Baxi 720644701 Assembly Instructions

Installation & User’s Instructions
AUTO
1
7
6
5
4
3
2
MODE MENU
24
21
18
15
12
3
6
9
°C
Baxi Heating UK Ltd 2011
c
Please keep these instructions in a safe place. If you move house, please hand them over to the next occupier.
Part No. 720644701 7 day Wired Digital Programmer & Room Sensor
Part No. 720644801 7 day Wireless Digital Programmer & Room Sensor
Part No. 720644901 24hr Wireless Digital Programmer & Room Sensor
720644801 shown
B

1.0 Contents
2
1.0 Contents 2
2.0 Introduction 3
3.0 Programmer & Room Sensor Functions 4
4.0 Installation & Wiring 5
5.0 Wireless Room Unit 7
6.0 Manual Synchronization 8
of Wireless Units
7.0 Standby & Operating Mode 9
8.0 Central Heating & Domestic Hot 10
Water activation
9.0 Temperature Settings 11
10.0 Setting the Time & Day 12
11.0 Setting Central Heating & Domestic 13
Hot Water
12.0 Programmer & Room Sensor 14
Parameter Codes
13.0 Error Codes 15
Page
Baxi Heating UK Ltd 2011
c
Programmer & Room Sensor - 7 day Wired
Programmer & Room Sensor - 7 day Wireless
Programmer & Room Sensor - 24hr Wireless
Receiver
Batteries (AA/LR6)
Fixing Screws
Rawlplugs
Instructions
720644701
720644801
720644901
1
1
1
111
1
1
-
4
22
42
442
-
--
--
--
Kit contents
Table 1. Kit contents

2.1 General Introduction
2.2 Wireless versions (720644801 & 720644901)
2.0 Introduction
3
Fig. 2 Receiver
Fig. 1 Programmer & Room Sensor (720644801 shown)
AUTO
1
7
6
5
4
3
2
MODE MENU
24
21
18
15
12
3
6
9
°C
Boiler
Unit
AUTO
1
7
6
5
4
3
2
MODE MENU
24
21
18
15
12
3
6
9
°C
Boiler
Unit
Receiver
1. Specification of Units.
720644701 7 day Wired (for use with Neta-tec &
Duo-tec) is wired directly to your boiler unit (Fig. 3).
720644801 7 Day Wireless & 720644901 24h Wireless
(for use with Neta-tec, Duo-tec & Megaflo Compact) are
operated remotely via radio frequency wireless transmis-
sion to a Radio Frequency Receiver fitted close to the
boiler unit (Fig. 4).
2. The sensor constantly monitors the temperature of the
room in which it is installed. It can be operated in four
temperature modes, ‘Hi’ (or ‘COMFORT’), ‘Lo’ (or
‘REDUCED’), ‘Frost Protection’, or left in ‘Automatic’
(AUTO) to operate as programmed.
3. Depending on the settings, the boiler will run the ‘Hi’
COMFORT settings during a heating demand and the ‘Lo’
REDUCED setting for overnight periods or times when the
property is left unoccupied.
1. The units require 2 AA type alkaline batteries (Supplied).
Installation of the batteries is shown in Fig. 12.
2. If the battery symbol is seen flashing in the digital display
(Fig. 5) the batteries need replacing. See Fig. 12 for details.
3. The batteries have a lifespan of approximately 2 years.
Batteries should be changed within this timescale as a
precaution.
4. The Clock Function will need to be checked every time
the batteries are replaced.
Baxi Heating UK Ltd 2011
c
NOTE: If the batteries are left flat the unit will only retain
its settings for a maximum of one week.
NOTE: If the batteries are flat the boiler will return to a
default setting of Boiler ON.
AUTO
1
7
6
5
4
3
2
MODE MENU
24
21
18
15
12
3
6
9
°C
Fig. 3 Programmer & Room Sensor - Wired version
Fig. 4 Programmer & Room Sensor - Wireless version
Insulation Class II
IPX Rating IP44
Operating Temperature -5°C to 50°C
Transmission Frequency 868MHz
(Wireless only)
2.3 Technical Specifications

3.1 Description of Functions
3.0 Programmer & Room Sensor Functions
4Baxi Heating UK Ltd 2011
c
AUTO
1
7
6
5
4
3
2
MODE MENU
24
21
18
15
12
3
6
9
°C Current Time
Measured
Temperature
Battery life
(Replace if flashing)
Programme
and Time
Segments
Current Day
(1 = Monday)
(7 day version only)
Menu Button
Selector Button
Mode Button
Burner ‘ON’
Indicator
Communication
(Wireless only)
Central Heating
Domestic Hot
Water
REDUCED Mode
COMFORT Mode
Automatic Mode
Manual Mode
STANDBY
MODE
MENU
1
1
Press the
MENU
Button
Day of
the week
1= MON
(7 day only)
Day of
the week
selected
(7 day only)
Standby
selected
Central
Heating
(flashing = selected)
Signal
Strength
(flashing = no
signal)
Boiler runs
using User
defined
times
Boiler in
REDUCED
Mode
Boiler in
COMFORT
Mode
Press the
MODE
Button
Rotate the
Selector
Button
Press the
Selector
Button
Symbol Meaning Symbol MeaningSymbol Meaning
°C
AUTO
Time
(flashing = selected)
Temperature
(flashing = selected)
Domestic
Hot
Water
(flashing = selected)
Fig 5. Programmer & Room Sensor front view with functions
Table 2 Programmer & Room Sensor symbols & meanings

4.1 Installation
4.2 Connecting 720644701 7 day Wired
4.0 Installation & Wiring
720644701 7 day Wired
1. This Programmer & Room Sensor will take full control of
the boiler once fitted. All the boiler functions are
transferred to the Programmer & Room Sensor except
Chimney, Commissioning and the Combustion Adjustment
functions (Refer to the Boiler Instruction Manual).
2. The boiler must be fully commissioned before fitting this
Programmer & Room Sensor.
NOTE: Communication between the boiler and the
Programmer & Room Sensor can take up to 2 minutes to
establish. During this time, the boiler may attempt to fire
prior to communication being established.
3. If necessary, control can be transferred back to the
boiler. Either remove the unit from its cradle, or remove
the plug from the Receiver, then turn the power to the
boiler off and back on.
NOTE: The yellow link wire across terminals 1 & 2 on
the Boiler terminal block ‘M1’ must be removed when
fitting this Low Voltage control system. Fig. 6.
1. Power down the boiler.
2. Remove the backplate from the unit by pressing down
on the rear tab and easing apart. Fig. 12.
3. Identify a suitable site to locate the Programmer & Room
Sensor. See Fig. 8 for guidance on where to locate the unit.
4. Use a suitable grade of wire when connecting the
Programmer & Room Sensor to the boiler. A specification
of 2 x 0.75mm with a maximum length of 50m should be
used.
4. Pass the wires through the access slots in the backplate
and wire the terminals as shown in Fig. 6.
5. Screw the backplate to the wall using the fixings provided
and reattach the Programmer & Room Sensor.
6. Turn the power back on.
5
Baxi Heating UK Ltd 2011
c
123
Programmer & Room
Sensor Backplate
Min. 200 mm
MODE MENU
24
21
18
15
12
3
6
9
°C
MODE MENU
24
21
18
15
12
3
6
9
°C
MODE MENU
24
21
18
15
12
3
6
9
°C
MODE MENU
24
21
18
15
12
3
6
9
°C
1500mm
XX
Fig 6. Wiring details for 7 day Wired
720644701
Fig. 7 Connector Pins
Fig. 8. Location positions
2
Rear Tab
Boiler Wiring
Terminal M2
Low
Voltage
Terminal
Block
Boiler
Mains
Voltage
Terminal
Block M1
1
2
!
IMPORTANT
When fitting Low
Voltage Controls
remove the Yellow Link Wire
from the Boiler Terminal Block M1

4.0 Installation & Wiring (cont.)
NOTE: The yellow link wire across terminals 1 & 2 on the
Boiler terminal block ‘M1’ must be removed when fitting
this Low Voltage control system. Fig. 9.
1. The Receiver should be wired to the boiler as shown in
Fig 9.
2. Turn the power to the boiler off.
3. Remove the Receiver backplate by carefully prising it
away from the body. Fig. 10.
4. Route the wires through the rear of the backplate panel.
If a surface mount is required it will be necessary to break
off the appropriate tabs to give the wire access.
5. Connect the wires to the ‘OT’ connection on the
terminal block. Fig. 9. Note this is removable for ease of
wiring.
6. Connect the other end of the wire to the terminals on
the boiler. Please refer to the boiler manual for wiring
details.
7. Fix the Receiver to the wall using the fixings provided
and refit the front cover ensuring the correct orientation.
Fig 11.
8. Fit the batteries to the Programmer & Room Sensor.
Fig 12.
6Baxi Heating UK Ltd 2011
c
OT
OT
Fig. 9. Receiver Backplate
4.3 Connecting 720644801 7 day Wireless &
720644901 24h Wireless.
Fig. 12. Accessing batteries
Fig 11. Completed Receiver
1. Press Securing Tab.
1. Press Securing Tab.
2. Ease away from Backplate.
2. Ease Backplate away.
Fig 10. Receiver & Access Tab
2 x AA/LR6 Batteries
(Supplied)
Boiler Wiring
Terminal M2
Low
Voltage
Terminal
Block
Boiler
Mains
Voltage
Terminal
Block M1
1
2
!
IMPORTANT
When fitting Low Voltage
Controls remove the
Yellow Link Wire from the
Boiler Terminal Block M1

5.1 Boiler & Programmer Communication
5.0 Wireless Room Unit
7
1. The units are pre-synced so should communicate with
each other when powered up.
NOTE: Communication between the boiler and the
Programmer & Room Sensor can take up to 2 minutes
to establish. During this time, the boiler may attempt to
fire prior to communication being established.
2. If Error codes 83 or 85 are seen during commissioning,
there is a communication problem.
3. Error 83 is due to the Receiver not communicating with
the boiler. Check the wiring between the Receiver and
boiler. Fig. 9
4. Error 85 is due to the Programmer & Room Sensor not
communicating with the Receiver. The Programmer &
Room Sensor is either out of range or has not
synchronized correctly. Check the unit’s location (Fig 13)
or proceed to the Manual Sync process in Section 6.0
AUTO
1
7
6
5
4
3
2
MODE MENU
24
21
18
15
12
3
6
9
°C
Fig. 14 Remote unit Error Codes
Fig. 15 Signal Strength Test
Fig. 13 Maximum permitted separation
Boiler
Unit
Receiver
Error
85
Error
83
5. If Error 85 is seen after commissioning, check:
a) The Programmer and Room Sensor and the Receiver are
within range of each other. See Fig. 13 and Section 5.2
b) The units are synchronized correctly. Section 6.1.
c) The wiring is correct between the Receiver and boiler.
Fig. 9
6. The maximum distance between the Receiver and the
Programmer & Room Sensor will depend on the layout of
the house. For a typical house, a guideline of 3 floors or
walls can be used, as shown in Fig 13.
MODE MENU
24
21
18
15
12
3
6
9
°C
MODE MENU
24
21
18
15
12
3
6
9
°C
MODE MENU
24
21
18
15
12
3
6
9
°C
A
B
C
X
Before mounting the Programmer & Room Sensor to the
wall, perform the following test to determine the signal
strength. Fig 15.
1. Press and hold the Selector Button for approximately 6
seconds and HC 1 will be seen in the display.
2. Rotate the Selector Button until ‘tSt OFF’ is seen in the
display.
3. Press the Selector Button and OFF will flash. Rotate the
Selector Button until ON is seen.
4. Press the Selector Button to start the signal strength test.
The test may last for up to 8 minutes. During this time,
numbers ranging from 0 to 4 are displayed. ‘0’ indicates no
signal available and ‘4’ shows excellent signal strength Fig 15.
Baxi recommends locating the unit to give a signal strength
of 3 or 4. If the signal is low, move the unit to a more
suitable location and retest.
5. Press the Selector Button at any time to interrupt the
test or press MENU to escape once the test has finished.
6. If the Manual Sync. process needs to be carried out see
Section 6.0.
5.2 Test for Signal Strength
Baxi Heating UK Ltd 2011
c
Hold for 6 seconds
HC
1
tSt
OFF
tSt
OFF
tSt
ON
0 No Signal
1 Weak Signal
2 Poor Signal
3 Good Signal
4 Excellent Signal
Up to 8
minutes
test result
Retest
OK
Example A:
1 floor + 2 walls.
Example B:
2 floors + 1 wall.
Example C:
3 floors + no walls.

6.1 Synchronizing 720644801 7 day Wireless
& 720644901 24h Wireless
6.0 Manual Sync. Function
The Programmer & Room Sensor and the Receiver can be
synchronized using the method shown in Fig. 18 as follows:
1. Start by setting up the Programmer & Room Sensor.
Press and hold the Selector Button (Fig. 16) for approx. 6
seconds. ‘HC 1’ will be seen on the display.
2. Rotate the Selector Button until ‘SnC OFF’ is seen in the
display.
3. Press the Selector Button and ‘OFF’ will flash. This display
will only remain on the screen for approximately 60
seconds.
4. Now set up the Receiver. LED ‘L1’ will be flashing. Fig.
18. One of the following conditions will be seen.
1 One flash every 2 secs Boiler and Controller Synchronized.
2 Two flashes every 2 secs Communication error
3 Three flashes every 2 secs No communication yet
4 Flash for 1sec NA for Sync
5 1 sec flash every 1 sec Synchronization initialisation
See Fig. 27 for detailed description
5. If one flash is seen every 2 seconds, the boiler and
Programmer & Room Sensor are already synchronized.
Return to the Programmer & Room Sensor and press
Menu twice to exit the Synchronization menu.
8Baxi Heating UK Ltd 2011
c
AUTO
1
7
6
5
4
3
2
MODE MENU
24
21
18
15
12
3
6
9
°C
Hold for 6 seconds
Fig. 16. Programmer & Room Sensor
Selector Button
Fig. 18. Manual Sync Process Diagram
Fig. 17. Receiver LED Display
& Button
L1 L2
L1 L2
HC
1
SnC
OFF
SnC
End
Err
L1
Rapid Flash
Press &
hold until
slow flash
L1
Slow Flash
SnC
ON
OFF
SnC
OFF
SnC
OFF
Return
to
Controller
Go to
Receiver
Unit
Reposition
&
Retry
6. If L1 shows 3 flashes every 2 seconds the units are not
synchronized. Press and hold the Receiver Button until
the rapid flash at L1 changes to a slow flash.
7. Return to the Programmer & Room Sensor where
‘SnC OFF’ will be flashing. Rotate the Selector Button
until ‘SnC ON’ is seen. Press the Selector Button and
the display shows 4, 3, 2, 1 counting down. When this
process is complete, the unit will display ‘End’ if
synchronization has been successful. Press the Selector
Button to return to the ‘SnC OFF’ screen then press
MENU to escape.
8. If Error 85 is still displayed, the unit hasn’t synchronized
correctly. Return to the beginning and repeat the process.
. . . 4, 3, 2, 1
MENU

7.0 Standby & Operating Mode
9
Baxi Heating UK Ltd 2011
c
7.1 Standby and Operating modes
1. The controller can be set to either Standby Mode or
Operating Mode. In Standby, both the Central Heating and
Domestic Hot Water functions are switched OFF.
2. In Standby the Boiler Frost Protection function is still
activated and will fire the boiler if the temperature in the
boiler drops below 4°C.
3. In Operating Mode, the boiler will respond to any preset
Central Heating or Domestic Hot Water demand.
4. The screen display shows the current settings. Fig 19
shows the unit in Standby Mode. Fig 20 shows Operating
Mode.
1. To change the unit’s settings, follow the flow diagram
shown in Fig 21.
2. Press the Mode button and the Standby symbol will flash
and ‘OFF’ is shown in the main display. The Central Heating
and Domestic Hot Water symbols can also be seen.
3. Press the Selector Button once and ‘OFF’ will flash. The
Central Heating and Domestic Hot Water symbols
disappear.
4. Rotate the Selector Button clockwise until ‘On’ is seen in
the display.
5. Press the Selector Button once to confirm the selection
and then ‘Menu’ to return to the main screen. If Menu isn’t
pressed the display will return to the Main screen after
approximately 2 seconds. The unit is now in ‘Operating
Mode’.
Fig 21. Standby & Operating Mode Diagram
MODE
MENU
To Escape
(or wait 2 secs)
Confirm
Confirm
AUTO
1
7
6
5
4
3
2
MODE MENU
°C
Fig 19. Unit in Standby Mode.
AUTO
1
7
6
5
4
3
2
MODE MENU
°C
Fig 20. Standby turned off.
7.2 Changing Standby and Operating Mode settings
AUTO
1
7
6
5
4
3
2
AUTO
1
7
6
5
4
3
2
AUTO
1
7
6
5
4
3
2
AUTO
1
7
6
5
4
3
2
Table 3. Display Icons
AUTO
OFF Heating or Hot Water set to OFF
COMFORT room temperature
REDUCED room temperature
Domestic Hot Water setting
Hourly Central Heating programme
Hourly Domestic Hot Water programme
Time
Band
Time
Band
In AUTO, the boiler will heat the property to the
temperature set on the i-THINK Controller during
the programmed timed Heating periods
In REDUCED mode, the boiler will maintain a
minimum temperature in the property. If at any time,
day or night, the temperature falls below this value
the boiler will fire until the temperature is achieved.
In COMFORT, the boiler will constantly heat the
property to the temperature set on the i-THINK
Controller. NOTE: This will continue until the boiler
is taken out of COMFORT mode.

8.0 Central Heating & Domestic Hot Water ON
10 Baxi Heating UK Ltd 2011
c
1. Press the MODE button and rotate the Selector Button
until the flashing Central Heating symbol is seen in the
display. Fig. 22.
2. Press the Selector Button once to confirm the setting
and the OFF will flash.
3. Rotate the Selector Button to scroll through the options
available. In Central Heating, these are AUTO, REDUCED,
COMFORT and OFF. Press the Selector Button to confirm
the setting.
4. Press MENU to escape, or wait 3 seconds and the unit
will return automatically to the main display screen.
NOTE: A delay during this process will cause the unit to
revert back to the main screen. If this happens the process
must be restarted.
1. The Room Temperature can be increased or decreased
during a heating period by rotating the Selector Button to
give the required temperature. Press the Selector Button to
confirm the new setting.
2. The set temperature will return to the ‘Comfort’ mode
value at the next heating demand period.
1. For Combi boilers it is recommended that the Domestic
Hot Water setting is left in the ‘ON’ position. If it is
necessary to alter the setting follow the process shown in
Fig 22.
1. If the symbol ‘Sd’ appears in the display please contact
heateam as your boiler may require servicing. The contact
telephone number is shown on the back page.
8.1 Setting Central Heating to ON
8.3 Setting Domestic Hot Water to ON
8.4 Service Warning
MODE MODE
AUTO
REDUCED
COMFORT
OFF
MENU
To Escape
(or wait 3s)
MENU
To Escape
(or wait 3s)
Confirm
Confirm
OFF OFF
ON
ECO
OFF
Confirm
Confirm
8.2 Manual Override of Room Temperature
AUTO
1
7
6
5
4
3
2
24
21
18
15
12
3
6
9
°C
Fig 23. Typical Operating Modes.
7 day Wireless 7 day Wired 24h Wireless
AUTO
1
7
6
5
4
3
2
24
21
18
15
12
3
6
9
°C
AUTO
1
7
6
5
4
3
2
24
21
18
15
12
3
6
9
°C
Fig 22. Central Heating & Domestic Hot Water activation

11
Baxi Heating UK Ltd 2011
c
1. To set the Room Temperature, press the MENU button
and SC ON will appear in the display with the current
Room Comfort Set Point shown.
2. Press the Selector Button and the Comfort Set Point will
flash. This set point can be adjusted up or down by rotating
the Selector Button.
3. Press the Selector Button again to confirm the set point
and then press MENU to return to the main display screen.
The Comfort Set Point is now confirmed.
The Comfort Set Point can be increased or decreased
during a heating period by rotating the Selector Button to
give the required temperature. Press the Selector Button to
confirm the new setting. The set temperature will return to
the previous COMFORT mode value at the next heating
demand period.
1. To adjust the REDUCED set point, press the MENU
button and rotate the Selector Button until ‘Sr Ed’ appears
in the display.
2. Press the Selector Button to access the menu. The
current set point will be seen flashing. The set point can be
adjusted up or down by rotating the Selector Button.
3. Press the Selector Button again to confirm the set point
and then press MENU to return to the main display screen.
The REDUCED temperature is now confirmed.
1. To set the Domestic Hot Water temperature, press the
MENU button and rotate the Selector Button until ‘Sd HU’
appears in the display.
2. Press the Selector Button and the current temperature
set point will flash. The temperature can be adjusted up or
down by rotating the Selector Button.
3. Press the Selector Button again to confirm the
temperature and then press MENU to return to the main
display screen.
The Domestic Hot Water temperature is now confirmed.
1. To adjust the Outdoor Sensor value press and hold the
Selector Button for approximately 6 seconds to access the
parameter menu. Rotate the Selector Button until ‘otC’ is
seen in the display and press the Selector Button to access.
2. Set the required temperature compensation value from
the graph (Fig. 25) by rotating the Selector Button and
pressing to confirm. Press ‘MENU’ until the main screen is
displayed.
9.1 Setting the Room Temperature (Comfort)
9.3 Setting the REDUCED Temperature
9.4 Setting the Domestic Hot Water
9.5 Setting the Outdoor Sensor Curve
9.2 Manual Override of COMFORT setting
9.0 Temperature Settings
Fig 24. Temperature adjustment diagram
Fig 25. Outdoor Sensor Curve Graph
MENU
MENU
SC ON Sd HUSr Ed
SC ON Sd HUSr Ed
+ °C
- °C
°C °C°C
30
35
40
45
50
55
60
65
70
75
80
85
9.0 8.0 7.0 6.0 5.0 4.0 3.0
2.0
1.0
1.5
0
1520 10 5 0 -5
Outdoor Temperature
Example: For a minimum outdoor temperature of -10°C and
a required flow temperature of 80°C, the otC value should
be set to 3.0. For further details please see Outdoor Sensor
Kit - Part No. 720103001
Default Value
otC Menu Values
Boiler Flow Temperature
-10 -15 -20 NOTE: This function can not be set or displayed from the boiler
front panel when the Programmer and Room Sensor Controller
is fitted.

7 day version only
10.1 To Set the Time.
10.2 To Set the Day (720644701 7 day Wired &
720644801 7 day Wireless only).
10.0 Setting the Time & Day
12 Baxi Heating UK Ltd 2011
c
1. From the main display screen press MENU and rotate
the Selector Button until the clock is displayed. Fig. 26.
2. Press the Selector Button once and the hour will flash.
Rotate the Selector Button to increase or decrease the
time. Press the Selector Button once to confirm the hour
setting. The minutes display will now flash.
3. Rotate the Selector Button to set the minutes and press
the Selector Button once to confirm. The time is now set.
Press MENU until the main screen is displayed.
1. Set the Time as described above. Once the Time is
confirmed by pressing the Selector Button, the day symbols
on the right hand side of the screen will flash.
2. Rotate the Selector Button set the day. Monday = 1,
Tuesday = 2 etc. The current day is shown in a small circle.
Press the Selector Button to confirm.
3. The correct time and day should now be shown in the
display. Press MENU once to return to the main display
screen.
Confirm
Confirm
Confirm
MENU
+ hrs- hrs + min- min
+ day- day
Confirm
MENU
°C
1
6
5
4
3
2
7
1
6
5
4
3
2
7
1
6
5
4
3
2
7
1
6
5
4
3
2
7
NOTE: The clock will not update automatically so will
require manual adjustment.
7 Day
Version
Only
7 day version only
Fig. 26. Setting the Time & Day
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday

MENU
11.0 Setting Heating & Domestic Hot Water
13
Baxi Heating UK Ltd 2011
c
1. Press the MENU button and rotate the Selector Button
until ‘PCH’ is seen in the screen. Fig. 27. Press the Selector
Button once.
7-day version only: Press the Selector Button once and
‘Day 1’ (Monday) will be seen flashing. The display can be
set to either 7 individual days, 5 weekdays and 2 weekend,
or 7 days identical. The 24h version does not have ‘Day’
function displayed.
2. To set the day sequence, rotate the Selector Button until
the required day is displayed. Press the Selector Button to
confirm.
3. The screen displays the time and the letters ‘Pr’ flashing.
Press the Selector Button again and ‘On 1’ flashes.
(Pr = current setting, Pr1, Pr 2 & Pr 3 are presets).
4. Press the Selector Button again and the time flashes. The
first Timed ‘On’ period can now be set. Rotate the Selector
Button to set the desired Central Heating start time.
5. Press the Selector Button to confirm and the first timed
‘Off’ period flashes. Use the Selector Button to set the
required off period. Press the Selector Button once to
confirm.
6. Repeat the above process for ‘On 2’, ‘Off 2’, ‘On 3’ and
‘Off 3’ time periods. If only 2 Heating periods are required
set ‘On 2’ and ‘Off 2’ to the same time (e.g. 12:00).
7. After ‘Off 3’ has been set the screen will show the ‘On 1’
time flashing again. If Programming is complete, press
‘MENU’ repeatedly to return to the main display screen.
1. Press MENU and rotate Selector Button until ‘PdHU’ is
displayed. Fig. 27. Press the Selector Button to confirm and
repeat the sequence as described above.
11.1 Setting the Central Heating
11.2 Setting the Domestic Hot Water
1234567
1234567
12345 67
MENU
00:00
Pr
00:00
On 1
7 day
24h
Preset Programmes
Pr1 Pr2 Pr3
OFF OFF OFFOn 2 On 3
00:00
On 1
00:00
OFF
00:00
On 3
00:00
OFF
00:00
On 2
00:00
OFF
PCH PdHU
Fig. 27. Setting Central Heating & Domestic Hot Water

12.1 Programmer & Room Sensor Functions
12.0 Parameter Codes
14 Baxi Heating UK Ltd 2011
c
HC Assigns the Programmer & Room Sensor to heating circuit.
.Ao Sets the Programmer & Room Sensor as Master (CEn).
rtE Enables the USER to adjust the reduced room temperature setting
dh Enables the USER to adjust the DHW temperature and hourly programming
Sets the DHW mode: 24h: DHW always active
rEL CHP: DHW is enabled according to the CH hourly programme
DhP: DHW is enabled according to the DHW hourly programme
oFS Sets the offset of the room sensor. Used to correct the temperature value read by the
sensor if this differs from the actual temperature.
Un Selects the temperature unit of measurement (°C or °F)
SoFt Displays the software version
oSt Not used
oSp Not used
tLr Not used
Enables / Disables room anti-freeze function (from +4° C to reduced room temperature)
ICE OFF = disabled
4°C = settable
otC Sets the kt curve for external weather sensor 720103001 (0.1 – 9.0). (See Section 9.5)
rtS Enables (ON) / Disables (OFF) the room sensor.
Mod. Enables (ON) / Disables (OFF) room temperature modulation.
ULt Sets the maximum CH flow temperature (Max CH)
TSP Accesses the “Pxx” board parameters menu
Snc Synchronization of Programmer & Room Sensor (720644801 & 720644901) with the boiler.
Refer to Sections 5 and 6 of this manual
TSt Radio transmission test (WIRELESS only). The function lasts 8 minutes or when the Selector
Button is pressed. The display shows the numbers 1 to 4 (1=25% - 4=100%)
End To return to the main screen.
Display Description Default
1
CEn
Enabled
Read only
Enabled
0
°C
N/A
N/A
N/A
4°C
1.5
ON
ON
85°C
- - -
Combi
24h
1. To access the Menu, press and hold the Selector
Button for approximately 6 seconds. The parameters can
be accessed by rotating the Selector Button.
*
* Adjustment is required for Low Temperature or Underfloor heating systems.
Table 4. Parameter codes

13.0 Error Codes
1. Some error codes can be reset. If an error code is seen
in the display use the reset procedure to try and remove
the fault. Fig. 29.
2. Press the Selector Button once and rotate immediately
until ‘rSt’ is shown in the display.
3. Press the Selector Button again and the error should
reset. If the error doesn’t reset, consult the boiler manual
for further information.
1. Press the Selector Button once and ‘000’ will be
displayed.
2. Rotate the Selector Button until ‘015’ is seen is the
display.
3. Press the Selector Button once and ‘Service Due’ will
clear. Fig 30.
NOTE: Resetting this function without completing the
required service will invalidate your warranty.
1. If necessary, control can be transferred back to the
boiler. Either remove the unit from its cradle, or remove
the plug from the Receiver, then turn the power to the
boiler off and back on.
15
Baxi Heating UK Ltd 2011
c
2s 2s
L1 Flash L1 Flash L1 Flash
Normal
Operation
Wired - No
Communication
between Boiler
& Transmitter
L1 Flash x 2 L1 Flash x 2 L1 Flash x 2
2s 2s
Wireless - No
Communication
between Room
Unit & Transmitter
L1 Flash x 3 L1 Flash x 3 L1 Flash x 3
2s 2s
Initialization
Phase between
Transmitter
& Boiler
L1 Flash L1 Flash
Parameter
Change
L2 Flash
2s 1s
Receiver L1 L2
1s 1s 1s 1s
Programmer & Room Sensor Error Codes (See Sec. 5.1)
85 Error between Programmer & Room Sensor
& Receiver
83 Error between Boiler & Receiver
13.1 Error Codes
13.2 Resetting the ‘sd’ - Service Due Code
13.3 Boiler Control
Gas Valve Connection Cable
Gas Valve Fault
Central Heating NTC Fault
Flue NTC Fault
Central Heating Return NTCFault
Pre-circulation Fault
Safety Thermostat Operated
Primary System Water Pressure Too High
Primary System Water Pressure Too Low
Circulation Fault (Primary)
Flame Failure
Flue NTC Operated
Interruption Of Gas Supply or Flame Failure
Elapsed Time - Gas Valve Open Without Gas
Interruption Of Gas Supply (Internal Error)
Flow/Return Sensor Temperature Test
Fan or Fan Wiring Fault
Circulation Fault (Dry Fire)
Hot Water NTC Fault
False Flame
09
15
20
28
40
109
110
117
118
125
128
130
133
134
135
154
160
270
321
384
Table 5. Error Codes
Calibration Required
55
rSt
Fig 28. Receiver status indicator LEDs
Fig 29. Resetting Error Codes
000 015
Fig 30. Resetting the Service Due Code.

1.0 X X X X X X X X X X X
Comp No. 720898904 (12/11)
All descriptions and illustrations provided in this leaflet have been carefully
prepared but we reserve the right to make changes and improvements in
our products which may affect the accuracy of the information contained
in this leaflet. All goods are sold subject to our standard Conditions of Sale
which are available on request.
BAXI
A Trading Division of Baxi Heating UK Ltd (3879156)
Brooks House, Coventry Road, Warwick. CV34 4LL
After Sales Service 0844 871 1525 Technical Enquiries 0844 871 1555
Website www.baxi.co.uk
e&oe
Baxi Heating UK Ltd 2011
c
This manual suits for next models
2
Table of contents
Other Baxi Thermostat manuals