Bradley S19-322 User manual

Installation
P.O. Box 309
Menomonee Falls, WI 53052 USA
800 BRADLEY (800 272 3539)
+1 262 251 6000
bradleycorp.com
215-1845 Rev. B; ECN 17-05-068
© 2017 Bradley
Page 1 of 12 11/21/2017
S19-322
Recessed Emergency Signaling System
Table of Contents
Pre-Installation Information ..........................2-3
Components....................................... 4
Install Flow Switch .................................. 5
Mount Signaling Assembly ........................... 6
Connect Signaling Assembly.......................... 6
Complete Electrical Supply Connections................. 7
Test the Signaling System ............................ 7
Maintenance ...................................... 8
Remove Sensing Option ............................. 8
Service of Lights ................................... 8
Troubleshooting .................................... 9
Service Parts ..................................... 10
Wiring Diagram ................................... 11
Schematic ....................................... 12

2
S19-322 Installation
11/21/2017 Bradley • 215-1845 Rev. B; ECN 17-05-068
WARNING
Power supplied to the unit should be between 90-264VAC, 50-60 Hz, 15 amp branch circuit with a
dedicated circuit breaker or fuse and should not supply power to any other device. Compliance
and conformity to local codes and ordinances is the responsibility of the installer.
Do not use this safety equipment in a location that does not match its hazardous location rating.
Verify the appropriate ratings prior to installation.
When making electrical connections be sure to follow all lockout–tagout safety procedures.
Flush the water supply lines before beginning installation and after installation is complete. Test
the unit for leaks and adequate water flow. Main water supply should be “ON” at all times unless
system is being serviced. Provisions shall be made to prevent unauthorized shutoff.
CAUTION
Supply the unit with clean, potable water.
NOTICE
Before installing this product, ensure that there are adequate clearances around the product and
activation of the product does not interfere with other products or obstructions.
It is recommended that all water supply and electrical connections be made at temperatures above
freezing. Failure to do so may result in major product and/or property damage.
Constant power supply to safety equipment is necessary for it to function.
Avoid cleaners containing organic solvents, alcohols and hydrocarbons. Rinse with potable water
after cleaning.

3
Installation S19-322
Bradley • 215-1845 Rev. B; ECN 17-05-068 11/21/2017
IMPORTANT
The installation and location of all safety drench showers, eye and eye/face washes must comply
with the requirements of ANSI/ISEA Z358.1.
Read this installation manual completely to ensure proper installation, then file it with the owner
or maintenance department. Compliance and conformity to local codes and ordinances is the
responsibility of the installer.
Separate parts from packaging and make sure all parts are accounted for before discarding any
packaging material. If any parts are missing, do not begin installation until you obtain the missing
parts.
Installation and maintenance of this system must be completed by a qualified plumber and
electrician according to the information contained in this installation manual and in compliance
with all national and local codes.
The ANSI/ISEA Z358.1 standard requires an uninterrupted supply of flushing fluid. Bradley
plumbed emergency fixtures require a minimum of 30 PSI (0.21MPa) flowing pressure.
Weekly activation must be conducted on all plumbed emergency equipment to ensure a suitable
flushing fluid supply is present and any sediment build up in the supply line is cleared. Inspect
safety equipment monthly to address any maintenance issues ensuring the equipment is in good
operating condition and that there are no signs of wear.
Perform functional test upon relocation of safety equipment.
Workers who may come in contact with potentially hazardous materials should be trained
regarding the placement and proper operation of emergency equipment per ANSI/ISEA Z358.1.
For questions regarding the operation or installation of this product, visit www.bradleycorp.com or
call 800-BRADLEY (272.3539).
Product warranties and parts information may also be found under ”Products” on our web site at
bradleycorp.com.
Supplies Required
• Appropriate hardware to mount control box to in-wall studs
• Black, white and green AWG 18 minimum (14 AWG maximum) wire to connect signaling system to electric
power supply
• 3/4" conduit fittings for electrical wiring (all customer supplied hubs and fittings must match the electrical
rating of the enclosures)

4
S19-322 Installation
11/21/2017 Bradley • 215-1845 Rev. B; ECN 17-05-068
S19-322 Components
9"
(229mm)
8"
(203mm)
3-1/8"
(80mm)
6"
(152mm)
System is prewired. Installer
connects ONLY ground
black and white wires.
7"
(178mm)
1-13/16"
(46mm)
13-13/16"
(351mm)
¾" NPT Hub,
Plugged
Brass
Sensor
Body
Brass
Adapter
and Tee
1/2" (eyewash)
or 1¼" (drench
shower) NPT Inlet
and Outlet
NEMA 3R
Junction Box
and Cover
Electrical Quick
Disconnect Male
2-3/8" (60mm) for
eyewash or
3-9/16" (91mm) for
drench shower
3" (76mm)
4-11/16"
(119mm)
Red
Blue
Black
Remote
Sensing
12-3/8"
(315mm)
2-7/8"
(73mm)
1-5/8"
(41mm)

5
Installation S19-322
Bradley • 215-1845 Rev. B; ECN 17-05-068 11/21/2017
1Install the Flow Switch
The flow switch will attach to the mounted alarm via a 6 foot waterproof cable. Keep the
location for mounting the alarm in mind when choosing the flow switch location.
AChoose a location for mounting the
flow switch in a horizontal run of the
water supply line.
B
Mount the flow switch assembly in
the water supply line.
• The switch body must be in the
vertical position with the water
pipe horizontal.
• The water flow must be in the
direction marked by the arrow on
the flow switch body.
• Use teflon tape or pipe sealant
(supplied by installer) on all water
pipe connections.
16" (406mm)
min. ceiling
clearance
To Water
Supply
Flow Switch
1¼" to 1" Reducing
Bushing may be
required based on
model. Flow switch is
1-1/4" on inlet and outlet.
Piping supplied by
installer (must be
minimum 6 inches
from any fittings)
For drench shower
or combination units
To 1/2" Water
Supply
Flow Switch
Piping supplied by
installer (must be
minimum 3 inches
from any fittings)
For eye or eye/face
wash units

6
S19-322 Installation
11/21/2017 Bradley • 215-1845 Rev. B; ECN 17-05-068
2Mount the Signaling Assembly in Wall
C
Chose a location for mounting the
signaling assembly. The signaling
assembly should be mounted at least
7 feet above ground level for best
visibility.
Recessed signaling system display needs to be installed in a location where it is not in the
direct spray pattern of a drench shower.
D
Size appropriate hole to mount the
signaling system in. The wall must
have sufficient depth to accommodate
the flush mounting of the control box.
EMount the control box to the in wall
studs using the holes provided and
fasteners (customer provided).
3Connect Signaling Assembly to Flow Switch
Make sure cable is not taut to prevent
undue stress to cable and connector.
A
Connect the flow switch to the
signaling system by plugging the
prewired cable into the socket
provided in the flow switch junction
box. The plug and socket have an
alignment pin and groove which
makes for error-free hook-up.
B
Tighten the locking collar on the
female cable socket by rotating it
clockwise after plugging in. This
makes a good watertight connection.
Prewired Cable
Flow Switch
Junction Box
Locking Collar
ARemove the four screws on the front
panel/cover to install the control box.
B
Unplug the connector that attaches
the wire to the front panel, located
in the lower right hand corner of the
control board. Set the front panel
aside.
25JP1
24
15
JP4
14
7
JP3
JP2
6
1
28

7
Installation S19-322
Bradley • 215-1845 Rev. B; ECN 17-05-068 11/21/2017
4Complete electrical supply connections
WARNING To prevent personal injury and damage to the components, follow all manufacturer's
warnings and instructions when performing any maintenance or installation of
components used in this emergency signaling system.
A
Run electric power conduit (3/4"
conduit hub, customer provided) and
AWG 18 minimum power wire into
the hole to the floating terminal block
per the wiring schematic.
B
Re-attach connector from control box
to front panel (located on the lower
right hand corner of the control board).
Compliance and conformity to local codes and
ordinances is the responsibility of the installer.
CRe-attach the cover and tighten the
four screws.
Do not exceed 14 AWG wire.
5Test the Signaling System
Testing the signaling system for the first time using the drench shower may expose the flow switch to
an unnecessary water hammer since the downstream piping may be empty of water. The flow switch is
designed to withstand such a water hammer, but using the smaller eyewash flow is recommended.
A
Apply power to the alarm branch
circuit. The alarm should remain
in the OFF position and the green
beacon light will turn on at a steady
state.
B
Open the eyewash valve. The horn
should sound and the beacon light
will become a signal light and flash
amber shortly after water flows from
the system.
C
Close the eyewash valve. Once flow
is discontinued, the horn will shut off
and the beacon/signal light return to
green steady state.
ERepeat steps A through D, this time
using the drench shower only.
Discontinuing the flow will automatically
reset the silence feature.
The signaling system is designed to work properly
even if both the eyewash and drench shower are
used simultaneously. The signaling system will
continue to operate so long as either the eyewash
or drench shower is still in use.
The horn will continue to sound and
beacon/signal light will continue to flash
as long as the fixture is activated.
See wiring diagram and schematic
on pages 11-12. DTurn on supply power to the signaling
system. Test the signaling system at
this time.

8
S19-322 Installation
11/21/2017 Bradley • 215-1845 Rev. B; ECN 17-05-068
Servicing of Lights
S19-322 LED Light/Horn Replacement
ADe-power the control box by
observing standard lock-out tag-out
practices.
B
To disconnect the wire leads of the
light requiring the bulb to be replaced,
use a small blade screwdriver to
depress the orange terminal release
tab adjacent to the wire's location.
With the tab fully depressed, the
wire can be easily removed from the
terminal location.
C
Remove the 4 nuts which attach the
light to the front panel and remove
light. This is a sealed light and has
no serviceable components, the
complete housing must be replaced.
D
Using the old light for reference,
prepare the replacement light's lead
wire and exposed conductor's lengths.
EReverse the disassemble process to
reinstall the light.
F
Check that the signaling station is
functioning properly once the power
is restored by activating the fixture
attached to the signaling station.
Signaling System Maintenance
The Bradley Emergency Signaling System is designed to be virtually maintenance free. An occasional damp cloth
wiping of the clear dust cover is all that is needed to ensure maximum visual attention-getting ability.
The horn is factory-set at the loudest possible sound level, 85 decibels at 3 feet.
Remote Sensing Option
Flow Switch Capability
If remote sensing is wanted, remove the pipe plug from the back of the junction box. Connect the extra black
wire (common to both switch arrangements) and the blue wire (normally open switch arrangement) or red wire
(normally closed switch arrangement) to your application per local electrical codes. The switch is rated at 5 amps
at 125/250VAC and is isolated from the contacts used by the signaling station. The customer supplied connections
should be of a type equal to or greater than the junction box's rating to maintain the integrity of the system.
See wiring diagram and schematic on pages 11-12.

9
Installation S19-322
Bradley • 215-1845 Rev. B; ECN 17-05-068 11/21/2017
Troubleshooting
Problem Cause Solution
The signal light and horn (if
applicable) does not operate
when water flows.
No power to the signal station. Check that the circuit breaker or fuse is supplying power to the
signal station
Component failure. Check the two 3 Amp 24VDC fuses on the print circuit board in
the signal station enclosure.
No input power. Check that there is 24VDC being supplied from the power supply
mounted on the print circuit board in the signal station enclosure.
Water flowing in wrong
direction for flow switch body.
Verify that the direction of the water flow corresponds to the arrow
on the flow switch body.
Insufficient water flow. Check that water flow is sufficient (2.4 gallons per minute is
required).
Installation error. Check all electrical connections, including power supply at the
quick-connect cable, from the signal station to the flow switch.
Horn sounds and signal light
does not light.
Component failure. Check light connections and filament in the light.
Beacon light does not
operate. (This light should
turn off when the signal light
turns on and back on when
the signal light turns off.)
Fixture in use. Make sure that the flow switch contacts are open (horn and/or
signal light are not ON).
Power disconnected in error. Check that the circuit breaker or fuse is supplying power to the
signal station.
Component failure. Check the 3 Amp 24VDC fuses on the print circuit board in the
signal station enclosure.
No input power. Check that there is 24VDC being supplied from the power supply
mounted on the print circuit board in the signal station enclosure.
Component failure. Check light connections and filament in the light.

10
S19-322 Installation
11/21/2017 Bradley • 215-1845 Rev. B; ECN 17-05-068
S19-322 Service Parts
5 6
8384
8182
80
4
3
1
2
79 90 92
91
89
93
Item Part No. Qty. Description
1 255-072 1 Enclosure, General Area
2 S90-561 1 Signaling System PCB
3 186-1910 1 Panel, Recessed Alarm
4 257-013 1 Light, 2 Color, w/ Buzzer
5 269-2454 1 Cord Grip, 3/4"-4X-200
6 269-524 1 Cond Cable, 6'
79 269-2477 1 Ring, Lug, 1/4 22-16 AWG
80 269-1421 1 Flow Switch - 1-1/4" T-DPDT
80 269-1522 1 Flow Switch - 1/2" T DPDT
Item Part No. Qty. Description
81 269-1902 1 J-Box, 1-Gang
82 269-1903 1 Cover - 1 Gang J-Box
83 269-518 1 Reducing Bushing
84 269-514 1 Cable Receptacle
89 160-490 4 Screw, #10-32x1/4" Phil
90 160-467 4 Screw, 1/4-20x3/4 PN MA
91 161-060 4 Nut, 1/4-20SS Nylon IN
92 161-026 4 Nut, 1/4-20 Hex
93 269-2460 2 Plug, 3/4" Conduit
Light/horn (item 1) includes hardware for
attaching it to panel (item 3).

11
Installation S19-322
Bradley • 215-1845 Rev. B; ECN 17-05-068 11/21/2017
Wiring Diagram
RED
(UNUSED)
BACKSIDE OF PANEL WITH
LAMP ATTACHED TO FRONT
BLK (18AWG)
WHT (18AWG)
BRN (22AWG)
YEL (22AWG)
BLK (22AWG)
GRN (22AWG)
GRY (22AWG)
UNSWITCHED
AUX OUTPUT
700mA MAX.
COMBINED
OUTPUT
± 24 VDC
28
25
JP1
24
15JP4
S90-561 CONTROL BOARD
14
7
JP3
JP2
6
1
RED
JUMPER RED
90-264VAC
INPUT
FLOATING
TERMINAL
BLOCK
WHT WHT
BLK BLK
GRN GRN
FLEX
CABLE
CONNECTOR
BLK
BLU
RED
(UNUSED)
BLU
(AUX)
RED
(AUX)
BLK
(AUX)
FLOW SWITCH (DPDT)
GROUND WIRE
CUT 3" AND
ATTACHED TO
FLOW SWITCH
JUNCTION BOX
GROUND SCREW
TOP VIEW
OF FLOW
SWITCH
#2 SWITCH
WIRE GROUP
CUT 3" LONG
FOR UNIT
WIRING
#1 SWITCH
WIRE GROUP
CUT 6" LONG
FOR AUX.
CUSTOMER
WIRING
CRIMP
CAP
NOTES:
1. Powered device is 24VDC.
2. All wires are 18 AWG unless supplied with
the device, then those wires are to be used.
3. The flow switch is shown in the no flow state.

12
S19-322 Installation
11/21/2017 Bradley • 215-1845 Rev. B; ECN 17-05-068
Schematic
FUSE
NORMALLY OPEN
SWITCH
RELAY COIL
NORMALLY OPEN
NORMALLY CLOSED
LIGHT
HORN
FLOW SWITCH
FLOW SENSOR
COMPONENT SOLDERED
WIRE
LEGEND
CONTACT
CONTACT
INTERNAL JUMPER
TERMINAL BLOCK
CONNECTION
UNSWITCHED
24 VDC OUTPUT
S83-346
S83-345
S83-344
UNSWITCHED
24 VDC OUTPUT
NORMALLY OPEN
CONNECTION
NORMALLY CLOSED
SWITCH
R4
R3
LAMP/HORN MODULE
Table of contents
Other Bradley Security Sensor manuals