Bedrock UPS.500 User manual

UPS.500
Quick Start Guide

The UPS.500 contains lithium-ion batteries. The product is not
field-serviceable. Contact Bedrock Automation for instructions on
returning the UPS.500.
Never attempt to open the UPS.500 enclosure. The enclosure is
securely sealed. Opening the enclosure will void the warranty and
cause the UPS.500 to be inoperable.
Always use an appropriate fuse on the power in and power out
connections.
For both the panel and pipe mount configurations, it is required
that the UPS.500 mounting bracket is grounded.
Important User Information
Select an input power supply with a rating that is greater than the
UPS.500 power consumption which can be calculated as follows:
((output voltage x configured current limit) +
configured charge power)
The UPS.500 contains lithium-ion batteries. The output port may
carry voltage even when the UPS.500 is not connected to a power
source.
Prior to connecting the cables, read this guide thoroughly, paying
attention to important electrical and safety information.

1 - Status LEDs
Ethernet Activity
Ethernet Link
Tri-color UPS Status

2 - Ports
Note: Bedrock part no. CI00100 or Phoenix
Contact part no. 1656990 must be
used for the Ethernet connector in
order to maintain the IP66/IP67 rating.
Note: A shielded
Ethernet cable is
required.
Power
Out
Power
In Relay
Enable
Ethernet

3 –UPS.500 Block Diagram
Dual
Ideal
Diode
Controller
Dual
Relays
Regulator
Line
In
Enable
DC
Out
Ethernet
Port
Battery
Pack
Charging
Circuit
Microcontroller
Ethernet
Controller
Relay
Input A
Input B
Output
Control
Control

4 –General Wiring Diagram
Note: Battery Enable Connector must be connected prior to power up
Load
Power
Supply
Recommended
Fusing
Power
Out
Power
In
Recommended
Fusing
To Discrete
Inputs for
Alarming Relay
Output
(optional)
Ethernet
24 V Power Supply
Battery
Enable
Connector
Select an input power supply with a rating that is
greater than the UPS.500 power consumption which
can be calculated as follows:
((output voltage x configured current limit) +
configured charge power)
One of the
following:
Workstation
Running
OPC UA
Bedrock
SIO4.E comm.
module
UCG.5
OSA Remote

5 –Bedrock Configuration
Note: Battery Enable Connector must be connected prior to power up.
Bedrock Configuration only valid with SPS.500
One of the
following:
Workstation
Running
OPC UA
Bedrock
SIO4.E comm.
module
UCG.5
OSA Remote
Load
(SPM)
SPS.500
Recommended
Fusing
Power
Out
Power
In
Recommended
Fusing
To Discrete
Inputs for
Alarming Relay
Output
(optional)
Ethernet
Battery
Enable
Connector
Ethernet
Input B
Input A
ORed
Output
Field
Devices
Recommended
Fusing

6 –Parts List (Panel Mount)
1
2
3
ITEM
NO.
DESCRIPTION
QTY.
1
UPS.500 ASSEMBLY
1
2
#14 x 1” SELF TAPPING
SCREW
4
3
UPS MOUNTING BRACKET
1
Use Bedrock Part No. MI00128 when ordering the
UPS Mounting Bracket Assembly (Panel Mount)

7 –Parts List (Pipe Mount)
1
2
4
Use Bedrock Part No. MI00127 when ordering the
UPS Mounting Bracket Assembly (Pipe Mount)
ITEM
NO.
DESCRIPTION
QTY.
1
UPS.500 ASSEMBLY
1
2
3/8”-16 x 3/4 HEX BOLT
4
3
UPS MOUNTING BRACKET
1
4
2” SCHEDULE 40 PIPE
MOUNTING BRACKET
1
5
3/8”- WASHER
4
6
3/8”-16 HEX NUT
4
3
5
6

8 –Mount UPS
2
1

9 –Clamp UPS
4
3
3

10 –Open Shroud

CAUTION: See panel 17 for relay
contact rating specification.
11 –UPS Cables
Note: See panel 12 for pin out tables.
Connect drain wire to panel ground.
Power In
Power Out
Relay
PIN 1
PIN 2
PIN 3
PIN 4
PIN 5
PIN 6
DRAIN WIRE
PIN 1
PIN 2
PIN 3
PIN 4
PIN 5
PIN 6
DRAIN WIRE
DRAIN WIRE
PIN 6 RELAY B (NO)
PIN 5 RELAY B (COM)
PIN 4 RELAY B (NC)
PIN 3 RELAY A (NO)
PIN 2 RELAY A (COM)
PIN 1 RELAY A (NC)
Bedrock Part No. UPSPOWRIN
Bedrock Part No. UPSPOWOUT
Bedrock Part No. UPSRLYCBL

12 –Cable Pin Outs
Power In
Power Out
Relay
Pin/Wire
Function
Color
PIN 1
RELAY A (NC)
BLACK
PIN 2
RELAY A (COM)
RED
PIN 3
RELAY A (NO)
WHITE
PIN 4
RELAY B (NC)
GREEN
PIN 5
RELAY B (COM)
ORANGE
PIN 6
RELAY B (NO)
BLUE
PIN 7
DRAIN WIRE
N/A
NOTE: Cable length should not
exceed 9 meters (29.5 ft.).
Note: Figures show the connector end of each cable.
Pin/Wire
Function
Color
DRAIN WIRE
GROUND
N/A
PIN 1
24 V DC
RED
PIN 2
24 V DC
RED
PIN 3
24 V DC
RED
PIN 4
24 V RET
BLACK
PIN 5
24 V RET
BLACK
PIN 6
24 V RET
BLACK
Pin/Wire
Function
Color
DRAIN WIRE
GROUND
N/A
PIN 1
24 V DC
RED
PIN 2
24 V DC
RED
PIN 3
24 V DC
RED
PIN 4
24 V RET
BLACK
PIN 5
24 V RET
BLACK
PIN 6
24 V RET
BLACK
NOTE: Cable length should not
exceed 9 meters (29.5 ft.).
CAUTION: Each contact is rated for 10 amps at
25°C. In order to support full capacity,
all wires must be connected to their
respective contacts.
CAUTION: Each contact is rated for 10 amps at
25°C. In order to support full capacity,
all wires must be connected to their
respective contacts.

13 –Enable Connector
The enable connector must be
connected before the power input
cable for the UPS.500 to be operable.
Remove the enable connector prior to
transporting the UPS.500
Enable
Connector
Use Bedrock Part No. MI00097 when ordering the Enable Connector

14 –Cable Alignment
Step 1: Align open arrow with arrow on mating
connector and then press together.
Step 2: Rotate ¼ turn clockwise to the locked
position.
1
2

15 –Cables Connected

16 –Shroud Closed

17 - Specifications
UPS.500 Hold Up Time (reflects fully charged pack)
12 amps
45 minutes
10 amps
75 minutes
8 amps
105 minutes
6 amps
135 minutes
4 amps
165 minutes
2 amps
180 minutes
UPS.500 General Specifications
Communication/output ports:
Two Type C relay contacts rated
Max switching voltage
125 V DC, 150 V AC
Max switching current
1 amp resistive load
One 10/100 Ethernet port with:
IEEE-1588 timestamp
OPC UA supporting one client
Status indicators:
Tri-color status LED
See UPS.500 LED Status Codes Table
Yellow Ethernet link LED
On indicates Ethernet link
Yellow Ethernet activity LED
On indicates Ethernet activity
Dimensions
Height
235 mm (9.25 inches)
Depth
159 mm (6.25 inches)
Width
292 mm (11.5 inches )
Weight
11.34 kg (25 pounds)
Enclosure
IP66/IP67
NEMA Ratings: 4, 5, 6
Metal: Aluminum
Coating: Electroless nickel plated
UPS.500 Electrical Specifications
Input voltage
22-26 volts
Hold up time
See UPS.500 Hold Up Time Table
Maximum load current
12 amps
Maximum total input current
18 amps (12 amps load + 6 amps charging)
Short circuit current
20 amps maximum (see Overcurrent Behavior in the
Bedrock UPS.500 User Manual)
Maximum load capacitance
8000 µF
Standby power
< 2.5 watts
Charging power
Programmable: 48 watts to 140 watts
Charging time
4 to 10 hours (dependent upon configured charging
power)
Charging current
1 to 6 amps (dependent upon configured charging
power)
Output voltage range
Input voltage minus 0.3 volts

18 –Specifications and Certifications
UPS.500 Environmental Specifications
Operating temperature
-10°C to 60°C
Storage temperature
-20°C to 60°C
Operating humidity
5% to 100% relative humidity
CE Testing - European EMC Directive 2014/30/EU including:
EN 61326-1 EMC Requirements
IEC 61000-4-4 EFT / Burst Immunity
CISPR 11: 2010 Radiated Emissions
IEC 61000-4-5 Surge Immunity
IEC 61000-4-2 ESD Immunity
IEC 61000-4-6 Conducted RF Immunity
IEC 61000-4-3 Radiated RF Immunity
IEC Environmental Testing
IEC 60068-2-27
Shock
IEC 60068-2-6
Vibration
FCC Testing
CFR FCC Part 15 Subpart B, Class A (2016)
Radiated Emissions
EMP Testing
MIL-STD-461-E
Requirement RS105
Radiated Susceptibility
Transient Electromagnetic Field
Safety Certifications
UL 508
Industrial Control Equipment
UL 121201
Class I Division 2 Hazardous Locations
CE mark
UPS.500 LED Status Codes
System State
Color
Number of Blinks and Duration
Normal, battery pack ready
Green
Steady
Normal, battery pack charging
Orange
1 blink –repeats while condition persists
Normal, one or more cells ~85% or more
charged while pack is charging
Green
1 blink –repeats while condition persists
Main power failure
Blue
1 blink –repeats while condition persists
Main power failure, battery pack depleted
Red
1 blink –repeats while condition persists
Main power recovery
Blue
4 blinks –repeats while condition persists
Overcurrent when running on battery
Blue/Red
Alternates while condition persists
Overcurrent when running on 24 V input
Green/Red
Alternates while condition persists
Fault
Red
4 blinks –repeats until fault cleared
Brownout condition
Blue
Steady
Security Certification
Achilles Communication Level 2 Certification
UPS.500 Network Robustness
Other manuals for UPS.500
3
Table of contents
Other Bedrock UPS manuals
Popular UPS manuals by other brands

Fortress Technologies
Fortress Technologies LI 660 Replacing Guide

CyberPower
CyberPower CP350SLG user manual

Toshiba
Toshiba G9000 SERIES Installation and operation manual

WÄRTSILÄ
WÄRTSILÄ JOVYTEC L Series operating manual

Altronix
Altronix RESERV ReServ5WP installation guide

Tescom
Tescom T-3250 user manual