BESTPOWER610-UPSInstallation
Model Shown:
0610-3000U soft-wired version
Your UPS is fitted with a DB9 communications
connector on the rear panel. From this connector,
you can access opto-coupled outputs indicating
mainsfailure or low battery. The contactratings
are30 VDC at 10 mA. The diagrambelow shows
DB9 contact connections.
Alternatively, RS232serial communication is
available.ThisRS232providesaproprietary
command sequence for the computer to monitor the
utility and the UPS status and to control the UPS
output. The data format of the RS232 is 2400 bps, 8 bit
data, 1 stop bit and no parity.
Thebattery test modeis alsoavailablethrough the
RS232command sequence whenthe UPSisoperating
and the power is normal. During the test, the 4 LED’s
(line,bypass, battery andinverter) will lightalternatively
until the test is completed.
Each UPS is supplied with a package of CHECKUPS
II®AdvancedUPS communications software.
Thispackage includes thecorrect interconnection
cable for your Best Power 610 UPS. If your computer
does not have a DB9 connector on the serial port, use
astandardDB9-DB25 adaptor,availableat most
computeraccessorystores. The CD-ROMprovidedwith
yourUPS includes softwarefor manystandard
operating systems. Refer to section 4.1 for more
details of CheckUPS II® and its capabilities.
Ifyou areadding the optionalBest RelayCard
(AS400®), refer to Section 5.2 for instructions to install
the card. Be careful to connect your Best Relay
(AS400®)interface cableto the correct DB9 connector.
Refer to Section 5.2 for more details of the Best Relay
(AS400®)card option.
If you are adding the BestLink SNMP/Web option card,
refer to Section 5.3 for instructions to install the card.
Only one (1) card, either Best Relay (AS400®)
or
SNMP, can be fitted into the slot at any one time.
2.9 Setting up the UPS Monitoring from your Computer
5
Note 1: Remote shutdown is
available in battery mode only,
with no mains input power.
Keeping pin 6 at +5 to +12 VDC
for 1 second will turn off the UPS
inverter.
N. O.
Closes
on
Input
Mains
Failure
N. C.
Opens
on
Input
Mains
Failure
N. O.
Closes
on
Low
Battery
Rs232
transmit Data
Rs232
Receive Data
See Note 1.
Rs232 Ground
DB9