2.1. Level 1 - Setpoint Adjustment
In this level only the Setpoint (SP) parameter is available, alternating the name with its respective value. Adjust the desired
temperature for setpoint by clicking on the and keys.
Level Function
SP (Set Point) Temperature adjustment for control OUTPUT 1. SP value is limited to the values programmed in SPL and SPk in the
programming level (Parameter conguration, level 2).
2.2. Level 2 - Conguration - Parameters conguration Level
Contains the conguration parameters to be dened by the user, according to the system’s requirements.
Use and keys to set the value. The display alternates the parameter name and respective value.
Level Function
Unt Temperature Unit: Selects display indication for degrees Celsius or Fahrenheit.
0- Temperature in degrees Celsius
1- Temperature in degrees Fahrenheit
typ Input Type: Selects the input sensor type to be connected to the controller. Available only for thermocouple models, al-
lowing selection of types J, K and T.
0- Thermocouple type J
1- Thermocouple type K
2- Thermocouple type T
ofs Sensor Offset: Offset value to be added to the measured temperature to compensate sensor error.
spl SP Low Limit: Lower range for SP. spl must be programmed with a lower value than SPH.
SPH SP High Limit: Upper range for SP. SPH must be greater than SPL.
Hy1 OUTPUT 1 Hysteresis: Denes the differential range between the temperature value at which the
OUTPUT 1 is turned on and the value at which it is turned off. (In degrees).
Ac1 Control action for OUTPUT 1:
0 - Reverse: For heating applications. Outputs turn on when temperature is lower than SP.
1- Direct: For cooling applications. Output turns on when temperature is above SP.
of1 (Off time) Off time: Denes the minimum off time for control OUTPUT 1. Once OUTPUT 1 is turned off, it remains so for at least the
time programmed in oft. For thermocouple inputs this parameter is not available. This parameter is intended for refrigera-
tion systems where longer compressor life is desired. For heating systems, program of1 to zero. Value in seconds, 0 to
999 s.
on1 (On time) On time: Denes the minimum on time for control OUTPUT 1. Once turned on, OUTPUT 1 remains so for at least
the time programmed in on1. For thermocouple inputs this parameter is not available. This parameter is intended for
refrigeration systems where increased compressor life is desired. For heating systems, program on1 to zero. Value in
seconds, 0 to 999 s.
dl1 (Delay 1) Delay time to start control: Upon power-on, control OUTPUT 1 is kept off until the time programmed in
dl1 is elapsed. Its usage is intended to prevent multiple compressors to start simultaneouly after the
turn-on of a system with several controllers. Value in seconds, 0 to 250 s.
Add (Adress) Adress: Controllers with the optional RS485 Modbus RTU communication interface have the Add parameter at the
Conguration level. Set a unique Modbus address for each equipment connected to the network. Address range is from 1
to 247.