BEIER-Electronic SV1-2-10Z User manual

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 1
Instruction Manual
Controller
Typ: SV1-2-10Z
BEIER-Electronic
Winterbacherstr. 52/4, 73614 Schorndorf - Weiler
Telefon 07181/46232, Telefax 07181/45732

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 2
Table of Contents
Table of Contents....................................................................................................... 2
Dangers caused by Electric Power............................................................................. 3
Safety-Technical Indications for the User................................................................... 4
General Description of the Device.............................................................................. 5
Technical Data............................................................................................................ 6
Technical Data............................................................................................................ 7
Technical Data............................................................................................................ 8
Technical Data............................................................................................................ 9
Wiring Diagram......................................................................................................... 10
Wiring Diagram (Min/Max-Mode).............................................................................. 11
Technical Description ............................................................................................... 12
Technical Description ............................................................................................... 13
Technical Description ............................................................................................... 14
Technical Description ............................................................................................... 15
Technical Description ............................................................................................... 16
Technical Description ............................................................................................... 17
Technical Description ............................................................................................... 18
Technical Description ............................................................................................... 19
Technical Description ............................................................................................... 20
Technical Description ............................................................................................... 21
Electrical Equipment................................................................................................. 22

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 3
Dangers caused by Electric Power
Emergency !
In the case of danger caused by electric power,
shut-down the machine immediately by means of
the main switch!
Warning!
Damages on the machine may result therefrom.
Operate the controller only with faultless condition of the electrical
equipment. When damages are recognized: Immediate shut-down of the
controller, switch-off by means of the main switch and have it repaired!
Put controller back to use only, if the faultless condition of the electrical
equipment has been verified by an electrician.
In the case of disturbances in the electrical power supply, the controller must
be switched off immediately!
Only use original fuses with the current intensity specified in the Technical
data sheet!
Connecting cables and leads must be laid so that damages and dangers are
excluded and impossible.
Work on the electrical equipment may only be carried out by electricians or
instructed personnel under the supervision of electricians, according to the
electrical-technical regulations in force.

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 4
Safety-Technical Indications for the User
The following indications are for the purpose of personal safety of the operators, as
well as for the safety of the described products and the connected devices.
Non-observance may result in death, serious injuries of the body or damage to
property!
Warning!
Before opening the device
the mains plug must be disconnected.
•Before setting the device into operation the accordance of the mains voltage of
the controller and the feeding device with the local mains voltage must be verified.
•Set and connect plugs, plug link, slide switch according to technical description!
•The set-up is to be carried out by technically qualified personnel!
•Only inductive loads may be connected to the controller!
•Check the electrical equipment of the controller at least once a week for visible
damages and defaults on the outside!
•Detected defaults as well as changes in the operation behavior must be reported
immediately to the person / dept. in charge. Immediate shut-down and securing of
the controller, if required!
Check the electrical equipment of the controller regularly in accordance with the
respective national regulations.

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 5
General Description of the Device
Power unit
The SV1-2-10Z is a control device for oscillation conveyor drives with electromagnets
and works according to the principle of a frequency converter. This control is setting
standards as regards feeding performances, operating comfort and energy savings.
In spite of its very compact construction design the control device SV1-2-10Z covers
the performance range that is usual with vibration feeding devices. As standard finish
the device is equipped with soft start and soft run-out, which can both be adapted at
any time to the connected oscillation conveyor drive.
By means of the external, potential-free control input 10 - 30V AC or DC, the
SV1-2-10Z can be enabled or disabled.
In applications with frequent switching functions (e.g. level control), the
controller may be not constantly switched via the mains voltage! In this case
the control input must be used, since otherwise the life span of the controller
is limited!
All settings, like e.g. set-point input or frequency input are done by means of menue-
assisted key inputs at the front plate.
A 16-digit LC-Display and a status LED inform at any time about the current state of
the SV1-2-10Z.
The electronic current control prevents a possible overload of the control device and
the conveyor system.
Within the indicated limit values there is no setting required for the mains voltage and
mains frequency.
Power supply
The SV1-2-10Z disposes of a switch-controlled 24V DC power pack. It is used for the
supply the internal time function elements, the connected proximity switches and the
outputs (blast air, control output). The power pack is short circuit-proof and can
supply current of max. 1,5A.
Time function elements
The integrated time function elements have an extensive logic (see page 10+11). A
total of 8 times is available enabling the realisation of different functions. These times
can be set from 0,0 to 25,0 seconds.
The SV1-2-10Z is compatible with control SV1-2-10Z. Furthermore, by means of an
optional Input a 2-Sensor min/max level control is also possible.
By a second, adjustable, set-point value e.g. single counter operations can be dosed
more exactly.

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 6
Technical Data
Mains voltage 110 - 230V AC +/-10%
Mains frequency 50 / 60Hz +/-1%
Output voltage 0 - 220V (at 230V mains voltage)
Output current per feeding
device max. 2,5 / 6,0A internal selectable.
With heat sink max. 10,0A
Output frequency 10,0 - 150,0Hz (resolution 0,1Hz)
Load max. 2200 VA. Only inductive loads are allowed to
be connect!
Device fuse 6,3A melting fuse (5x20mm)
Control fuse 1A melting fuse
Electronic over-current
disabling At approx.. 3,5 / 14,0A
Control input 10 – 30V AC or DC (potential-free)
Insulation Voltage Input/Output 0,5kV
Input for set-point selection 10 – 30V AC or DC (potential-free)
Insulation Voltage Input/Output 0,5kV
Inputs for proxmity switches 4 inputs: 10-30V DC
Outputs 4 pnp-outputs: 24V DC, max. 0,5A
1 relay-output: 230V, max. 5A
Soft start 1,0 – 5,0 seconds
Soft run-out 0,2 – 5,0 seconds
Time function elements 4 time function elements with adjustable turn-
on/turn-off delay (0,0 – 25,0 seconds)
Display 16 digit LCD and status-LED
Ambient temperature 0 – 40°C
Dimensions Aluminum housing 160 x 160 x 90mm
Type of protection IP54

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 7
Technical Data

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 8
Technical Data
K51
140
110
160
160
F1
F2
X51
X1
X21
X11
X0

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 9
Technical Data
X0 Connection for mains voltage
X1 Connection for feeding device
X11 Connection for external control input
X12 Connection for control output
X13 Connection for set-point selection
X14 Connection for malfunction output
X15 Connection for optional input
X21 Connection for proximity switch
X31 Connector for blast air valve 1
X32 Connector for blast air valve 2
X41 Connection for proximity switch
X42 Connection for proximity switch
X50 Connection for inputs, outputs and time function elements
X51 Bridge -/PE, relay contacts K51
Q1 Main switch
H1 Status-LED
H2 LC-Display
S1 Key ‚Menue‘
S2 Key ‚Cursor‘
S3 Key ‚Minus‘
S4 Key ‚Plus‘
S5 Key ‚Enter‘
S11 DIP-switch for miscellaneous settings (page 15)
S12 DIP-switch for miscellaneous settings (page 15)
S13 DIP-switch for miscellaneous settings (page 15)
F1 Melting fuse 6,3A
F2 Melting fuse 6,3A
F3 Melting fuse 1A

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 10
Wiring Diagram

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 11
Wiring Diagram (Min/Max-Mode)

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 12
Technical Description
Pin assignment X0 (Voltage supply)
Pin 1: L1
Pin 2: free
Pin 3: N
Pin PE: PE
Pin assignment X1 (Feeding device)
Pin 1: output
Pin 2: output
Pin 3: free
Pin PE: PE
Pin assignment X11 (Control input)
Pin 1: free
Pin 2: free
Pin 3: 10-30V DC or AC
Pin 4: 10-30V DC or AC
As for the control input, the polarity of the voltage need not be taken into account.
X12 (Connection for control output)
X50 / Pin 23: output (Out)
X50 / Pin 25: -DC
X13 (Connection for set-point selection)
X50 / Pin 14:10-30V DC oder AC
X50 / Pin 15:10-30V DC oder AC
As for the set-point selection, the polarity of the voltage need not be taken into
account.
X14 (Connection for malfunction output)
X50 / Pin 30:Output (Out)
X50 / Pin 31:- DC
X15 (Connection for optional input)
X50 / Pin 16:+24V DC
X50 / Pin 17: Signal
X50 / Pin 18:- DC
PIN assignment X21 (Proximity switch)
Pin 1: +24V DC
Pin 2: free
Pin 3: -DC
Pin 4: Signal

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 13
Technical Description
X31 (connector for blast air valve 1)
X50 / Pin 27: output (Out)
X50 / Pin 28: - DC
X32 (connector for blast air valve 2)
X50 / Pin 29: output (Out)
X50 / Pin 30: - DC
X41 (Proximity switch)
X50 / Pin 13: +24V DC
X50 / Pin 14: Signal
X50 / Pin 15: - DC
Adhesive label inside the controller
PE
PE
3
1N
L1
X0
Ext. Start/Stop
4
3
X11
10-30V AC/DC
S11.1
ON
OFF
inv.
n. inv.
4
3
1
X21 +24V
_
Signal
26 27 28 29
X31
DC 24V max. 0,5A
X50
Out
_
X32
Out
_
789 11 12 13
+24V
Signal
+24V
Signal
_
X41 X42
X50
_
22 23 24 25
X12
X50
Out _
DC 24V max. 0,5A
Sollwert-Auswahl
X13 10-30V
AC/DC
14 15
X50
30 31
DC 24V max. 0,5A
X50 X14
Out
_
PE 41 42 43-X51
0V
PE
K51 max. AC230V / 5A
39
X50
F1
6,3A MT
F2
6,3A MT
Inductive
load only !
PE PE
3
2
X1 1

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 14
Technical Description
Soft start T01 ON
When switching the controller on by means of the mains voltage or by the control
input or a time function element, the feeding device does not start feeding abruptly
with the set performance; it is „accelerated“ by means of a time ramp. The length of
the time ramp can be set in menue line “D” and is about approx. 5 seconds
maximum.
Soft run-out T01 OFF
If the controller is disabled via the control input or time function element, the feeding
device does not stop abruptly; it is „decelerated“ by means of a time ramp. The
length of the time ramp can be set in menue line “D” and is about approx. 5 seconds
maximum.
Time function elements T41-T45
The time function elements have a rise-delay time (ON) and a down-delay time
(OFF). Die Times can be set in the menue lines “E” – “H”.
Status display H1
With the aid of the status-LED the current state of the SV1-2-10Z controller can be
instantly recognised.
Status-LED State
Green continuous light Selection via control input available. Feeding
device is ON
Green flashing light No selection via control input. Feeding
device is OFF
Red continuous light Over-current has occurred ÆDisplay on
Indicator ‚ !!! OVERLOAD !!! ‘.
or
Over-temperature has occurred ÆDisplay
on Indicator ‚ OVERTEMPERATURE! ‘.
Green flashing light + red continuous
light The mains voltage supply has just been
switched OFF ÆDisplay on Indicator
‚ POWER OFF ! ‘.
LED dark No voltage supply.

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 15
Technical Description
DIP-switch S11
OFF DIP-switch S11 ON
No inverting of control input
X11 1 Inverting of control input X11
No inverting of input X21 2 Inverting of input X21
No inverting of input X41 3 Inverting of input X41
No inverting of input X42 4 Inverting of input X42
Without blast air 1 (X31) 5 With blast air 1 (X31)
Without blast air 2 (X32) 6 With blast air 2 (X32)
Control output X12 without
control input X11 7 Control output X12 with control
input X11
Control output X12 for following
device without T44 8 Control output X12 for following
device with T44
DIP-switch S12
OFF DIP-switch S12 ON
Feeding device X1 without T43 1 Feeding device X1 with T43
Standard OFF 2 Change of access enable
Standard OFF 3 Change code
Standard OFF 4 Change I-MAX
Without Set-point value 2 5 With Set-point value 2
Current range 2,5A 6 Current range 10A
Current waveform ‚Trapez‘ 7 Current waveform ‚Sinus‘
Always on OFF 8 ---
DIP-switch S13
OFF DIP-switch S13 ON
No inverting of input X15 1 Inverting of input X15
Standard mode 2 Min/Max mode
Reserve 3 Reserve
Reserve 4 Reserve
Reserve 5 Reserve
Reserve 6 Reserve
Delivery settings:
S11.1 S11.2 S11.3 S11.4 S11.5 S11.6 S11.7 S11.8
ON ON ON ON OFF OFF ON ON
S12.1 S12.2 S12.3 S12.4 S12.5 S12.6 S12.7 S12.8
ON OFF OFF OFF OFF ON ON OFF
S13.1 S13.2 S13.3 S13.4 S13.5 S13.6
OFF OFF OFF OFF OFF OFF

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 16
Technical Description
Menue lines
Menue line ‚A‘
A 5 0 , 0 1 0 0 , 0 7 , 5
Set-point value2 Set-point value1 Measured current
In Menue line ‚A‘ the two set-point values as well as the measured current (in A) are
displayed. The set-point values can be set in 0,5% steps between 0,0% and I-MAX
(see Menue line ‚B‘). This directions refer always to the set output current range (see
DIP-Switch S12.6). The set-point value 2 is only displayed if it has been released by
switch S12.5. The changeover between set-point value 1 and 2 is done by Input X13.
If this input is selected, set-point 2 is active, otherwise set-point1.
Menue line ‚B‘
B 0 5 0 % = 1 , 2 A 2 , 5 A
Maximum current Current range
In menue line ‚B‘ the maximum output current can be limited. Through that, the
connected feeding device can be protected from overloading. Furthermore, the
current range set with DIP-Switch S12.6 is displayed.
Attention: In this menue the value can only be changed by actuating DIP-Switch
S12.4.
Menue line ‚C‘
C f =1 2 0 , 4 Hz
Set frequency
In this menue the output frequency is displayed resp. adjusted. An adjustment
between 10,0 and 150,0 Hz is possible.
Menue line ‚D‘
D T 0 1 = 2 , 0 1 , 0
Soft start Soft run-out
In Menue line ‚D‘ the soft start and soft run-out can be set. Values between 1,0 and
5,0 seconds are possible.

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 17
Technical Description
Menue line ‚E‘
Input Output
E T 4 1 =• 0 7 , 5 • 1 1 , 8
Rise-delay time Down-delay time
In Menue line ‚E‘ the rise-delay time and down-delay time of the time function
element T41 is set. Values between 0,0 and 25,0 seconds are possible. The in- and
output of the time function element is represented by a dot in front of the number.
Menue line ‚F‘
Input Output
F T 4 2 =• 0 7 , 5 • 1 1 , 8
Rise-delay time Down-delay time
In Menue line ‚F‘ the rise-delay time and down-delay time of the time function
element T42 is set. Values between 0,0 and 25,0 seconds are possible. The in- and
output of the time function element is represented by a dot in front of the number.
Menue line ‚G‘
Input Output
G T 4 3 =• 0 7 , 5 • 1 1 , 8
Rise-delay time Down-delay time
In Menue line ‚G‘ the rise-delay time and down-delay time of the time function
element T43 is set. Values between 0,0 and 25,0 seconds are possible. The in- and
output of the time function element is represented by a dot in front of the number.

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 18
Technical Description
Menue line ‚H‘
Input Output
H T 4 4 =• 0 7 , 5 • 1 1 , 8
Rise-delay time Down-delay time
In Menue line ‚H‘ the rise-delay time and down-delay time of the time function
element T44 is set. Values between 0,0 and 25,0 seconds are possible. The in- and
output of the time function element is represented by a dot in front of the number.
Key functions
Key (Menue)
By means of this key it is possible to page among the different menue lines. Upon
each key actuation a jump to the next menue line is executed (A ÆB ÆC ÆD ÆE
ÆF ÆG ÆH ÆA)
Menue line ‚A‘ Set-point values / measured current
Menue line ‚B‘ Maximum output current
Menue line ‚C‘ Output frequency
Menue line ‚D‘ Soft start / soft run-out
Menue line ‚E‘ T41 ON / T41 OFF
Menue line ‚F‘ T42 ON / T42 OFF
Menue line ‚G‘ T43 ON / T43 OFF
Menue line ‚H‘ T44 ON / T44 OFF
Key (Enter)
By mean of the Enter-Key a jump into the change-mode is executed. Now it is
possible to change values, this is displayed by the flashing cursor. By means of the
keys and the requested value can be set. Shall the new value be permanently
stored it has to be confirmed by a second pressing of the . The change mode is
now finished. The new set value will be still available after ON/OFF of the SV1-2-10Z.
Shall the new value not be permanently stored, the change mode has to be left by
key . The new set value remains unchanged only until the next switch OFF of the
device.
Attention: There is a possibility to lock several menue lines for the access by the
operator. A change into the change-mode is then only possible after correct enter of
a 3-digit code word.

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 19
Technical Description
Taste (Cursor)
While being in the change mode (see key ), the flashing cursor is removed to the
next possible input position by actuating the key . In some menue lines there is
only one input position available. In this case the cursor key is out of function.
Key (Minus)
By means of this key the value to be set can be decreased. To do this change first
into the change mode.
Taste (Plus)
By means of this key the value to be set can be increased. To do this change first
into the change mode.
Additional setting possibilities of control SV1-2-10Z
Change of access enable
There is a possibility of locking respective menue lines for inputs by the operator
resp. to unlock them. To do this one has to change into the desired menue line by
means of key and switch the DIP-Switch S12.2 to position ON. The current status
of the access enable is displayed in this menue line.
M e n u e D : l o c k e d
Menue line Access enable
By means of key the menue line can now be locked or unlocked. Shall the new set
value be permanently stored this has to be confirmed by a second pressing of key
. The DIP-Switch S12.2 should then be set back to position OFF. If a menue line is
locked the operator has to enter first a 3-digit code to unlock it. In case of an incorrect
input the menue line remains locked for modifications.
Change code
To be able to change the unlocking-code the DIP-Switch S12.3 has to be set to
position ON.
N e w c o d e : 2 6 4
By means of the keys , and a new code can be entered and stored by means
of key . The DIP-Switch S12.3 should then be set back to position OFF. The code
is always valid for all menue lines.

GB Controller SV1-2-10Z
GB_SV1-2-10Z.DOC 1003 BEIER-Electronic 20
Technical Description
Change I-MAX
Upon switching the DIP-Switch S12.4 to position ON, the maximum current, which
flows into the connected feeding device can be limited.
B 0 5 0 % = 1 , 2 A 2 , 5 A
Maximum current Current range
By means of the key and a new maximum current can be entered. Values
between 10% and 100% are admissible. The given percent values refer always to the
set current range (2,5A or 10A). The value is stored upon actuating key . It must
be observed, that the feeding device cannot be overloaded by the operator! After the
adjustment the DIP-Switch S12.4 has to be set back to position OFF.
Set-point value 2
By means of the DIP-Switch a second set-point value can be made possible. If the
switch is in position ON both set-point values are displayed in menue line “A”. The
change over between set-point value 1 and 2 is done by means of Input X13. If this
input is selected set-point value 2 is active, otherwise set-point value 1.
Current range
Generally 2 current ranges are available. If the DIP-Switch S12.6 is in position OFF
the SV1-2-10Z supplies an output current of 2,5A maximum. In position ON the
feeding device disposes of 10A at most.
Attention: In case of currents higher than 6A the device has to be mounted on
a heat sink!
Current waveform
Two different output current waveforms are possible which can be selected by the
DIP-Switch S12.7. At position OFF the current is trapezoidal at position ON nearly
sinusoidal. The current waveform which is better for the respective feeding device
(feeding performance, noise level, current input) must be found out by testing. At
frequencies less than 40Hz, the sinusoidal current waveform is recommended.
Additional information regarding control SV1-2-10Z
Even if the control unit is switched off by the main switch Q1 or
disconnected from the voltage supply the inner side of the device
remains energised (dangerous to life). The device is reenergised
when ‚ POWER OFF ‘ expires on the display and the status LED
H1 is dark. This can take up to 20 seconds. Before this the device
must not be opened!
Table of contents
Other BEIER-Electronic Controllers manuals

BEIER-Electronic
BEIER-Electronic SFR-1-HL User manual

BEIER-Electronic
BEIER-Electronic UFR-1230-D User manual

BEIER-Electronic
BEIER-Electronic SFR-1 User manual

BEIER-Electronic
BEIER-Electronic SFR-1-D User manual

BEIER-Electronic
BEIER-Electronic UFR-1230 User manual

BEIER-Electronic
BEIER-Electronic SV3-1-8Z User manual