
ENGLISH
8
MySMART
9
MySMART R.S.I. adjustments table
Maximum 
number of fan 
rotations
rpm
Ø 50 
pipework 
pipes
maximum 
length 
Ø 60 
pipework 
pipes 
maximum 
length
Ø 80 
pipework 
pipes 
maximum 
length
ΔP at the 
boiler 
output 
with max 
length (*) 
DHW CH m m m Pa
4.500 4.500 2,9 12,4 80 120
4.600 4.600 4,7 16,8 92 150
4.700 4.700 7,3 23,1 127 193
4.800 4.800 9,5(*) 28,5(*) 157(*) 230
4.900 4.900 10,8(*) 31,8(*) 175(*) 253
5.000 5.000 12,6(*) 36,1(*) 198(*) 282
5.100 5.100 15,1(*) 42,3(*) 233(*) 325
5.200 5.200 19,0(*) 51,8(*) 285(*) 390
(*) Maximum installable lenght only with exhaust pipes in H1 class
NOTE
If p
ipes different than those in the Beretta catalogue are used you must 
see the ΔP values on the above tables to calculate the maximum length 
of the pipes.
The Ø 60 and Ø 50 configurations have experimental, laboratory checked 
data.
In the event of installations other than those indicated in the “base 
configurations” and “adjustments” table, see the equivalent Ø 80 - Ø 
60 or Ø 50 linear lengths shown below.
 In any case the maximum lengths declared in the booklet are 
guaranteed and it is essential that they are not exceeded.
Ø 60 component Linear equivalent in 
metres Ø 80 (m)
45° Ø 60 curve 5
90° Ø 60 curve 8
0.5 m Ø 60 extension 2.5
1.0 m Ø 60 extension 5.5
2.0 m Ø 60 extension 12
 Ø 50 COMPONENT Linear equivalent in 
metres Ø 80 (m)
45° Ø 50 curve 12,3
90° Ø 50 curve 19,6
0.5 m Ø 50 extension 6,1
1.0 m Ø 50 extension 13,5
2.0 m Ø 560 extension 29,5
3.12 Installation on collective flues in positive pressure
The collective flue is a gas discharge system suitable for collecting 
and expelling the combustion products of several appliances installed 
on several floors of a building (fig. 18).
The collective flues in positive pressure can be used only for type C 
condensing appliances. Consequently the B53P/B23P configuration 
is not permitted.
Installation of the boiler on collective flues in pressure is permitted 
only at G20 using a specific check valve, supplied as an accessory. 
See the related instructions for the assembly procedure.
The boiler is sized to operate correctly up to a maximum internal 
pressure of the smoke pipe no higher than the value shown in the 
multigas table.
Complete the check valve assembly operations and proceed with 
adjustment of the number of fan rotations as shown in the multigas 
table.
Ensure that the air suction pipes and combustion product outlet are 
airtight.
Installation of the check valve (fig. 19) requires the application of the 
ATTENTION label that comes with the same accessory on a visible 
part of the boiler shell. Applying the label is essential for safety during 
maintenance or replacement of the boiler and/or the collective flue.
WARNINGS
 The manufacturer will not be liable in the event of failure to 
apply the check valve and the related label prior to placing the 
boiler in service.
 The appliances connected to a collected flue must all be of the 
same type and have equivalent combustion characteristics.
 The number of appliances that can be connected to a collective 
flue in positive pressure is defined by the smoke pipe designer.
MAINTENANCE FOR APPLICATION IN A COLLECTIVE FLUE 
UNDER PRESSURE
During scheduled maintenance on the appliance you must also 
check the condition of the check valve in order to guarantee correct 
operation and safety of the system.
Before proceeding with maintenance you must conduct an analysis 
of the combustion product and check the boiler operating status.
 In the event of maintenance on the boiler's combustion circuit 
(gas discharge pipes, condensate syphon, burner, electrode 
conveyors) you must close the gas discharge pipe that comes 
from the smoke pipe under pressure and check the seal.
Subsequently:
- Remove electrical power by setting the system's main switch to “off”
- Close the gas interception taps
- Remove the shell
- Unhook the instrument panel and rotate it downward
- Unhook and remove the air box cover
- After undoing the related fixing screws, remove the right side of 
the air box
- Undo the nut that secures the gas train valve to the air box
- Undo and remove the mixer connection gas train (A, fig. 20)
- Remove the ignition electrode and flame detection electrical 
connections and the fan electrical connections
- Undo the 4 screws that secure the air gas conveyor to the main 
heat exchanger (B, fig. 20)
- Remove the conveyor-fan assembly from the heat exchanger (C, 
fig. 20), taking great care not to damage the burner insulating panel
- To access the check valve remove the fan by undoing the 4 screws 
(D, fig. 21) that secure it to the conveyor
- Ensure that there is no material deposited on the check valve 
membrane and remove any you may find, ensuring there is no 
damage.
- Check the cor
rect opening and closing operation of the valve
- Reassemble the components working in reverse order, ensuring 
that the check valve is reassembled in the correct direction (fig. 21)
 Failure to observe the above may lead to abnormal operation 
of the check valve and consequent differences in the boiler's 
performance, up to failure to operate.
 Failure to observe what is described here may compromise the 
safety of people and animals due to possible carbon monoxide 
leaks from the smoke pipe.
 Once the operations have been completed, carefully check all 
the combustion product exhaust and air suction pipe seals, 
conducting a combustion analysis.
NOTE
If the fan is removed ensure that the check valve is reassembled in 
the correct direction (fig. 21).
3.13 Filling the heating system (fig. 22-23-24)
Once the hydraulic connections have been carried out, fill the heating 
system.
This operation m
ust be carried out with a cold system, following these 
instructions:
- open the lower automatic relief valve cap (A) by two or three turns 
to allow continuous air venting and leave it open
- ensure that the cold water inlet tap is open
- open the filling tap (C) (outside the boiler for R.S.I. model) until the 
pressure indicated on the water gauge is between 1 bar and 1.5 bar
- re-close the filling tap.
NOTE
The deareation of the boiler takes place automatically by means of 
the two automatic Aand Ebleed valves, the former positioned on 
the circulator whereas the latter is positioned inside the air box. If 
the deareation phase is difficult, operate as described in section 3.4.
3.14 Emptying the heating system
Before starting emptying, switch off the electricity supply by turning 
off the main switch of the system.
- Close the heating system shut-off devices
- Slacken the discharge system valve by hand (D)
- The system's water is discharged through the discharge manifold (F).
 The discharge manifold must be connected via a rubber pipe 
to an appropriate collection and evacuation system in the white 
water discharge drain in compliance with current regulations. 
The outer diameter of the manifold is 20 mm: it is therefore 
advisable to use a rubber pipe Ø18-19 mm closed with a 
suitable clamp (not provided).