Basler BE1-59N User manual

BE1-59N
UBG-7
1-02
APPLICATION
Page 2
SPECIFICATIONS
Page 3
EXTERNAL
CONNECTIONS
Page 6
ORDERING
Page 7
P. O. BOX 269 HIGHLAND, ILLINOIS 62249, U.S.A. PHONE 618-654-2341 FAX 618-654-2351
ADDITIONAL INFORMATION
INSTRUCTION MANUAL
Request publication 9171400990
Request bulletin SDA
STANDARDS, DIMENSIONS & ACCESSORIES
The BE1-59N Ground Fault Overvoltage Relay provides sensitive protection for
ungrounded and high resistance grounded systems.
ADVANTAGES
• Provides 100% stator ground fault protection.
• 100/120 Vac or 200/240 Vac nominal sensing input.
• Four sensitivity ranges for overvoltage are available: 1-20 and 10-50 Vac for a
100/120 Vac input and 2-40 and 20-100 Vac for a 200/240 Vac input.
• Four sensitivity ranges for undervoltage are available: 0.1-2.5 Vac and 0.5-12 Vac
for a 100/120 Vac input and 0.2-5 Vac and 1-24 Vac for a 200/240 Vac input.
• Instantaneous, definite, and inverse time characteristics.
• 40 dB harmonic filtering.
• Low sensing input burden.
• Power supply status contact.
• Qualified to the requirements of
— IEEE C37.90.1-1989 and IEC 255 for surge withstand capability;
— IEC 255-5 for impulse.
• UL Recognized under Standard 508, UL File #E97033.
• Five year warranty.
BE1-59N
GROUND FAULT
OVERVOLTAGE RELAY

BE1-59N
APPLICATION
2
PURPOSE
The available fault current for single-phase-to-ground
Faults is very limited for ungrounded systems and
systems that are grounded through a high resistance.
This current limiting reduces the possibility of extensive
equipment damage, and eliminates the need for a
neutral breaker by reducing the fault current below the
level required to sustain an arc.
But it remains important to detect and isolate single-
phase- to-ground faults in order to prevent their evolu-
tion into more dangerous faults such as phase-to-
phase-to-ground and three-phase-to-ground faults.
Sensitive voltage relays can be used to detect ground
faults where the fault current is very small. The
BE1-59N is especially suited to the task.
HIGH RESISTANCE GROUNDING
A common method of grounding an ac generator is to
connect a distribution transformer between the neutral
of the generator and the station ground. The distribu-
tion transformer’s primary voltage rating is equal to, or
greater than, the generator’s rated line-to-neutral
voltage. The distribution transformer secondary is rated
at 200/240 Vac or 100/120 Vac, and a resistor is con-
nected across the secondary winding. When reflected
through the transformer, the resistor is effectively a
high resistance.
RP= RS X N2
where RP is the effective primary resistance
RS is the actual value of the secondary resistor
N is the turns ratio of the distribution transformer
Available single-phase-to-ground fault current at the
generator terminals is greatly reduced by the high
effective resistance of the distribution transformer and
secondary resistor. The distribution transformer pro-
vides isolation for the protection scheme and reduces
the voltage to a convenient level.
The BEl-59N ground fault overvoltage relay is con-
nected across the secondary resistor to detect the
increase in voltage across the distribution transformer
caused by a ground fault in the generator stator
windings. A ground fault at the generator terminals will
result in rated line-to-neutral voltage across the trans-
former primary, while ground faults near the neutral will
result in lower voltages. The overvoltage relay set point
must be higher than any neutral voltage caused by
normal unbalances in order to avoid nuisance trips.
This will allow a certain percentage of the stator
windings to go unprotected by the overvoltage relay.
The overvoltage relay function typically protects 90 to
95% of the generator stator windings.
The BEl-59N ground fault overvoltage relay monitors
the fundamental frequency (50 or 60 Hz) voltage that
accompanies a ground fault, and is insensitive to the
third harmonic voltage present during normal opera-
tion.
One hundred percent protection of the generator stator
windings is obtainable with the optional overlapping
undervoltage element. The undervoltage element is
tuned to measure the third harmonic voltage, which is
present in the generator neutral under normal operat-
ing conditions. The undervoltage element detects the
reduction of the normal third harmonic voltage that
accompanies a ground fault near the neutral point of
the generator.
An undervoltage inhibit feature is included with the
third harmonic undervoltage element. This feature
supervises the operation of the ground fault relay to
prevent operation during startup and shutdown by
monitoring the generator terminal voltage.
UNGROUNDED SYSTEMS
The BEl-59N ground fault overvoltage relay is used to
detect ground faults on ungrounded three-phase-three-
wire systems. The relay is connected as shown in
Figure 1. A set of voltage transformers is wired with a
grounded wye primary and a broken delta secondary.
The BEl-59N is connected across the broken delta. It is
often necessary to connect a resistor across the
broken delta to avoid ferroresonance.
Figure 1 - Ungrounded 3-Phase, 3-Wire System

BE1-59N
3
APPLICATION, continued
SPECIFICATIONS
Grounded wye/broken delta voltage transformers act as
zero sequence filters by summing the three phase
voltages. Under normal conditions this sum is zero.
When a ground fault occurs, the BEl-59N ground fault
overvoltage relay will detect the presence of the sec-
ondary zero sequence voltage (3V0).
The BEl-59N ground fault overvoltage relay greatly
reduces the risk of equipment damage by detecting
and isolating the first ground to occur on an un-
grounded system.
FUNCTIONAL DESCRIPTION
The specifications on these pages define the features
and options that can be combined to exactly satisfy an
application requirement. The block diagram (Figure 2)
illustrates the overall operation of the relay.
INPUTS
Nominal sensing input ratings, defined by the style
number, are 100/120 or 200/240 Vat with a maximum
burden of 2 VA single-phase at nominal 50/60 Hz. The
maximum continuous voltage rating is 360 Vat for 100/
120 Vat nominal, and 480 Vat for 200/240 Vat nominal.
Overvoltage Sensing
In a typical application, the BEl-59N Ground Fault
Overvoltage Relay monitors the voltage across a
resistor in the generator’s grounding circuit. The
voltage across the resistor is supplied to the sensing
transformer in the relay.
The derived secondary voltage is applied to an active
filter to obtain the fundamental component of the input
voltage. If this voltage exceeds the OVERVOLTAGE
PICKUP (controlled at the front panel), an LED illumi-
nates, and an internal signal is developed that may be
employed three different ways, depending upon the
timing option selected.
1. The overvoltage output relay is energized instanta
neously.
2. A definite time delay (optional) is initiated whose
period is determined by the front panel TIME DIAL
over a range or 0.1 to 99.9 seconds. At the expira-
tion of the time delay, the overvoltage output con-
tacts close.
3. An inverse time delay (optional) is initiated whose
period is determined by two factors:
a. Magnitude of the overvoltage condition (±2%
or 100 mV or whichever is greater for the 120
Vac pickup range or ±2% or 200 mV for the 240
Vac pickup range), and
b. Selection of a particular response curve by the
front panel TIME DELAY over the range of 01 to
99 (±5% or 25 mSec, whichever is greater)
(Reference Figure 4.)
Figure 2 - Functional Block Diagram

BE1-59N
4
Undervoltage Sensing Option
The undervoltage option is sensitive to the third har-
monic (150 Hz or 180 Hz) voltage at the generator
neutral, and insensitive to the fundamental frequency
(50 or 60 Hz). The undervoltage measuring element
determines within 5 cycles if the third harmonic voltage
is less than or greater than the UNDERVOLTAGE
PICKUP setting on the front panel. If less than, the
UNDERVOLTAGE LED will illuminate, and an internal
signal is developed which may be employed three
different ways, depending upon the timing option
selected.
1. The undervoltage output relay is energized instanta-
neously.
2. A definite time delay is initiated whose period is
determined by the front panel TIME DIAL over a
range or 0.1 to 99.9 seconds. At the expiration of the
time delay, the undervoltage output contacts close.
3. An inverse time delay is initiated whose period is
determined by two factors:
a.Magnitude of the undervoltage condition (±2%
or 100 mV or whichever is greater for the 120 Vac
pickup range or ±2% or 200 mV for the 240 Vac
pickup range), and
b.Selection of a particular response curve by the
front panel TIME DIAL over the range of 01 to 99
(±5% or 25 mSec, whichever is greater)
(Reference Figure 3.)
SPECIFICATIONS, continued
Undervoltage Inhibit
When the undervoltage measuring element is selected,
an undervoltage inhibit circuit is included to monitor the
generator terminal voltage. When the terminal voltage
is less than the UNDERVOLTAGE INHIBIT setting on
the front panel, the undervoltage sensing option is
inhibited to prevent relay operation during start-up or
shutdown of the generating unit.
The UNDERVOLTAGE INHIBIT range is continuously
adjustable from 40 to 120 Vac for the 100/120 Vac
sensing input, and 80 to 240 Vac for the 200/240 Vac
input.
PICKUP ACCURACY
Relay pickup will not vary from its setting more than as
follows for variations in input power or operating
temperature within the specified limits.
For 120 Vac sensing range: ±2.0% or 100
millivolts, whichever is greater.
For 240 Vac sensing range: ±2.0% or 200
millivolts, whichever is greater.
DROPOUT RATIO
Overvoltage and undervoltage elements reset within
2.0% of their actual pickup level within seven cycles.
Figure 3 - Undervoltage Inverse Time Curve Figure 4 - Overvoltage Inverse Time Curve

BE1-59N
SPECIFICATIONS (continued)
5
TIMING ACCURACY
Definite time is adjustable from 00.1 to 99.9 seconds, in
steps of 0.1 seconds. Accuracy is within 2.0% or 100
milliseconds, whichever is greater.
Inverse time is adjustable from 01 to 99 in increments
of 01. The setting defines a curve as illustrated in
Figures 3 and 4. Inverse timing is accurate within ±5%
or 25.0 milliseconds, whichever is greater, for any
combination of time dial and pickup setting.
POWER SUPPLY
One of five power supply types may be selected to
provide internal operating power. They are described in
Table 1.
Table 1 - Power Supply Options
Type K J L Y* Z
Nominal 48Vdc 125Vdc 24Vdc 48Vdc 250 Vdc
Voltage 120 Vac 125 Vdc 240 Vac
Burden 7.0 W 7.5 W 7.5 W 7.0 W 12.0 W
15.0 VA 7.5 W 33.5 VA
*The type Y power supply is field selectable for 48 or 125Vdc.
Selection must be accomplished at the time of installation. This
Power Supply option is factory set for 125Vdc.
POWER SUPPLY STATUS OUTPUT
A normally closed output relay may be provided,
whose contact remains open when energized by the
presence of nominal voltage at the output of the power
supply. If the power supply voltage falls below require-
ments, the power supply status output relay will de-
energize, closing its contact. A shorting bar is included
in the relay case so that the status output terminals can
provide a remote indication that the BE1-59N relay has
been withdrawn from its case or taken out of service by
removing the connection plug.
OUTPUTS
Output contacts are rated as follows:
Resistive
120/240 Vac - make 30 A for 0.2 seconds,
carry 7 A continuously, break 7 A.
250 Vdc - make and carry 30 A for 0.2 seconds,
carry 7 A continuously, break 0.1 A.
500 Vdc - make and carry 15 A for 0.2 seconds,
carry 7 A continuously, break 0.1 A.
Inductive
120/240 Vac, 125 Vdc, 250 Vdc - Make and carry 30A
for 0.2 sec., carry 7A continuously, and break 0.1 A
(L/R = 0.04).
Push-to Energize Output Switches
Momentary pushbuttons accessible by inserting a 1/8-
inch diameter non-conducting rod through the front
panel. Pushbuttons are used to energize the output
relays in order to test system wiring.
TARGET INDICATORS
Function targets may be specified as either internally
operated or current operated by a minimum of 0.2A
through the output trip circuit. When current operated,
the output circuit must be limited to 30A for 0.2 sec-
onds, 7A for 2 minutes, and 3A continuously.
SURGE WITHSTAND CAPABILITY
Qualified to IEEE C37.90.1-1989, Standard Surge
Withstand Capability Test and IEC 255, Impulse Test
and Dielectric Test.
MECHANICAL
Operating Temperature
-40°C (-40°F) to +70°C (+158°F)
Storage Temperature
-65°C (-85°F) to +l00°C (+212°F)
Case Size: S1.
Weight
13.6 pounds (6.17Kg) maximum.
Shock
In standard tests, the relay has withstood 15g in each
of three mutually perpendicular planes without struc-
tural damage or degradation of performance.
Vibration
In standard tests, the relay has withstood 2g in each of
three mutually perpendicular planes, swept over the
range of 10 to 500 Hz for a total of six sweeps, 15
minutes for each sweep, without structural damage or
degradation of performance.

BE1-59N
6
CONNECTIONS
Figure 5 - Typical Control Circuit Connections
Figure 6 - Voltage Sensing Connections

BE1-59N
7
ORDERING
MODEL NUMBER
BE1-59N Ground Fault Overvoltage Relay
STYLE NUMBER
The style number appears on the front panel, drawout
cradle, and inside the case assembly. This style number
is an alphanumeric combination of characters identifying
the features included in a particular unit. The sample style
number below illustrates the manner in which the various
features are designated. The Style Number Identification
Chart (page 8) defines each of the options and character-
istics available for this device.
SAMPLE STYLE NUMBER: A5FF6JD1S3F
The style number above describes a BE1-59N Ground
Fault Overvoltage relay having the following features.
Sensing Input Type (A) Single-phase
Sensing Input Range (5) 120 Vac, 60 Hz
(nominal) with 1-20 Vac
pickup range
HOW TO ORDER:
Designate the model number followed by the complete
Style Number.
BE1-59N Style Number
Complete the Style Number by selecting one feature from
each column of the Style Number Identification Chart and
entering its designation letter or number into the appropriate
square. (Two squares are used to indicate time delay
characteristics.) All squares must be completed.
STANDARD ACCESSORIES:
The following accessories are available for the BE1-59N,
Ground Fault Overvoltage Relay.
Test Plug
The test plug (Basler part number 10095) provides a
quick, easy method of testing relays without removing
them from their case. The test plug is simply substituted
for the connection plug. This provides access to the
external stud connections and to the internal circuitry.
Extender Board
The extender board permits troubleshooting of the printed
circuit boards outside of the relay cradle. Order Basler
Electric part number 9165500100.
SAMPLE STYLE NUMBER ILLUSTRATED
Output (F) Two NO output relays: one for
the overvoltage function and one
for the undervoltage function
Timing (F6) Inverse for the overvoltage
function: definite time for the
undervoltage function
Power Supply (J) 125 Vdc and 100/120 Vac
Target (D) Two (one for each function),
current operated
Option 1 (1) Undervoltage element
Option 2 (S) Push-to-energize outputs
Option 3 (3) Two NO auxiliary output relays
(one per function)
Option 4 (F) Semi-flush mounting
NOTE: The description of a complete relay must include
both the model number and the style number.
Other manuals for BE1-59N
3
Table of contents
Other Basler Relay manuals

Basler
Basler BE1-50B User manual

Basler
Basler BE1-50-219 User manual

Basler
Basler BE1-50/51B-225 User manual

Basler
Basler BE1-50B-235 User manual

Basler
Basler BE1-79M User manual

Basler
Basler BE1-51/27R User manual

Basler
Basler BE1-51A User manual

Basler
Basler BE1-DFPR User manual

Basler
Basler BE1-51/27R User manual

Basler
Basler BE1-51B User manual

Basler
Basler BE1-27 User manual

Basler
Basler BE1-50M User manual

Basler
Basler BE1-51 User manual

Basler
Basler BE1-87T User manual

Basler
Basler BE1-50/51B-214 User manual

Basler
Basler BE1-46N User manual

Basler
Basler BE1-27 User manual

Basler
Basler BE1-50/51M-222 User manual

Basler
Basler BE1-59N User manual

Basler
Basler BE1-49 User manual