04
-Ex protection Code Ex II 2 G Ex eb mb IIC T4
-IECEx Certificate IECEx PRE 14.0039U
-ATEX no. Presafe 14 ATEX 5355U
According to directives and standards listed:
ATEX Directive 2014/34/EU
EN 60079-0:2018 Explosive atmospheres -- Part 0: Equipment - General requirements
EN 60079-7:2015 Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
EN 60079-18:2015/A1:2017 Explosive atmospheres - Part 18: Equipment protection by encapsulation "m"
IECEx Scheme
IEC 60079-0:2017 Explosive atmospheres - Part 0: Equipment - General requirements
IEC 60079-7:2015+ AMD1:2017 Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
IEC 60079-18:2014/AMD1:2017 Explosive atmospheres - Part 18: Equipment protection by encapsulation "m"
EMC-Directive 2014/30/EU
EN 55015:2013/A1:2015 Limits and methods of measurement of radio disturbance characteristics of electrical lighting and
similar equipment
EN 61000-3-2:2014 Electromagnetic compatibility (EMC) - Part 3-2: Limits - Limits for harmonic current emissions (equipment
input current <= 16 A per phase)
EN 61000-3-3:2013 Electromagnetic compatibility (EMC) -- Part 3-3: Limits - Limitation of voltage changes, voltage fluctuations
and flicker in public low-voltage supply systems, for equipment with rated current <= 16 A per phase and not subject to
conditional connection
EN 61547:2009 Equipment for general lighting purposes - EMC immunity requirements
Low Voltage Directive 2014/35/EU
EN 61347-1:2015 Lamp control gear -- Part 1: General and safety requirements
EN 61347-2-7:2012 Lamp control gear -Particular requirements for battery supplied electronic control gear for emergency
lighting
EN 61347-2-13:2014/A1:2017 Lamp control gear - Part 2-13: Particular requirements for dc. or ac. supplied electronic control
gear for LED module
RoHS Directive 2011/65/EU
EN 50581:2012 Technical documentation for the assessment of electrical and electronic products with respect to the restriction of
hazardous substances

Barel reserves the right to change technical specifications without further notice Page 3of 7
3Technical data
3.1 Product range
Ik max=1500A
Marking Ex II 2 G Ex eb mb IIC Gb
Ta
T c
Dimension
LxWxH
Weight
-52 to +65°C
80°C
285x75x32mm
960g
3.2 Mechanical data
-Aluminium housing fastened with 2 screws in the plastic end-caps, c-c 276mm.
Name
Barel part
number
LED current
in normal
operation +/-
7%
Lamp type
Input Current
range AC +/-10%
PF at 230V
50Hz
THD% at
230V 50Hz
Battery type
Emergency
output
90min (+/ -
10%)
Emergency
output
180min (+/ -
10%)
ARC 600 0,16-0,06A 0,84 28 35mA 28mA
ARC 1200 0,29-0,12A 0,94 17 28mA 24mA
ARC 600 0,26-0,12A 0,92 22 60mA 44mA
ARC 1200 0,57-0,22A 0,98 10 47mA 25mA
ARC 600 110mA 70mA
ARC 1200 44mA 32mA
ARC 600 0,18-0,1A 0,92 26 110mA 70mA
ARC 1200 0,34-0,16A 0,97 14 44mA 32mA
ARC 600 0,26-0,13A 0,96 20 110mA 70mA
ARC 1200 0,57-0,22A 0,99 10 44mA 32mA
Input Voltage AC
50/60Hz -DC
220-
250VDC
*
110-
254VAC
4,8V NiCD 4-
5Ah
7,2V NiCD 4-
5Ah
7,2V NiCD 4-
5Ah
200mA
7,2V NiCD 4-
5Ah
11949-370
HFXE LED
200mA
250mA
370mA
11951 * (not for
newdesign - replaced
by11949-200)
11949-250
11949 * (not for
newdesign - replaced
by11949-370)
11949-200
Available on request
370mA
4,8V NiCD 4-
5Ah

Barel reserves the right to change technical specifications without further notice Page 4of 7
3.3 Expected lifetime
HFXE LED: At Tc <55°C the expected lifetime to survival of >90% of units exceeds 75.000 hours
Expected lifetime of the system HFXE LED and ARC depends on the following parameters:
•Operation at maximum ambient temperature will decrease lifetime
•Number of switching cycles –
oFrequent switching causing rapid temperature change will decrease lifetime
•Number of thermal cycles –
oFrequent and rapid cycling from cold to warm will decrease lifetime
•Constant operation in stabile low to medium temperature will increase lifetime
•Mains supply quality, susceptibility for high-voltage spikes in the supply lines
4Installation
These components do not cause harm or injury when used as specified in these instructions. If this
equipment is not utilized in a manner specified by the manufacturer, the protection by the
equipment may be impaired.
Inrush current and circuit breaker characteristics/amount of units per circuit breaker must be
considered in the installation.
Do not energize circuit before all components and LED-modules are connected properly.
In case of no function or malfunction: first de-energize the circuit. Disconnect mains and battery
supply before LED modules are disconnected.
•Connect all components, battery and LED module.
•Check that all connections are made to the correct port, tightened to the correct torque and that
no wires are loose or damaged.
•The LED module must be connected to correct polarity. Do not operate the unit without LED
module properly connected.
•Energize the unit from mains supply.
oThe LED module will light up in normal mode.
•Test of HFXE; The battery must be properly charged before this test –min 24h.
oDisconnect mains supply, all phases.
oThe HFXE will switch the internal source to battery supply, and LED module will
light up in reduced mode.
oThe preset emergency operation time 90 or 180 minutes will be completed before the
HFXE will switch of the LED module.
•When mains supply is reconnected the HFXE will stop battery operation and return to normal
mode and normal light output.
•Disconnect battery before mains before storage. Battery should be fully charged and
disconnected before storage longer period.
4.1 Schedule of limitations
-The temperature of the TC point must not be exceeded
-The minimum operating temperature of the
o HFXE LED-driver is -52°C
-The HFXE LED have an output rating of 50-130V and 200-370mA. The current is limited to
850mA and breaking capacity of 1500A and has been tested together with Barel ARC LED
600 and 1200, certified Presafe 15 ATEX 6296U and IECEx PRE 15.0014U.
-Charge current is limited to max 200mA
-Charge voltage is limited to 9,3V

Barel reserves the right to change technical specifications without further notice Page 5of 7
-With one fault condition of the charging system, the charging power is limited to 2W by a
transformer and the current is limited to 200mA for 11949-XXX.
-Discharge current = 0.5A - 1.75A.
-Discharge cut-off voltage = 1.0V/cell i.e. 6.0V for 7.2V battery,
-The fault current on the battery input is limited to 6.8A.
-The indicator LED outputs has the following nominal ratings: 3V, 14mA and is limited to
5.4V and 18.3mA.
-The LED-driver shall be mounted inside an Ex e luminaire and not directly exposed to light.
-The terminal has a rating of 450V, Torque 0.9Nm and capacity on the screw side of one
conductor with dimensions 1.0 - 2.5mm2 rigid or flex.
4.2 Electrical connection
Electrical connections of the LED-driver must be done with mains power supply off, and
disconnected. The mains supply must be disconnected by an external 2-pole switch (both phases
must be off). Connect “GND” to Protective Earth and chassis of the luminary or to a separate
ground connection. The aluminium chassis is internally connected to the gnd pin. DC input:
Connect –to “N” and + to “L/L1/L4”. Connect L1 via switch to allow battery charging while light
is switched off. Indicator LED to be connected to 5-6 or 5-7 as indicated: (LED module
connection according to marking label) ( Do not connect HFXE LED to mains supply without
LED module connected)
4.3 Battery
Batteries are to be assessed with final certification of luminaire. Charge and discharge
characteristics are suitable for use with high-temp NiCd cells, 7,2V 4Ah (6C). Connect battery to
correct polarity of HFXE “13” and “14”. Maximum continuous charge current <200mA.
4.4 Operation
Setting of 1.5h and 3h operation is selected by connection of Charging Indicator (LED) to
terminals 5, 6 and 7 as described in table below.
For manual operation (no self-test) a single color (green) LED is used. It is recommended to use
bidirectional LED, for correct functionality of the charging indicator. For use of the luminaire
without connected battery L4 should be disconnected to ensure proper functionality of the green
LED.
For a Self-test operation, a bidirectional LED is used (RED / GREEN) connected such that OK =
GREEN. For connection of the bicolor LED the green colored LED is referred to as Anode and
Cathode.

Barel reserves the right to change technical specifications without further notice Page 6of 7
TEST:
NOTE: A full test should not be activated when the battery is empty or low capacity - this could
result in a wrong error-message.
Manual test:
By disconnecting the mains when the battery has been charged for a minimum of 24 hours.
Status of the test must be observed manually. In case of failure: repair the problem and re-test or
reset unit by disconnecting mains.
Self-test:
By using a bipolar LED connected to the 2 of the 3 pins 5, 6 or 7 as shown above, then a self-test
will be performed. This test will automatically run a short test after 24h, then monthly and a full
annual test operating the LED module in emergency mode from the battery. The test-timer
includes a random-period to avoid all luminaires to self-test at the same time. Disconnection/reset
of mains and battery at the same time will reset the test-timer. Test-program is conducted acc to
IEC 62034.
Indicator
LED
(green) no
self-test
Indicator
LED
(red/green)
self-test
System
status
Action
Continuous
green
Continuous
green
System
ok
Battery charging ok and no faults apparent.
No light
Continuous
blinking
red
Battery
capacity
problem
24 h charge period after last discharge not completed, or faulty
battery. Retest system after 24h charging period, or replace
battery
No light
Intermittent
blinking
red
Faulty
LED
module
Replace faulty or missing LED module.
No light
Continuous
red
Charging
error
Battery defective or missing. Connect or replace battery.
No light
No light
No
function
Connect to mains supply voltage within specified limits.
4.5 Cable
Cable cross sectional area: 1 –2,5 mm2 (solid or multi wire).
Terminal torque: 0,9Nm.
Terminal screw/tool: 0,6x3,5mm Slotted bit of high quality is recommended.
Suitable ferrule should be used to secure the connection of stranded wires.
For Aluminium cables; a bi metallic connector should be used to provide a copper connection.

Barel reserves the right to change technical specifications without further notice Page 7of 7
5What to do if...
Do not energize circuit before all components are connected properly.
In case of no function or malfunction: first de-energize the circuit. Disconnect mains and battery
supply before LED modules are disconnected.
-No light in LED module when connected to mains supply-
- Make sure all components are the correct type and suitable for driver type, mains supply
voltage and frequency range
- Make sure all connections are correct.
- Allow a reset of mains supply.
-Some internal protection circuits require a reset of mains supply before resuming operation after a
fault is detected.
- Contact Barel if no fault was found and the reset does not restart the unit.
-Do not attempt to open or repair these units. Both HFXE and ARC should be replaced in case of
failure –to avoid premature failure of the other component.
-No light in emergency mode:
- Reconnect mains supply
- Check the indicator LED status-
- If green; There is a fault in the HFXE. De-energize the unit. Disconnect battery
before LED module.
- If red or no light in indicator;
-Allow the battery to charge 24h
-Retest emergency mode.
If problems with conducted emission during EMC measurements, contact Barel for assistance.
Important issues are:
-Keep all wires short.
-Separate LED module wires from mains supply wires
-Ground the LED-driver through a short wire connection, and if possible
separate from mains cabling internally in luminaire.
Table of contents
Popular Inverter manuals by other brands

Toshiba
Toshiba TOSVERT VF-AS1 Series Brochure & specs

Chicago Electric
Chicago Electric 92708 Assembly and operating instructions

Fronus
Fronus Xtreme Series quick guide

Kaco
Kaco blueplanet 87.0 TL3 manual

JPS
JPS PDA Series instruction manual

Generac Power Systems
Generac Power Systems 04673-2 Installation and owner's manual

Clenergy
Clenergy PV-ezRack SolarRoof ER-TL-10/15 installation guide

Wasserstein
Wasserstein Noorio Spotlight Cam B210 user manual

Telecom
Telecom DC instruction manual

PanelClaw
PanelClaw Polar Bear III 10 Degree installation manual

Rohde & Schwarz
Rohde & Schwarz SMF100A operating manual

Velleman
Velleman PI300BN user manual