BEKA BA3101 User manual

1. INTRODUCTION
The BA3101 is an IECEx, ATEX and UKCA certied
intrinsically safe Operator Display. It is the core of the
Pageant Operator Display System comprising a 7 inch
backlit display with 8 touch buttons plus 8 sockets which
can accommodate a single CPU module and up to 7 input
and output modules.
The Operator Display and all of the plug-in modules are
powered from a BEKA Power Isolator in the safe area or
Zone 2 via a plug-in CPU (Central processing unit) module.
The CPU module can also have external communications.
Fig 1 shows the rear of the BA3101 Pageant Operator
Panel with its features identied.
The BA3101 and all of the plug-in modules have individual
intrinsic safety apparatus certicates. Compatible input
and output safety parameters allow any certied BEKA
plug-in Pageant CPU module to be tted in display socket
‘C’. Similarly, any certied BEKA plug-in Pageant input or
output module may be tted into sockets 1 to 7, providing
the sum of the percentage power consumption of all the
modules tted does not exceed 100%. See Pageant
System Operator Panel instructions for further details.
Apart from an earth stud, all eld connections to the
BA3101 Pageant Operator Display are made via removable
terminals on the plug-in modules.
BA3101 Operator Display
Sockets for up to
7 plug-in Input and
Output Modules
Panel mounting
clamps 8 off
Socket for plug-in
CPU Module 'C' socket
Certification
information
label
M4 earth
stud
1 2 3 4 5 6 7
C
Fig 1 Rear view without plug-in modules
2. INTRINSIC SAFETY CERTIFICATION
Notied Body CML B.V. and UK Approved Body Eurons
CML have issued the BA3101 Pageant Operator Display
with the following apparatus certicates:
IECEx IECEx CML 20.0150X
ATEX CML 20ATEX2252X
UKCA CML21UKEX2003
The ATEX certicate conrms compliance with harmonised
European standards and this has been used to conrm
compliance with the European ATEX Directive for Group
II, Category 1G and 1D equipment. The BA3101 Operator
Display carries both the CE and UKCA marks, subject to
local codes of practice, it may be installed in any of the
European Economic Area (EEA) member countries and
in the UK. ATEX certicates are also acceptable for
installations in some non EU countries.
These instructions describe IECEx, ATEX and UKCA
installations which conform with IEC
/
EN 60079-14
Electrical installations design, selection and erection.
When designing systems the local code of practice should
be consulted.
Instructions for
BA3101 Pageant Operator Display
Issue 2
21st February 2023
BEKA associates Ltd. Old Charlton Rd, Hitchin, Hertfordshire,
web: www.beka.co.uk
The BA3101 Pageant Operator Display is CE marked to show compliance with the European Explosive
Atmospheres Directive 2014/34/EU and the European EMC Directive 2014/30/EU.
The BA3101 is also UKCA marked to show compliance with UK statutory requirements Equipment and
Protective Systems Intended for Use in Potentially Explosive Atmospheres Regulations UKSI 2016:1107
(as amended) and with the Electromagnetic Compatibility Regulations UKSI 2016:1091.

2.1 Gas atmospheres - Zones, gas groups and T rating
All of the BA3101 Operator Display certications specify
the same gas code:
Ex ia IIC T4 Ga -40°C ≤ Ta ≤ 65°C
The Operator Display has no external connections, the
only input and output intrinsic safety parameters are for
the plug-in modules. It is therefore only necessary for the
specier and installer to ensure that all the plug-in modules
are manufactured by BEKA and are certied for use with a
BA3101 Pageant Operator Display.
When tted with a certied BEKA plug-in CPU module
and certied BEKA plug-in input and output modules, the
BA3101 may be installed in:
Zone 0 explosive gas air mixture
continuously present.
Unlikely requirement
Zone 1 explosive gas air mixture likely
to occur in normal operation.
Zone 2 explosive gas air mixture not
likely to occur, and if it does
will only exist for a short time.
Be used with gases in groups:
Group A propane
Group B ethylene
Group C hydrogen
In gases that may be used with equipment having a
temperature classication of:
T1 450°C
T2 300°C
T3 200°C
T4 135°C
At an ambient temperature Ta between -40°C and +65°C
2.2 Dust atmospheres - Zones
All of the BA3101 Operator Display certications specify
the same dust code:
Ex ia IIIC T135°C Da -40°C ≤ Ta ≤ 65°C.
For applications in dust atmospheres, the certicates
specify Special Conditions of Use (See section 2.3) which
require the rear of the Operator Panel to have additional
protection. This requirement can be satised by mounting
the BA3101 Operator Display in a component certied
Ex e enclosure with cable glands providing a minimum
IP5X sealing.
When tted with a certied BEKA plug-in CPU module
and certied BEKA plug-in input and output modules, the
BA3101 may be installed in:
Zone 20 explosive atmosphere in the form of a cloud
of combustible dust in air is continuously
present, or for long periods or frequently.
Zone 21 explosive atmosphere in the form of a cloud
of combustible dust in air is likely to occur
occasionally in normal operation.
Zone 22 explosive atmosphere in the form of a cloud
of combustible dust in air is not likely to occur
in normal operation, but if it does occur, will
only persist for a short period.
Be used with dust in subdivisions:
IIIA combustible yings
IIIB non-conductive dust
IIIC conductive dust
2.3 Special conditions for safe use
All three certicate numbers have an ‘X’ sufx indicating
that special conditions apply, please see certicates.
i. Under certain extreme circumstances, the non-
metallic parts incorporated in the enclosure of this
equipment may generate an ignition-capable level
of electrostatic charge. Therefore, the equipment
shall not be installed in a location where the
external conditions are conducive to the build-up of
electrostatic charge on such surfaces. In addition,
the equipment shall only be cleaned with a damp
cloth.
ii. The metal bezel of the equipment shall be connected
to earth via the integral earth stud.
iii. In installations requiring EPLs Da, Db, or Dc, the
surface temperature assigned to this equipment
shall take precedence over the surface temperature
assigned to any plug-in module which may be
installed within its enclosure.
iv. In installations requiring EPL Da, Db, or Dc, the
equipment shall be mounted to an enclosure which
provides a minimum degree of protection of IP5X
and which meets the requirements of EN60079-0
Clause 8.4 (material composition requirements for
metallic enclosures for Group III) and/or EN60079-0
Clause 7.4.3 (Avoidance of a build up of electrostatic
charge for Group III) as appropriate.
All cable entries into the equipment shall be made via cable
glands which provided a minimum degree of protection of
IP5X
2

2.4 Certication label information
The certication information label is tted to the side of the
Pageant Operator Display. It shows the model number,
certication information and BEKA associates address
and year of manufacture together with the serial number.
Certication Information Label
3. INSTALLATION
3.1 Location
The BA3101 Pageant Operator Display has a 316 stainless
steel front panel surrounding the backlit display which is
protected by a 4mm thick toughened glass window. The
front of the Operator Display has IP66 protection and a
silicone moulded gasket provides an IP66 seal to the
instrument panel. The rear of the BA3101 Pageant
Operator Display has IP20 protection.
The BA3101 may be installed in any panel providing the
environmental and safety limits shown in the specication
are not exceeded. Although the front of the Operator
Display has IP66 protection, it should be shielded from
continuous direct sunlight and severe weather conditions.
Fig 2 shows the overall dimensions of the BA3101 including
the plug-in modules and the panel cut-out.
Panel cut-out
248.5
184
230.6 +0.5/-0.0
166 +0.5/0.0
108.9
3
Fig 2 BA3101 dimensions including
plug-in modules and panel cut-out
3.2 BA3101 Operator Display Installation Procedure
1. Cut the aperture specied in Fig 2 in the panel and
ensure that all edges are de-burred.
2. First ensure that all eight panel mounting clamps
are closed by turning the knurled screws fully
anticlockwise until the two pips in the clamp foot
align with holes in the clamp body as shown in
Fig 3.
3. Ensure that the panel sealing gasket is correctly
positioned before inserting the BA3101 Operator
Display into the panel aperture.
4. Place a clamp in the recess on each side of the
BA3101, pulling gently to slide it onto the dovetail
as shown in Fig 3. Push the knurled screw slightly
forward to engage the thread and tighten by turning
clockwise until it is just nger tight. When both
clamps are tted ensure that the gasket behind
the front panel bezel remains correctly positioned
before tting the remaining panel mounting clamps.
Finally, fully tighten all the panel clamps to secure
the instrument. The maximum recommended clamp
tightening torque is 22cNm (1.95 lbf in) which is
approximately equivalent to nger-tight plus one
half turn. Do not over tighten.
Insert panel clamp into
recess and gently pull it onto
the dovetail. Engage screw
& turn clockwise to tighten
clamp
Insert instrument
into the panel
from the front
Position gasket
behind instrument
bezel
Align foot and body by
turning screw anticlockwise
Fig 3 Installation of panel and mounting clamps
3

4. PLUG-IN MODULES
The BA3101 Operator Panel can accommodate one plug-
in CPU module in the right hand socket, marked ‘C’ and up
to seven plug-in input or output modules in the remaining
sockets marked 1 to 7 as shown in Fig 1. Modules have
keyed plugs and sockets which ensure that an input or
output module can not be tted in the ‘C’ socket and a
CPU module can not be tted in sockets marked 1 to 7.
All BA3101 Operator Displays must be tted with a plug-in
CPU module which contains the central processing unit
and memory. It also distributes power to the display and
to all of the plug-in input and output modules from a BEKA
Power Isolator located in the safe area or in Zone 2. Some
CPU modules also include an external communication
port.
Input and output modules may be tted in any of the seven
sockets most convenient for eld wiring, they do not have to
be installed in a specic position or order, but their position
does have to be entered in the application software.
4.1 Installing a plug-in module
All Pageant plug-in modules are installed in the same way
and may be tted before or after the Operator Display is
mounted in a panel or cubicle. The Operator Display
should not be powered while a plug-in module is being
inserted or removed.
For a hazardous area installation plug-in modules must be
manufactured by BEKA and have certication that species
that they shall be used as part of a BEKA Pageant system.
BA3401
BA3XXX
Insert
module
BA3101 Pageant
Operator Display
When module has been
inserted tighten two
captive screws
CPU Module
plugged into
'C' socket
Fig 4 Installing plug-in modules
5. FIELD WIRING
All eld connections to the BA3101 Operator Panel are
made via the removable terminals on the plug-in modules
which are described in the instructions supplied with each
module. Apart from the earth stud, there are no direct eld
connections to the BA3101 Pageant Operator Display.
The M4 earth stud is located on the right hand side at the
rear of the Operator Panel as shown in Fig 1. It should
be connected to earth and to the metallic structure of the
enclosure in which the BA3101 Pageant Operator Panel
is mounted.
To simplify installation all module eld wiring terminals are
removable by gently pulling. Wiring should be supported
to prevent damage to the connectors, particularly in
installations subject to vibration.
6. ACCESSORIES
6.1 Tag number
The BA3101 Pageant Operator Panel can be identied by
a tag number or application information thermally printed
on a self-adhesive label tted to the side of the instrument.
7. MAINTENANCE
The BA3101 Operator Display should be regularly
inspected to ensure that it has not been damaged. The
frequency of inspections depends upon the environmental
conditions.
No attempt should be made to repair a faulty
BA3101 Pageant Operator Panel. Suspect
Operator Panels should be returned to BEKA
associates or your local BEKA agent.
8. GUARANTEE
Operator Displays which fail within the guarantee period
should be returned to BEKA associates or your local
BEKA agent. It is helpful if a brief description of the fault
symptom(s) is provided.
9. CUSTOMER COMMENTS
BEKA associates are always pleased to receive comments
from customers about our products and services. All
communications are acknowledged and whenever
possible, suggestions are implemented.
4

APPENDIX 1
BA3101 Pageant Operator Display Codesys Mapping
and Parameters
The Pageant Codesys Quick Start Guide which can be
downloaded from the BEKA website https://www.beka.
co.uk/manuals/pageant_codesys_quick_start_guide.pdf
explains how to setup the CODESYS v3 environment to
work with a BEKA Pageant Operator Panel and to start
developing PLC applications.
The BEKA Quick Start Guide is not a programming
manual, for detailed documentation about the
CODESYS v3 development system please refer to
https:/www.codesys.com and to the on-line help.
The following table lists the BA3101 Pageant Operator
Display Codesys parameters that can be set and mapped
during the initialisation of the PLC application which is
described in the BEKA Quick Start Guide. If the values
are not set in the Codesys project, the default values will
be used.
5
Channel or Parameter Name Type Default Variable Type Range Description
System Temperature Input N/A REAL 32 bits Float Display Temperature in degC
Backlight Control Output N/A BOOL 0..1 0: Backlight OFF, 1: Backlight ON
Left Side LED1
LED Control Output N/A BOOL 0..1 0: LED OFF, 1: LED ON
LED Colour Output N/A BYTE 1..3 1: Red, 2: Green, 3: Amber
Left Side LED2
LED Control Output N/A BOOL 0..1 0: LED OFF, 1: LED ON
LED Colour Output N/A BYTE 1..3 1: Red, 2: Green, 3: Amber
Left Side LED3
LED Control Output N/A BOOL 0..1 0: LED OFF, 1: LED ON
LED Colour Output N/A BYTE 1..3 1: Red, 2: Green, 3: Amber
Left Side LED4
LED Control Output N/A BOOL 0..1 0: LED OFF, 1: LED ON
LED Colour Output N/A BYTE 1..3 1: Red, 2: Green, 3: Amber
Right Side LED1
LED Control Output N/A BOOL 0..1 0: LED OFF, 1: LED ON
LED Colour Output N/A BYTE 1..3 1: Red, 2: Green, 3: Amber
Right Side LED2
LED Control Output N/A BOOL 0..1 0: LED OFF, 1: LED ON
LED Colour Output N/A BYTE 1..3 1: Red, 2: Green, 3: Amber
Right Side LED3
LED Control Output N/A BOOL 0..1 0: LED OFF, 1: LED ON
LED Colour Output N/A BYTE 1..3 1: Red, 2: Green, 3: Amber
Right Side LED4
LED Control Output N/A BOOL 0..1 0: LED OFF, 1: LED ON
LED Colour Output N/A BYTE 1..3 1: Red, 2: Green, 3: Amber
Left Side KEY1
Input N/A BOOL 0..1 0: No Key Press, 1: Key Pressed
Left Side KEY2
Left Side KEY3
Left Side KEY4
Right Side KEY1
Right Side KEY2
Right Side KEY3
Right Side KEY4
BA3101 Pageant Operator Display Codesys Mapping and Parameters
Table of contents
Other BEKA Monitor manuals

BEKA
BEKA FOUNDATION BA684DF-F User manual

BEKA
BEKA FOUNDATION BA484DF-F User manual

BEKA
BEKA BA488CF User manual

BEKA
BEKA BA684D User manual

BEKA
BEKA BA688CF-P User manual

BEKA
BEKA BA488C Operating instructions

BEKA
BEKA BA484DF-P User manual

BEKA
BEKA BA688CF User manual

BEKA
BEKA FOUNDATION BA684DF-F User manual

BEKA
BEKA BA684DF User manual