manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Braeburn
  6. •
  7. Thermostat
  8. •
  9. Braeburn 229100 User manual

Braeburn 229100 User manual

TROUBLESHOOTING
SYMPTOM DIAGNOSTIC STEPS
2. Check voltage at humidifier control terminals.
There should be no voltage for Power Humidifier.
Voltage should be 20-30 VAC for most others.
3. Inspect humidifier wiring. Refer to wiring diagrams.
DO NOT LEAVE IN "ON" POSITION, OVER HUMIDIFICATION WILL OCCUR.
1. Set thermostat to operate both furnace burner and blower.
Operation may be necessary for system power.
No Humidifier
Operation in
"ON" position
1. Humidity level in the home is higher than knob setting.
Humidifier control will not operate the humidifier until
humidity level is reduced.
Humidifier
operation in
"ON" position
only
1. When the humidity in the home is less than the knob
setting, the control will operate humidifier until the
humidity is higher. Reduce knob setting.
2. Use "ON" position. Verify that the humidifier operates.
1. Check voltage at humidifier control terminals.
There should be no voltage for a Power Humidifier.
Voltage should be 20-30 VAC for most others.
2. If mounted on return air duct, make sure humidifier control
is at least 24" upstream of humidifier's air discharge.
Humidifier
turns on and
off repeatedly
3. Remove wires from control terminals. If humidifier
continues to operate, check solenoid valve.
Humidifier
operation
continuous
WIRING
WARNING! Disconnect electrical power before beginning installation.
The wiring must conform to all building codes and ordinances as required by
local and national code authorities having jurisdiction for this installation.
Refer to the following wiring diagrams.
CHECKOUT
With furnace in operation, turn humidistat to "ON" position. Observe
humidifier operation.
SETTINGS
WARNING! Do not set relative humidity too high during cold weather. Over
humidification can result in condensation, structural damage and mold.
Condensation within a building's structure can cause loss of structural
strength. Condensation can also enable mold and mildew growth resulting in
personal injury and damage to building structure and contents.
Refer to OPERATION for proper settings.
I. SAFETY
WARNING! Improper electrical wiring can result in fire or loss of humidity
control. Disconnect electrical power before installing and servicing. Failure to
disconnect electrical power may result in injury or death. The wiring must
conform to all building codes and ordinances as required by local and
national code authorities having jurisdiction for this installation.
The 229100 must be installed by a qualified Technician. Failure to properly
install the 229100 may result in property damage or personal injury.
Homeowners must read instructions and understand the operation of the
229100 and the humidifier(s) it controls.
Improper operation can result in over or under humidification. Over
humidification can result in condensation, structural damage and mold.
Condensation within a building's structure can cause loss of structural
strength. Condensation can also enable mold and mildew growth resulting in
personal injury and damage to building structure and contents.
OUTDOOR
TEMPERATURE
RECOMMENDED
SETTING
INSTALLER:
PLEASE LEAVE OWNERS MANUAL WITH HOME OWNER.
HUMIDISTAT OWNERS MANUAL
II. APPLICATION
The 229100 humidistat provides low voltage control of humidifiers installed in
central heating systems. The humidistat has a SPST switch and is designed
for mounting on the return air duct.
RANGE: 10% to 85% RH ELECTRICAL RATING: 30 VAC / 60 VA
OPERATION
Set the control knob to the desired humidity
setting. The recommended setting for
optimum humidification is 30% to 50%. The
vertical position on the knob is approximately
42% RH.
Setting the humidistat above or below the
recommended settings may not provide
satisfactory results for your home.
229100
40°F 4°C 45
30°F -1°C 40
20°F -7°C 35
10°F -12°C
0°F -18°C
30
25
-10°F - 23°C
-20°F -29°C
20
15
III. INSTALLATION INSTRUCTIONS
PRECAUTIONS
The installer must be a qualified technician. Disconnect electrical power
before beginning installation. Do not install the humidistat on the warm air
duct. Conduct a thorough checkout before leaving the installation.
DUCT MOUNTING ON THE RETURN AIR - PREFERRED METHOD
Do not install the humidistat on the warm air duct or within 48” of UV light.
1. Locate the humidistat at least 24" upstream of the humidifier or
bypass on the return air duct. Avoid areas of direct radiation like
secondary heat exchangers in the fan compartment.
2. Remove face by inserting screwdriver into pry slot and twisting
(see fig 2)
3. Use the plastic duct mount plate as a template. Accurately mark and
drill the (4) 3/32”mounting holes and cut away the 4-1/4” x 2-1/2”
section of the duct inside the duct mount plate.
4. Place duct mount base gasket on the humidistat base and mount the
base with four screws. Low voltage wire may enter the humidistat
under the gasket (see fig 2).
5. Connect wires to screw terminals on the control assembly as shown in
wiring diagrams. Replace face and knob.
WALL MOUNTING INSTRUCTIONS
NOTE: Requires wall mount kit (Model 229110)
1. Chose a location for the 229100 about five feet above the floor
on an inside wall with average room temperature and relative
humidity conditions.
2. Drill a small hole in the wall and run low voltage wiring to the
location chosen. Pull about 6” of wire through the hole. Use the entire
mounting gasket (both inside and outside portions) to seal the wall
opening or use foam tape to prevent drafts from affecting the
humidistat operation. (see fig. 3)
3. Remove the knob on the humidistat. Squeeze the top and
bottom of the base to release the face of the humidistat.
4. Mount the base horizontally over the wires. Attach directly to
the wall, using the two screws provided in the slotted holes.
5. Connect wires to screw terminals on the control assembly as
shown in wiring diagrams. Replace face and knob.
©2014 Braeburn Systems LLC • All Rights Reserved • 229100-100-002 (MHX3-06B REV B)
Braeburn Systems LLC
2215 Cornell Avenue • Montgomery, IL 60538
Technical Assistance: www.braeburnonline.com
Call us toll-free: 866-268-5599 (U.S.)
630-844-1968 (Outside the U.S.)
ACC
EAC
(HOT)
C
115v.
60CY.
ON-OFF SWITCH
COMMON LEAD
FURNACE
C
HI
LO
229050
CURRENT
SENSING
RELAY
MULTI
SPEED
BLOWER
MOTOR
24V. SOLENOID VALVE
HUMIDISTAT
24 V. TRANSFORMER
ACC
EAC
(HOT)
C
115v.
60CY.
ON-OFF SWITCH
24V. SOLENOID VALVE
24V. SOLENOID VALVE
24 V. TRANSFORMER
L1
C
NO
(HOT)
L2
115v.
60CY.
ON-OFF SWITCH
AIR PRESSURE
SWITCH
24 V. TRANSFORMER
HUM
FURNACE
CONTROL BOARD
C
24v.
60CY.
24V. SOLENOID VALVE
HUMIDISTAT
HUMIDISTAT
HUMIDISTAT
FURNACE
BOARD
Braeburn Systems LLC warrants each new Braeburn humidistat against any defects that are due to faulty material or workmanship for a period of one year after
the original date of purchase by a professional service technician. This warranty and our liability does not include damage to merchandise or the humidistat
resulting from accident, alteration, neglect, misuse, improper installation or any other failure to follow Braeburn installation and operating instructions.
Braeburn Systems LLC agrees to repair or replace at its option any Braeburn humidistat under warranty provided it is returned postage prepaid to our warranty
facility in a padded carton within the warranty period, with proof of the original date of purchase and a brief description of the malfunction. This limited warranty
does not include the cost of removal or re-installation.
This warranty gives you specific legal rights and you may also have other rights that vary from state to state or province to province. Answers to any questions
regarding our limited warranty may be obtained by writing our corporate offices.
LIMITED WARRANTY
ACC
EAC
HOT
MANUAL HUMIDISTAT
120 VAC WITH CONTROL FROM FURNACE BOARD
FURNACE
OR FAN
CONTROL
120 VAC
FURNACE
CONTROL
FIELD SUPPLIED
RECEPT & SWITCH
C
HUMIDIFIER
RED
POWER TO HUMIDISTAT
YELLOW
CONTROL
NOTE: Red wires are for humidistat power if required.
DO NOT CONNECT RED WIRES TO ANOTHER POWER
SOURCE OR ONE ANOTHER. DOING SO WILL VOID WARRANTY.
NOTE:Yellow wires are for Humidistat Control. DO NOT APPLY VOLTAGE
TO YELLOW WIRES. DOING SO WILL VOID WARRANTY.
CAP OFF -
DO NOT CONNECT
TOGETHER
HUMIDISTAT
HOT
MANUAL HUMIDISTAT
120 VAC WITH CURRENT SENSING RELAY
FIELD SUPPLIED
RECEPT & SWITCH
C
HUMIDIFIER
RED
POWER TO HUMIDISTAT
YELLOW
NOTE: Red wires are for humidistat power if required.
DO NOT CONNECT RED WIRES TO ANOTHER POWER
SOURCE OR ONE ANOTHER. DOING SO WILL VOID WARRANTY.
NOTE:Yellow wires are for Humidistat Control. DO NOT APPLY
VOLTAGE TO YELLOW WIRES. DOING SO WILL VOID WARRANTY.
CURRENT
SENSING
RELAY
SINGLE OR
MULTI-SPEED FAN
C
HI
LO
CAP OFF -
DO NOT CONNECT
TOGETHER
HUMIDISTAT
WARRANTY
FACILITY: Braeburn Systems LLC
Attn: Warranty Department
2215 Cornell Avenue
Montgomery, IL 60538
PRECAUTIONS
The installer should be a qualified Technician. Disconnect electrical power before beginning installation. Use contacts C and NO
for humidifier operation. Use contacts C and NC for a dehumidifier. Conduct a thorough checkout before leaving the installation.
WIRING DIAGRAMS FOR BRAEBURN®220500 and 220600 HUMIDIFIERS
WIRING DIAGRAMS FOR BRAEBURN®220700 HUMIDIFIER
On furnaces with output terminals ACC, or EAC check output voltage to determine
that terminals are 115V. Connect on-off switch in series with the hot wire. On furnaces where it is desirable to use a current sensing relay, the
humidifier may be wired from a continuous 115 volt power source. Install the
on/off switch in series with the hot or black wire. Install the Braeburn®229050
Current Sensing Relay in series with the humidistat circuit. The Current
Sensing Relay will detect furnace operation and supply power to the
humidifier accordingly.
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
USE BOTH WITH
WALL MOUNTING
USE WITH DUCT
MOUNTING ONLY
USE OUTSIDE
PORTION ONLY
WITH DUCT
MOUNTING
GASKET PLACEMENT
FIG. 3*
DUCT MOUNT
VERSION
FIG. 2
DUCT MOUNT BASE
DUCT MOUNT BASE
GASKET
SCREWDRIVER PRY SLOT
WALL MOUNT BASE (229110)
(can mount on duct with
gaskets shown)
*Requires wall mount kit (Model 229110)

Other Braeburn Thermostat manuals

Braeburn 2020 Operating and maintenance manual

Braeburn

Braeburn 2020 Operating and maintenance manual

Braeburn 3020 Instructions for use

Braeburn

Braeburn 3020 Instructions for use

Braeburn 7320 User manual

Braeburn

Braeburn 7320 User manual

Braeburn 165 User manual

Braeburn

Braeburn 165 User manual

Braeburn 1020NC User manual

Braeburn

Braeburn 1020NC User manual

Braeburn 6100 Assembly instructions

Braeburn

Braeburn 6100 Assembly instructions

Braeburn 5020 User manual

Braeburn

Braeburn 5020 User manual

Braeburn Premier 5100 User manual

Braeburn

Braeburn Premier 5100 User manual

Braeburn 5200 User manual

Braeburn

Braeburn 5200 User manual

Braeburn 3020 User manual

Braeburn

Braeburn 3020 User manual

Braeburn 1200 User manual

Braeburn

Braeburn 1200 User manual

Braeburn Builder 1000NC User manual

Braeburn

Braeburn Builder 1000NC User manual

Braeburn Premier 5100 User manual

Braeburn

Braeburn Premier 5100 User manual

Braeburn Economy 2030 User guide

Braeburn

Braeburn Economy 2030 User guide

Braeburn 3020 Assembly instructions

Braeburn

Braeburn 3020 Assembly instructions

Braeburn 7320 User manual

Braeburn

Braeburn 7320 User manual

Braeburn Premier 5300 User manual

Braeburn

Braeburn Premier 5300 User manual

Braeburn 3000 User manual

Braeburn

Braeburn 3000 User manual

Braeburn 5200 User manual

Braeburn

Braeburn 5200 User manual

Braeburn 2010 User manual

Braeburn

Braeburn 2010 User manual

Braeburn 3100 User manual

Braeburn

Braeburn 3100 User manual

Braeburn 3020 User guide

Braeburn

Braeburn 3020 User guide

Braeburn Builder 2200 User manual

Braeburn

Braeburn Builder 2200 User manual

Braeburn 1020NC User manual

Braeburn

Braeburn 1020NC User manual

Popular Thermostat manuals by other brands

EPH Controls R37 operating instructions

EPH Controls

EPH Controls R37 operating instructions

Geca Roma manual

Geca

Geca Roma manual

Bticino KW4691 manual

Bticino

Bticino KW4691 manual

Bryant TSTATCCPS101 installation instructions

Bryant

Bryant TSTATCCPS101 installation instructions

Lux Products P722Ua Installation and operating instructions

Lux Products

Lux Products P722Ua Installation and operating instructions

ApenGroup SMART WEB Series Operating, Installation and Programming Manual

ApenGroup

ApenGroup SMART WEB Series Operating, Installation and Programming Manual

Sygonix MH-912 operating instructions

Sygonix

Sygonix MH-912 operating instructions

Honeywell Easy-To-See POWERPILE TS86A Homeowner's guide

Honeywell

Honeywell Easy-To-See POWERPILE TS86A Homeowner's guide

Watlow Electric SERIES146 user manual

Watlow Electric

Watlow Electric SERIES146 user manual

Zehnder Rittling ComfoControl Luxe Installer manual

Zehnder Rittling

Zehnder Rittling ComfoControl Luxe Installer manual

Honeywell Digital Round T8775A owner's guide

Honeywell

Honeywell Digital Round T8775A owner's guide

Heatmiser PRT-WTS user manual

Heatmiser

Heatmiser PRT-WTS user manual

S.M.S.L M500 MKII user manual

S.M.S.L

S.M.S.L M500 MKII user manual

Danfoss DEVIreg Smart installation guide

Danfoss

Danfoss DEVIreg Smart installation guide

Toptech TRUE COMFORT III TT-S-925 installation manual

Toptech

Toptech TRUE COMFORT III TT-S-925 installation manual

ritetemp 8050 install guide

ritetemp

ritetemp 8050 install guide

Honeywell CT55N owner's manual

Honeywell

Honeywell CT55N owner's manual

Honeywell T8000C owner's guide

Honeywell

Honeywell T8000C owner's guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.