manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. bolid
  6. •
  7. Control Unit
  8. •
  9. bolid S2000-AR2 User manual

bolid S2000-AR2 User manual

http://bolid.ru 1
Orion ISS
This Installation Manual provides instructions of how to mount the S2000-AR2 Rev.02
Addressable Double-Input Module (hereinafter referred to as the module) and get it ready for
operation.
To get information on module’s description and rules of settings and operation please refer to
its User’s Manual, which can be found online at http://bolid.ru in the section PRODUCTS.
1 SAFETY PRECAUTIONS
-The module contains no circuits under hazardous voltages.
-The design of the module meets the requirements of electric and fire safety
including emergency operation in accordance with Russian standards GOST
12.2.007.0-75 and GOST 12.1.004-91.
-Do shut off power from the polling loop controller prior to mounting and
installing the module.
-Installation and maintenance shall be carried out by personnel qualified for the
Electrical Safety of Level II or higher.
2 INSTALLATION
2.1 The module is to be installed on a wall, above a suspended ceiling, or on another structure
of the protected premises at a place protected against atmospheric precipitations, mechanical
damages, and unauthorized access.
2.2 The module should be mounted in line with Regulatory Document РД 78.145-93 “Fire
and Intrusion Alarm Installations. Rules for Performance and Acceptance of Works”.
3 MOUNTING
3.1 Make sure the wall the module to be connected to is durable, smooth, clean, and dry.
3.2 Apply the drilling template to the wall (Figure 1) and drill the holes.
3.3 Insert wall plugs into the holes.
3.4 Remove the module cover from its base using a flat-head screwdriver (see Figure 2).
3.5 Put the module to the wall so that to align the fastening holes with the wall plugs.
3.6 Screw the screws into the holes and fasten the module on the wall.
Addressable Double-Input Module
S2000-AR2 Rev.02
Installation Manual
2
http://bolid.ru
Figure 1. Overall and Mounting Dimensions of S2000-AR2 Rev.02
Figure 2. Opening
S2000-AR2 Rev.02 Enclosure
Figure 3. Closing
S2000-AR2 Rev.02 Enclosure
1
Put one long end of the cover
on the
enclosure
base
2
Snap on the
other
end of the
cover
http://bolid.ru 3
4 WIRING
4.1 Polling Loop Wiring
4.1.1 Connect the polling loop wires to the contacts “+” and “−” of the module terminal block
marked as “ДПЛС” on the PCB, observing polarity. Not observing polarity will result in non-
operability of the polling loop.
4.1.2 For the polling loop it is advised to use twin twisted-pair wires.
4.2 Detector Wiring
4.2.1 Connect alarm dry contact outputs of non-addressable detectors to terminals MC1 and
MC2 (marked as “КЦ1” and “КЦ2” respectively) in line with the schematic in Figure 4.
4.2.2 The resistance of the monitored circuit wires shall not exceed 100 Ohm while the leakage
resistance shall be at least 50 kOhm.
4.2.3 If a monitored circuit is not in use connect a 10 kOhm termination resistor to its contacts.
4.3 Close the module enclosure as shown in Figure 3.
КЦ1
ДПЛС
КЦ2
AD: Addressable Device
MC: Monitored Circuit
D1: A normally closed fire detector
D2: A normally open fire detector
D3: A normally open intrusion detector
D4: A normally closed intrusion detector
R1: An additional resistor MF1/4 - 20К±5%
R2: An additional resistor MF1/4 - 4К7 ±5%
R
EOL
: A termination resistor MF1/4 – 10К±5%
Figure 4. Schematic for External Wiring of S2000-AR2 Rev.02
D
2
D1
R1
R
EOL
R2
R
EOL
D
3
R
EOL
D4
Variant A Variant B Variant C
To detectors
(connection variant
A, B, or C)
To detectors
(connection variant
A, B, or C)
PL-
PL+
S2000-KDL
MC+
MC-
MC+
MC-
MC+
MC-
AD
MC2
MC1
4
http://bolid.ru
5 TESTING
5.1 Testing the module shall be carried out by personnel qualified for the Electrical Safety of
Level II or higher.
5.2 Do shut off power from the polling loop controller while connecting and disconnecting
external circuits.
5.3 Performance Testing
5.3.1 Apply power to the polling loop controller.
5.3.2 By means of the network controller arm the detector with the number assigned with
MC1 in the module.
5.3.3 Simulate an alarm response of the detector connected to MC1. The module LED shall
start flashing doubly every four seconds. The network controller shall display Intrusion Alarm
or Fire Alarm for the address assigned to the module’s MC1.
5.3.4 Place the detector into the normal state. The module LED shall start flashing once eve-
ry four seconds. By means of the network controller issue a command to reset alarm from the
detector related to MC1. When one monitored circuit is being tested the other circuit shall be
in norm.
5.3.5 Perform actions 5.3.2 - 5.3.4 for the monitored circuit MC2.
5.3.6 If no Intrusion / Fire Alarm message has come on the network controller then the
module is considered as defective and should be replaced.
5.3.7 By means of the network controller request for ADC values representing monitored
circuit states (see User’s Manual).
6 GETTING STARTED
In order the S2000-AR2 Rev.02 to operate under a polling loop controller in an Orion ISS, it
should be assigned to a polling loop address and the relevant settings should be carried out
(see User’s Manual).

Other bolid Control Unit manuals

bolid S2000-AR8 User manual

bolid

bolid S2000-AR8 User manual

bolid S2000-KPB User manual

bolid

bolid S2000-KPB User manual

bolid S2000-AR8 User manual

bolid

bolid S2000-AR8 User manual

bolid S2000-KPB User manual

bolid

bolid S2000-KPB User manual

bolid S2000-SP4/220 User manual

bolid

bolid S2000-SP4/220 User manual

bolid S2000-BI Rev.02 User manual

bolid

bolid S2000-BI Rev.02 User manual

Popular Control Unit manuals by other brands

turck TBPN-L FDIO1-2IOL Series manual

turck

turck TBPN-L FDIO1-2IOL Series manual

MonkMakes 00063 instructions

MonkMakes

MonkMakes 00063 instructions

Accton Technology CAP2315A installation guide

Accton Technology

Accton Technology CAP2315A installation guide

Maxon SD-125 Series quick start guide

Maxon

Maxon SD-125 Series quick start guide

QSC Q-Sys PTL-1 Quick start guides

QSC

QSC Q-Sys PTL-1 Quick start guides

DSC Power Series PC5904 installation instructions

DSC

DSC Power Series PC5904 installation instructions

Telit Wireless Solutions ZE51-2.4 user guide

Telit Wireless Solutions

Telit Wireless Solutions ZE51-2.4 user guide

JETStream 4" J-FORCE GEN II JF4X22 Product instructions

JETStream

JETStream 4" J-FORCE GEN II JF4X22 Product instructions

Keyscan CIM-LINK Setup guide

Keyscan

Keyscan CIM-LINK Setup guide

Texas Instruments ADC12DJ3200 user guide

Texas Instruments

Texas Instruments ADC12DJ3200 user guide

Trinamic IDX 7507 Hardware manual

Trinamic

Trinamic IDX 7507 Hardware manual

Keba Kemro NX 252/A Project engineering manual

Keba

Keba Kemro NX 252/A Project engineering manual

Zehnder Pumpen ENS 1.1 operating manual

Zehnder Pumpen

Zehnder Pumpen ENS 1.1 operating manual

Metso Full Bore Fire-Tite 9REL Series Installation maintenance and operating instructions

Metso

Metso Full Bore Fire-Tite 9REL Series Installation maintenance and operating instructions

Flowserve Edward 602Y Maintenance manual

Flowserve

Flowserve Edward 602Y Maintenance manual

Savant SKL-3040-00 Quick reference guide

Savant

Savant SKL-3040-00 Quick reference guide

Trinamic PD28-1-1021 Hardware manual

Trinamic

Trinamic PD28-1-1021 Hardware manual

Guntermann & Drunck G&D UCON-Audio-s Installation and operation

Guntermann & Drunck

Guntermann & Drunck G&D UCON-Audio-s Installation and operation

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.