Beltrame S2014 User manual

Rev. 4.0
BELTRAME
CENTRO SERVIZI ENERGIA


2
CONTENTS
IMPORTANT INFORMATION................................................................................................................
1. SAFETY INSTRUCTIONS............................................................................................................
1.1 General
1.2 Safety Instrucons
2. DEVICE DESCRIPTION...............................................................................................................
2.1 Introducon
2.2 S2014 Main Specificaons
2.3 CE / EU Compliance
2.4 Overall Dimensions and Fixing Holes...................................................................................
2.5 Applicaon Area
2.6 Basic Inseron Configuraons.............................................................................................
2.7 Hardware.............................................................................................................................
2.8 Control elements and interfaces
2.9 Terminal blocks....................................................................................................................
3. DEVICE CONNECTIONS.............................................................................................................
3.1 Input/Output power connecon / rated data
3.2 Device connecons: CN2 Interface
3.3 Device connecons: CN3 I/O control signals.......................................................................
4. OPERATING MODES.................................................................................................................
5. FUNCTIONS DESCRIPTION........................................................................................................
5.1 So Start
5.2 Compensaon and Droop funcons
5.3 ‘Keep Alive’..........................................................................................................................
5.4 Limiters................................................................................................................................
5.4.1 V/f Limiter
5.4.2 Minimum excitaon current: Under Excitaon limiter
5.4.3 Maximum excitaon current: Over Excitaon limiter..............................................
5.4.4 Minimum capability: Q- limiter
5.4.5 Maximum capability: Q+ limiter..............................................................................
5.4.6 S2014 Configr: Limits status
6. WORKING MODE AND REGULATIONS.......................................................................................
6.1 Automac Voltage Regulator (AVR)....................................................................................
6.2 Field Current Regulaon (FCR)
6.3 Power Factor regulaon (PF)...............................................................................................
6.4 Reacve power regulaon (VAR)
6.5 Digital reference adjustment by calibrator (Up/Down).......................................................
6.6 Digital reference adjustment by analog inputs
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
BELTRAME
CENTRO SERVIZI ENERGIA

7. OPERATOR INTERFACE..............................................................................................................
7.1 Control keypad and display
7.2 Navigang inside the menus
7.3 Parameters Saving...............................................................................................................
7.4 Menù descripon................................................................................................................
7.4.1 Menù “D” - Display (readings)
7.4.2 Menù “R” - References and Regulators
7.4.3 Menù “I” - Inputs and Outputs...............................................................................
7.4.4 Menù “C” - Commands
7.4.5 Menù “P” - Parameters............................................................................................
8. TROUBLE SHOOTING................................................................................................................
8.1 First Inspecon
8.2 Trouble shoong
8.3 Repairing..............................................................................................................................
9. CONNECTION DIAGRAM...........................................................................................................
9.1 Introducon
9.2 Basic S2014 Connecon Diagrams.......................................................................................
9.3 S2014 Connecon Diagrams with Low Voltage Alternator..................................................
9.4 S2014 Connecon Diagrams with Medium Voltage Alternator...........................................
10. BELTRAME CONFIGURATOR: THE PC SOFTWARE.......................................................................
10.1 Connecon between AVR and PC
10.2 Installaon and Communicaon setup
10.3 Parameters seng: P.xxx and procedure.............................................................................
10.4 Parameters Seng: L.xxx and R.xxx.....................................................................................
10.5 Parameters Seng: D.xxx....................................................................................................
10.6 Parameters Seng: O.xxx
10.7 Regulator Windows.............................................................................................................
10.8 Trend window
3
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
BELTRAME
CENTRO SERVIZI ENERGIA

4
Our experience has shown that, if the informaon and recommendaons contained in this Operang Instrucons
are observed, the best possible reliability of our products is assured.
The data contained herein purports solely to describe the product and it is not a warranty of performance or
characteriscs. It is with the best interests of our customers in mind that we constantly strive to improve our
products and keep them abreast of advances in technology. This may, however, lead to discrepancies between a
product and its "Technical Descripon" or "Operang Instrucons".
This document has been carefully prepared and reviewed, however should in spite of this the reader find an error,
he is requested to inform us at his earliest convenience.
It is scarcely possible for the operang instrucons for technical equipment to cover every eventuality, which can
occur in pracce. We would therefore request you to nofy us or our agent in the case of all unusual behavior that
does not appear to be covered by these operang instrucons.
It is pointed out that all local regulaons in force must be observed when connecng and commissioning this
equipment in addion to these operang instrucons.
We cannot accept any responsibility for damage incurred as a result of mishandling the equipment regardless of
whether parcular reference is made in these operang instrucons or not.
All rights with respect to this document, including applicaons for patent and registraon of other industrial
property rights, are reserved. Unauthorized use, in parcular reproducon or making available to third pares, is
prohibited.
IMPORTANT INFORMATION
BELTRAME
CENTRO SERVIZI ENERGIA

5
1. SAFETY INSTRUCTIONS
1.1 General
The safety instrucons shall be followed during installaon, commissioning, operaon and maintenance of the
excitaon system. Read all instrucons carefully before operang the device and keep this manual for future
reference.
1.2 Safety Instrucons
The safety instrucons precede any instrucon in the context where a potenally dangerous situaon may appear.
The safety instrucons are divided into three categories, and each one is introduced by a symbol with its
descripon:
Required Qualificaon
Personnel involved in installaon work and commissioning of the S2014 must be familiar, specially
instructed and informed about the residual danger areas according to the regulaons currently in
force. Operang personnel is not permied to work at the control system. Only specially instructed
personnel must carry out maintenance and repair work. The maintenance personnel must be
informed about the emergency shutdown measures and must be capable of turning off the system
in case of emergency. The maintenance personnel must be familiar with the accident prevenon
measures at their workplace and must be instructed in first aid and firefighng.
It is the owner’s responsibility to ensure that each person involved in the installaon and
commissioning of the S2014 has received the appropriate training or instrucons and has
thoroughly read and clearly understood the safety instrucons in this chapter.
DANGER!
This symbol indicates an imminent danger resulng from mechanical forces or high voltage.
A non-observance leads to life-threatening physical injury or death.
WARNING!
This symbol indicates a dangerous situaon. A non-observance may lead to bad or
life-threatening physical injury or death. It may cause also possible damages to the devices.
NOTICE!
This symbol emphasizes important informaon. A non-observance may cause damage to the
device or to objects close to it.
BELTRAME
CENTRO SERVIZI ENERGIA

6
2. DEVICE DESCRIPTION
2.1 Introducon
S2014 is a last generaon Automac Voltage Regulator for Generators excitaon control. The unit contains the most
advanced microprocessor technology together with IGBT semiconductor technology (Insulated Gate Bipolar
Transistor).
A praccal and simple-to-operate on board panel is used for all control operaons. In addion, user friendly
soware facilitates the commissioning and allows the opmizaon of the performances.
2.2 S2014 Main Specificaons
2.3 CE / EU Compliance
This product has been evaluated and complies with the relevant essenal requirements requested by the EU
legislaon.
It complies with the following EU Direcves:
• LVD 2014/35/EU;
• EMC 2014/30/EU;
• ROHS 2 2011/65/EU.
The harmonized standards used for the evaluaon are:
• EN 50178 - Electronic Equipment for use in Power Installaons;
• EN 61000-6-4 - Electromagnec Compability (EMC), Generic Standards, Emission Standard for Industrial
Environments;
• EN 61000-6-2 - Electromagnec Compability (EMC), Generic Standards, Immunity for Industrial
Environments.
MECHANICAL DETAILS
AMBIENT CONDITION
ELECTRICAL DETAILS
Other
Weight:
Protecon class:
Dimensions (LxWxH)
Power electronics supply:
Excitaon output:
Frequency range:
Accuracy
Voltage inputs
Ambient condion
< ±0.25%
From 10 to 500 Hz
Not insulated
AVR has to be protected against dust, moisture, rain
Temperature range for operaon:
Temperature range for storage:
Vibraon:
Approx. 600 gr
IP2X (limited by fast-on type terminals)
138x58x55 mm
From -20°C to +65°C
From -40°C to +80 °C
5 mm, 2 G, 5<f<150 Hz
3±300 Vac from 10 to 500Hz
Max connuous current 8 A
Current reducon for ambient
temperatures
> 50 °C: 1 A/degree
Forcing (max 10 s): 16 A
BELTRAME
CENTRO SERVIZI ENERGIA

7
2.4 Overall Dimensions and Fixing Holes
2.5 Applicaon Area
This AVR is used for the excitaon of synchronous machines. This unit is suitable for this only applicaon area.
The AVR can manage several regulaons. Among them:
- Voltage regulaon;
- Field Current Regulaon (FCR);
- Power Factor regulaon (PF);
- Reacve power regulaon (VAR).
37
67
6 54
48
129
8
134
142
9
60
54 6
Ø5
BELTRAME
CENTRO SERVIZI ENERGIA

8
In this configuraon the AVR is powered directly from
the generator output (or from an auxiliary winding).
The AVR DC output is feeding the stator of the exciter.
In this configuraon the AVR is powered from a PMG.
The AVR DC output is feeding the stator of the exciter.
This configuraon shows a possible replacement of a
Direct Current excitaon machine.
SM: Synchronous Machine E: Exciter PMG: Permanent-Magnet-Generator D:Direct Current machine
2.6 Basic Inseron Configuraons
The following SLD show some basic inseron configuraons of the S2014.
SM E
AVR
S2014
Vsense
Ig
Power
SM D
AVR
S2014
Vsense
Ig
Power
SM
PMG E
AVR
S2014
Vsense
Ig
Power
BELTRAME
CENTRO SERVIZI ENERGIA

9
Note: The interface is not isolated from the power supply: in order to
connect with a pc or other devices an interface isolator must be used.
2.7 Hardware
Structure:
The device is assembled inside a plasc case with aluminum base, and it is fixed on a heat dissipater.
The connecon terminals are integrated on the top of the circuit boards.
Power electronics:
- The power circuit is designed with IGBT semiconductors.
- A fuse protects the output against short-circuits.
Control elements:
- The operang keys and the display are located on board.
- The communicaon port connector is located on the front of the AVR.
Installaon:
- The site of installaon must be dry and free of dust. The AVR can be installed in vercal or
in horizontal posion.
Mounng:
- The AVR must be installed inside the Generator or inside the control panel in order to obtain protecon
against accidental contacts. To fasten the regulator, use the 4 MA through-screws in two corners holes.
It is recommendable to use self-locking nuts. It is recommended also to bind the regulator back on a
metal plate for beer heat dissipaon.
Connecon block diagram:
2.8 Control elements and interfaces
Carrying out sengs on the unit
The displays and the four keys allow complete operaon.
All sengs can be carried out directly on the unit without addional equipment.
• Inputs and outputs configuraon;
• Parameter seng;
• Selecon on the display of the main measured values.
Interface with PC (see the dedicated chapter)
Parameter seng and opmizaon is possible using the user-friendly S2014 Config for Microso Windows. Using
an USB/RS485 cable (made by Beltrame - Oponal), with USB insulator, for the connecon between PC and AVR, is
possible to:
• Configure inputs and outputs;
• Set all parameter;
• Select on the display all the measured values;
• Download, upload, save and open config files;
• … and a lot more.
GENERATOR
Exciter field Current
transformer
Sensing Voltage
transformer
Power supply
3÷300Vac
RS-485 Port
10÷500Hz
S2014
BELTRAME
CENTRO SERVIZI ENERGIA

10
2.9 Terminal blocks
Overview of the device connecons:
Descripon of the terminals:
CN2 – RS 485 Serial Interface CN3 – Control connecons
1GND
GND
-RESERVED-
LINK –
LINK +
-RESERVED-
-RESERVED-
-RESERVED-
AUX
Com
Excitaon output +
Excitaon output -
Voltage sensing input
PE
2
3
4
5
6
7
8
AUX
COM
+Ecc
-Ecc
Vsense
PE
FX1 - Power connecons FX2 – Current sensing inputs
C1 Com
Increase reference adjust
Decrease reference adjust
52G status (parallel feedback)
±5V analog input
1Kohm Potenometer input
+6V Aux
N.C.
OUT (E)
OUT (C)
C.T. input S1
C2
C3
C4
C5
C6
C7
C8
C9
C10
S1
C.T. input S2
S2
Note: the reserved pins have to be le unconnected
FUSE
BELTRAME
CENTRO SERVIZI ENERGIA

11
3. DEVICE CONNECTIONS
3.1 Input/Output power connecon / rated data
3.2 Device connecons: CN2 Interface
Terminal designaon
Modbus RTU and proprietary
protocols
half duplex
Not isolated
from power
supply
Communicaon
CN2 picture:
Descripon Diagram
CN2 Posion
Required Qualificaon
Personnel involved in installaon work and commissioning of the S2014 must be familiar,
specially instructed and informed about the residual danger areas according to the
regulaons currently in force.
Only specially instructed personnel must carry out maintenance and repair work.
Terminal designaon
(FX1 AND FX2)
Power electronics
supply
ADC input voltage
(single-phase)
3÷300 Vac
10÷500 Hz
AUX - COM
Measurements inputs 0 ÷ 500 Vrms (sensing)
Not isolated versus the power supply (AUX)
0÷5 Arms
With galvanic isolaon
COM - Vsense
TA s1 - TA s2
Terminals Signal Specificaons
Excitaon ouput Excitaon voltage
Excitaon current
Generator voltage
Generator current
3÷200 VDC (<0.8 V )
0÷8 A (16 A for 10s)
+ECC -ECC AUX
BELTRAME
CENTRO SERVIZI ENERGIA
LINK +
LINK -
GND
S2014
CN2
5
5V
1K
1K
120
4
2
1
Ω
Ω
Ω

12
3.3 Device connecons: CN3 I/O control signals
CN3 picture:
Terminal
designaon
3 programmable digital inputs
• 4mA
• Up / Down /
programmable funcon
• AVR/FCR/PF/VAR mode
CN3 Digital inputs
Descripon Diagram
N.1 programmable digital output
Max Load 65mA 24Vdc
CN3 Digital outputs
Not isolated
from power
supply
2x Analog inputs
Analog input: ± 5V Potenometer input: 1kohm
Not isolated
from power
supply
Ω
BELTRAME
CENTRO SERVIZI ENERGIA
S2014 CN3
COM
Increase
Decrease
Parallel feedback
Analog In
Potentiometer adjust
+6V AUX
N.C.
COM
Increase
Decrease
Parallel feedback
Analog In
Potentiometer adjust
+6V AUX
N.C.
COM
Increase
Decrease
Parallel feedback
Analog In
Potentiometer adjust
+6V AUX
N.C.
OUT (E)
OUT (C)
S2014 CN3
+24Vdc
GND
S2014 CN3
+24Vdc
GND
S2014 CN3 S2014 CN3
± 5V
1k
COM
Increase
Decrease
Parallel feedback
Analog In
Potentiometer adjust
+6V AUX
N.C.
COM
Increase
Decrease
Parallel feedback
Analog In
Potentiometer adjust
+6V AUX
N.C.
OUT (E)
OUT (C)
OUT (E)
OUT (C)
OUT (E)
OUT (C)
OUT (E)
OUT (C)

13
4. OPERATING MODES
S2014 allows bump less changeover between all operaon modes:
Automac voltage regulator (AVR)
It regulates the output voltage of the synchronous machine.
Note: Output Generator Current measurement is oponal: it is
used only for droop compensaon
Field Current Regulaon (FCR)
It regulates the excitaon (field) current of the synchronous
machine.
This operaon mode is quite useful during commissioning and/or
troubleshoong.
PF or Var regulaon (PF, Var)
Regulates the power factor or reacve power of the
synchronous machine.
Note: these funcons are available only if the machine
is working in parallel (and with closed 52G signal)
SM E
PID
PF
kVar
SM E
PID
BELTRAME
CENTRO SERVIZI ENERGIA

14
5. FUNCTIONS DESCRIPTION
5.1 So Start
Seng the following parameters, it is possible to set up the excitaon ramp of the Generator (Output Voltage vs Time):
Parameter Descripon (short) Descripon
P.100
R.002
Gen rated voltage
Ramp slope
Generator rated voltage [V]
Ramp slope [%/s]
The slope of the ramp is controlled by the V/Hz limiter.
The so start funcon is working only in the AVR mode.
5.2 Compensaon and Droop funcons
The compensaon funcon (K> 0) is used in order to reduce the voltage drop created by the possible presence of a power transformer
mounted aer the Generator.
The ‘droop’ funcon (K<0) is recommendable in case of operaon with more generators in parallel. It applies a machine output voltage
reducon according to the reacve power output. The “droop” funcon reduces the output voltage according the reacve power output
(higher is the reacve power, lower will be the output voltage).
Compensaon and droop funcons require:
- AVR mode
- alternator current reading
- digital input 3 programmed as I002= 4 (52G closed + Droop regulaon)
Parameter Descripon (short) Descripon
P.400 Voltage comp K Voltage comp [%]
Machine voltage (%)
P101
P100
(S)
Machine voltage
(%)
Kq = 1,5%
Kq = -1,5%
Reacve power
(%)
100%
inducve
100%
capacive
BELTRAME
CENTRO SERVIZI ENERGIA

15
Parameter Descripon (short) Descripon
P.250
P.130
Keep Alive min I
Gen. V/f min freq
% of the rated exc current (P.000) from 0Hz to P.130 Hz
Generator minimum frequency (Hz)
5.3 Keep Alive
This feature helps/allows the self-excitaon of the Generator in case the AVR input power line is connected to the generator terminal or to a
generator auxiliary winding.
With “keep alive” enabled (P.250>0), the S2014 will try to keep a minimum excitaon current during the start-up.
As default P.250 is adjusted to 5. This means that the S2014, during the start-up, will try to keep the excitaon current to 5% of the rated
excitaon current (P.000). Once the frequency will be higher the P.130 (Generator minimum frequency), the AVR will leave the “keep alive”
area and will enter in the V ramp area.
In case the AVR is powered with a PMG or with an external power source the “Keep Alive” funcon has to be disabled (set P.250=0).
Above screenshot shows the keep alive funcon effect during generator shung down. Once the frequency drops below P.130 the AVR
acvates the keep alive funcon and works in order to maintain the excitaon current to the P.250 keep alive seng (in this case 5%)
(Hz)
P.130
Keepalive
BELTRAME
CENTRO SERVIZI ENERGIA

16
5.4 Limiters
5.4.1 V/F Limiter
The V / Hz limit is acve during the voltage control phase. It works by liming the Generator voltage as the frequency falls below the
maximum frequency P.131. This operaon can avoid the Generator over-flushing in case of a reducon of speed.
5.4.2 Minimum excitaon current: Under Excitaon limiter
The limit of minimum excitaon current is only acve when the Generator is in parallel [digital input 52G (machine in parallel) closed].
It represents the minimum excitaon current below which the Generator cannot work.
The relaon between output voltage and frequency is:
V(Hz) = P. 100
*Hz
P.131 *1
P.132
Parameter Descripon (short) Descripon
P.100
P.130
P.131
Gen. rated voltage
Gen. V/f Min freq
Gen. V/f Max freq
Generator rated voltage [V]
Generator minimum frequency ramp (Hz)
Generator maximum frequency ramp (Hz)
P.132 V/f slope Generator V/f slope
Parameter Descripon (short) Descripon
P.002
r.900
r.901
F. UE Lim
OE/UE Lim reg KP
OE/UE Lim reg TI
OE/UE Lim reg TI
OE/UE Lim. Reg. KP
OE/EU Lim. Reg. TI
Machine voltage (%)
Gen. rated V
P. 132
min
freq
max
freq
Gen rated
freq
(Hz)
BELTRAME
CENTRO SERVIZI ENERGIA
Motor
Generator
Q+ (var)
overexcited
underexcited
Iemin
Q-
P (w)

17
5.4.3 Maximum excitaon current: Over Excitaon limiter
The limit of maximum excitaon current operates a limitaon on the maximum excitaon current.
The limit works in order to avoid to overtake the P.001 value, and if the excitaon current remains on P.001 for longer than P.032, the AVR
reduce the excitaon current to 102%. If the excitaon current goes in the area between P.000 and P.001, the AVR calculate the i*t integral
and once P.001xP.032 is reached, the AVR reduces the excitaon current to P.000.
5.4.4 Minimum capability: Q- limiter
The curve of minimum capability represents the reacve power limit absorbed by the machine. It is determined by interpolang 5 data:
Parameter Descripon (short) Descripon
P.100
P.130
P.131
Gen. rated voltage
Gen. V/f Min freq
Gen. V/f Max freq
Generator rated voltage [V]
Generator minimum frequency ramp (Hz)
Generator maximum frequency ramp (Hz)
P.132 V/f slope Generator V/f slope
P.132 V/f slope Generator V/f slope
Parameter Descripon (short) Descripon
P.160
P.161
P.162
Q – lim @ P 0%
Q – lim @ P 25%
Q – lim @ P 50%
Limit Q- a P=0%
Limit Q- a P=25%
Limit Q- a P=50%
P.163
P.164
Q – lim @ P 75%
Q – lim @ P 100%
Limit Q- a P=75%
Limit Q- a P=100%
BELTRAME
CENTRO SERVIZI ENERGIA
(%)
P.001
P.000
D.000
P.032 (S)
Motor
Generator
Q+ (var)
overexcited
underexcited
Q-
P (w)
100%
100%
75%
75%
50%
50%
25%
25%
0%

18
5.4.5 Maximum capability: Q+ limiter
The curve of maximum capability represents the reacve power limit delivered by the machine. It is determined by interpolang 2 data:
• Q+ limit a P=0% P.170 [%]
• Q+ limit a P=100% P.171 [%]
5.4.6 S2014 Config: Limits status
The S2014 Config soware reports an overview of the limiters status:
The reported limiters status shows that the V/Hz (underfrequency or underspeed limiter) is acve.
Parameter Descripon (short) Descripon
P.170
P.171
Q + lim @ P 0%
Q + lim @ P 100%
Limit Q+ a P=0%
Limit Q+ a P=100%
BELTRAME
CENTRO SERVIZI ENERGIA
Q+ (var)
overexcited
underexcited
Q-
P (w)
P=100%
P=100%
Motor
Generator
P=0%
P.171

19
1. AVR [Automac Voltage Regulator]
2. FCR [Field Current Regulaon]
3. PF/VAR [Control]
6. WORKING MODE AND REGULATIONS
Basically, there are 4 working modes (4 regulaon mode):
- AVR [Automac Voltage Regulator]: S2014 works in order to keep the output voltage to the ref value
- FCR [Field Current Regulaon]: S2014 works in order to keep the excitaon current to the ref value
- PF Control [Power Factor Regulator]: S2014 works in order to keep the PF to the ref value
- VAR Control [Reacve Power Regulator]: S2014 works in order to keep the Reacve Power to the ref value
P.100 +
-
FBK
r.350
r.350/r.351 1/s
Reference of
the voltage
excitaon
r. 000 +
-
FBK
r.250
r.250/r.251 1/s
SCR%
r. 401
r. 400
+
-
FBK
r.450
r.450/r.451 1/s
Reference of
the voltage
alternator
BELTRAME
CENTRO SERVIZI ENERGIA
Other manuals for S2014
1
Table of contents
Other Beltrame Controllers manuals
Popular Controllers manuals by other brands

Honeywell
Honeywell V8200 manual

Metso
Metso ND9100H Installation maintenance and operating instructions

Spectronik
Spectronik PRREG user guide

DEUTSCHMANN AUTOMATION
DEUTSCHMANN AUTOMATION LOCON 100 instruction manual

Woodward
Woodward 2301E Installation and operation manual

Danfoss
Danfoss VLT AQUA Drive FC 202 operating guide