Brant Radiant Heaters Patio-Pal PH Series User manual

Patio-Pal© PH Series Patio Heater Installation, Operation, Maintenance and Parts Manual
This heater must be installed and serviced by trained gas installation and service personnel only! Improper
installation, adjustment, alteration, service, or maintenance can cause property damage, injury or death. Read
and understand the instructions thoroughly before installing or servicing equipment. Retain these instructions
for future reference.
Not for indoor residential use. This heater is NOT approved for use in any INDOOR residential application.
This includes, but is not limited to, attached garages, solarium, living quarters, etc. Installation in indoor
residential spaces may result in property damage, asphyxiation, serious injury, or death. Consult your local re
marshal and/or insurance provider if unsure of your application.
Interdit pour usage résidentiel. Ne pas utiliser cet appareil à la maison, dans les chambres à coucher, dans
les harages attenants, etc.
This is NOT an explosion proof heater. Where there is a possibility of exposure to ammable vapors, consult
the local re marshal, the re insurance carrier and other authorities for approval of proposed installation.
Cet émetteur n’est pas un appareil antidéagrant. Lorsqu’il y a risque de contact avec des vapeurs
inammables, consulter le commissaire local des incendies, la compagnie d’assurance incendie ou tout autre
authorité compétente pour approbation de l’installation.
Storage of gasoline and other ammable vapors and liquids in the vicinity of this or any other appliance may
result in re or explosion. Do not store or use gasoline or other ammable vapors and liquids in the vicinity of
this or any other appliance. Maintain clearance to combustibles.
Il est interdit d’utiliser des liquides inammables ou dégageant des vapeurs inammabled à proximité de tout
appareil fonctionnant au gaz.
For Indoor/Outdoor Commercial Use.
For Outdoor Residential Use.
WARNING! / ADVERTISSEMENT!
FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. Do not touch electrical switches.
3. Shut off gas to the appliance.
4. Extinguish any open ame.
5. If odor continues, immediately call your gas supplier.
CONSIGNES DE SÉCURITÉ
Si vous sentez une odeur de gaz:
1. Ouverez les fenêtres.
2. Ne touchez pas aux interrupteurs électriques.
3. Couper l’alimentation de gaz vers l’appareil.
4. Éteignez toute amme nue.
5. Contactez immédiatement votre compagnie de gaz.
Patio-Pal©
PH Series
Gas-Fired High-Intensity
Infra-Red Patio Heater
Brant Radiant Heaters Limited
34 Scott Ave. P.O. Box 395
Paris, Ontario, Canada N3L 3T5
Tel: 519-442-7823 Fax: 519-442-7321
1-800-387-4778
www.brantradiant.com
Form No. PH0608

Contents
2
1.0 Safety 3
Warning Symbols 3
Application Considerations 3
Clearance to Combustibles 5
Gas Connection 6
Safety Signs & Labels 7
2.0 Installation 8
Design 8
Heater Mounting 10
Gas Supply 12
Electrical Requirements 15
Ventilation 16
3.0 Operation 17
Sequence of Operation 17
Wiring Diagrams 18
4.0 Maintenance 19
General Maintenance 19
Troubleshooting Guide 20
5.0 Parts 21
Heater Components and Parts List 21
6.0 Limited Warranty 23

WARNING!
This heater must be installed and serviced by trained gas installation and service personnel only!
Improper installation, adjustment, alteration, service, or maintenance can cause property damage,
injury or death. Read and understand the instructions thoroughly before installing or servicing
equipment.
CAUTION
WARNING!
NOTICE
Warning Symbols
Safety is the most important consideration during installation and maintenance of the infra-red heater. You will see the
following symbols and signal words when there is a hazard related to safety or property damage.
Application Considerations
• Infra-red heaters are designed and certied for use in industrial and commercial buildings such as outdoor restaurant
patios, warehouses, manufacturing plants, aircraft hangers and vehicle maintenance shops. For maximum safety, the
building must be evaluated for potential hazards before installing the heating system. A critical safety factor to consider
before installation is the clearances to combustibles.
• This heater may only be used in outdoor residential applications and is NOT approved for use in any indoor
residential application. This includes, but is not limited to, attached garages, living quarters, solarium, etc. Consult the
local re marshal and/or insurance provider if unsure of your application.
• The installation of this heater must conform with local building codes or, in the absence of local codes, with the current
CAN/CSA B149.1 and 2 and with the Canadian Electrical Code C22.1-latest edition.
• Check the CSA rating label on the heater to verify model number. Check and maintain the attached minimum
clearances to combustibles label and the proper gas to be used. Check all labels on the heater to verify proper
mounting.
• If an external electrical source is utilized, the heater must be electrically grounded in accordance with the Canadian
Electrical Code C22.1-latest edition.
• The installation of this heater in public garages must conform with the Canadian Electrical Code C22.1-latest edition
when an external source is utilized.
• In the installation for aircraft hangers, the heater must be installed at least 10 ft. (3 m) above upper wing surface and
engine enclosures of the highest aircraft which might be stored in the hanger. In areas adjoining to the aircraft storage
area, the heaters must be installed at least 8 ft. (2.4 m) above oor. The heater must be located in areas where they
will not be subject to contact by aircraft, cranes, moveable scaffolding or other objects.
• Under no circumstance is either the gas supply line or the electrical supply line to the heater to provide any assistance
in the suspension of the heater. The weight of the heater must be entirely suspended from a permanent part of the
building structure having adequate load characteristics.
1.0 Safety
1.0 Safety • Warning Symbols • Applications
Warning indicates a potentially hazardous situation
which, if not avoided, could result in death or injury.
Caution indicates a potentially hazardous situation
which, if not avoided, could result in minor or moderate
injury.
Notice indicates a potentially hazardous situation which,
if not avoided, could result in property damage.
3

WARNING!
• Neither the gas supply line, electrical supply line nor sprinkler heads shall be located in or near the path of the flue
products from the heater.
• The heater cannot be used in a building with an uninsulated roof or condensation problems could result.
• When installed indoors (Commercial/Industrial Applications Only), natural or mechanical means shall be provided to supply
and exhaust at least 4.0 (Natural) or 4.5 (L.P.) C.F.M. per 1000 BTU/H of the heater’s rated input.
Application Considerations cont’d
Improperly connected gas lines may result in serious injury or death, explosion, poisonous fumes, toxic
gases, asphyxiation. Connect all gas lines in accordance to national, provincial and local codes.
Placement of explosive objects, ammable objects, liquids and vapors close to the heater may result in
explosion, re, property damage, serious injury or death. Do not store, or use, explosive objects, liquids
or vapor in the vicinity of the heater.
Failure to comply with the published clearances to combustibles could result in personal injury, death
and/or property damage.
In locations used for the storage of combustible materials, signs must be posted to specify the maximum
permissible stacking height to maintain the required clearances to combustibles. Signs must either be
posted adjacent to the heater thermostats or in the absence of such thermostats, in a conspicuous
location.
Hazards Include:
For maximum safety the building must be evaluated for hazards before installing heating system. Examples include,
but are not limited to:
• Gas and electrical lines • Vehicle parking areas
• Combustible and explosive materials • Vehicles with lifts or cranes
• Chemical storage areas • Storage areas with stacked materials
• Areas of high fume concentration • Lights
• Provisions for accessibility to the heater • Sprinkler heads
• Adequate clearances around air openings • Overhead doors and tracks
• Combustion and ventilating air supply • Dirty, contaminated environment
A critical safety factor to consider before installing the heater is the clearances to combustibles. Clearance to
combustibles is dened as the minimum distance you must have between the infra-red surface, or reector and the
combustible item. Considerations must also be made for moving objects around the infra-red heater. The following is a
partial list of items to maintain clearances from:
Combustible Items: Moving Objects:
• Wood • Overhead doors
• Paper/Cardboard • Vehicle lifts
• Fabric • Cranes
• Chemicals • Hoists
• Wall or roof insulation • Car was equipment
When installing the infra-red heating system, the minimum clearances to combustibles must be maintained. These
distances are shown in Chart 1.1 and on the minimum clearance to combustibles label found on the heater. If you are
unsure of potential hazards, consult your local re marshall, re insurance carrier or other qualied authorities on the
installation of gas red infra-red heaters for approval of the proposed installation.
1.0 Safety • Applications • Clearance to Combustibles
4

1.0 Safety • Clearance to Combustibles
* Heaters mounted on an angle between 0° to 30° must maintain clearances posted for 0° or 30°; whichever is
greater.
Important! If the heater is mounted beneath a non-combustible surface an 8 in. minimum top clearance must be
maintained from the top of the heater to prevent overheating the controls.
Clearance to combustible distances represent a surface temperature of 90° F (32°C) above ambient. Ensure that
building materials with a low heat tolerance (i.e. awnings, fabrics, plastics, sprinklers, insulation) are protected
against degradation. This may require the heater to be mounted at a distance in excess of the published clearances
to combustibles. Contact the factory.
Model No. Mounting
Angle* Sides Back Top Below End(s) Front
PH 28 (-SS)
28,000 [N,P]
0° 14”/35.6cm N/A 13”/33.0cm 46”/116.8cm 22”/55.9cm N/A
30° N/A 8”/20.3cm 17”/43.2cm 46”/116.8cm 22”/55.9cm 46”/116.8cm
PH 31 (-SS)
31,000 [N,P]
0° 14”/35.6cm N/A 13”/33.0cm 46”/116.8cm 22”/55.9cm N/A
30° N/A 8”/20.3cm 17”/43.2cm 46”/116.8cm 22”/55.9cm 46”/116.8cm
PH 34 (-SS)
34,000 [N,P]
0° 14”/35.6cm N/A 13”/33.0cm 46”/116.8cm 22”/55.9cm N/A
30° N/A 8”/20.3cm 17”/43.2cm 46”/116.8cm 22”/55.9cm 46”/116.8cm
Chart 1.1 •Clearance to Combustibles in Inches and CM (see Figure 1.1)
Figure 1.1 •Clearance to Combustibles
Top
(to ceiling)
Side Side
Below Below
Top
(to ceiling)
Back
Front
Inlet side down
End End
END VIEW
0° MOUNTING ANGLE
END VIEW
30° MOUNTING ANGLE
SIDE VIEW
30°
5

IMPORTANT: Fire sprinkler heads must be located at an appropriate distance from the heater. This distance may
exceed the published clearance to combustibles. Certain applications will require the use of high temperature
sprinkler heads or relocation of heaters.
Potentially flammable substances, such as Propylene Glycol or antifreeze solutions, are not to be used in
conjunction with this heater.
For further information consult CAN/CSA B149.1 and 2. Always observe applicable provincial and local codes.
1.0 Safety • Gas Connection
An approved connector, suitable for the environment of equipment usage, is required. Visible or excessive swaying, flexing
and vibration of the gas connection must be avoided to prevent failure. Neither the gas pipe nor the connector shall be
placed in the flue discharge area or in direct contact with the infra-red rays. In no case shall the gas supply support or bear
the weight of the heater.
Brant Radiant Heaters Limited’s products comply or are certified by one or more of the following organizations or
standards:
• CSA International Requirement (CSA 2.37/5.90 U.S.)
Gas Connection
WARNING!
6

1.0 Safety • Safety Signs and Labels
Safety Signs and Labels
It is important to provide warnings to alert individuals to potential hazards and safety actions. CODE requires you to
post a sign “specifying the maximum permissible stacking height to maintain the required clearances from the heater
to the combustibles” near the heater’s thermostat or in absence of such thermostat, in a conspicuous location.
Safety warning labels must be maintained on the infra-red heater. Illustrations of the safety labels, and their locations,
are pictured below. In locations used for storage, signs must be posted to specify the maximum permissible stacking
height to maintain the required clearances from the heater to combustibles. Signs must either be posted adjacent to
the heater thermostats or in absence of such thermostats, in a prominent location.
Observe Proper Gas Type (Natural Gas or LP Gas)
Clearance Safety Tag
(Afx adjacent to heater’s thermostat)
Patio Heater Clearance to Combustibles Label
Top Panel
7

CAUTION!
Read and understand, the installation, operating and maintenance instructions thoroughly before
installing or servicing this equipment.
Only trained, qualied gas installation and service personnel may install or service this equipment.
NOTICE
Design
To ensure a safe, properly designed heating system, a layout should be developed for the correct placement of the
infra-red heater(s). Aside from safety factors such as clearance to combustibles (see Chart 1.1 on page 5), you should
take into consideration:
• The environment (e.g., is it cold/drafty, average, protected)?
NOTE: The effective infra-red surface temperature of a person or object may be
diminished with wind above 5 mph, wind barriers may be required.
• What is the area of heat coverage (e.g., sq. ft.) needed (Chart 2.1, Figure 2.2).
• Is the heater being used in a social gathering area or work station(s)?
• The mounting height of the heater (Chart 2, Figure 2.2).
• Type of mounting to be used.
• Physical space needed for the heater (Figure 2.1).
• Gas supply and connections.
• Combustion, ventilating air supply and exhaust path.
• Electricity and wiring to the heater.
IMPORTANT: Fire sprinkler heads must be located at an appropriate distance from the heater. This distance may
exceed the published clearance to combustibles. Certain applications will require the use of high temperature sprinkler
heads or relocation of the heaters.
Sprinkler systems containing propylene glycol or other flammable substances are not to be used in conjunction
with this heater without careful consideration for and avoidance of potential fire or explosions hazards. For further
information consult CAN/CSA B149.1 and 2. Always observe applicable provincial and local codes.
2.0 Installation
Radiant heat is capable of damaging or destroying certain materials or items. Do not store materials or items underneath
the heater. Always maintain clearance to combustibles.
This heater cannot be used in a building with a roof that is not insulated or where condensation problems can occur.
8

2.0 Installation • Design
Figure 2.1 •Heater Dimensions
SIDE VIEW END VIEW
Chart 2.1 •Recommended Mounting Heights
Figure 2.2 •Recommended Mounting Heights
Model & Input
Recommnded
Mounting Height
(Dim. A)
Approximate
Coverage Area
Approximate Coverage
(sq. ft.)
PH-28
28,000 BTU/H 8’-0” to 8’-6” 7’ x 7’ 49 sq. ft.
PH-31
31,000 BTU/H 8’-0” to 9’-0” 8’ x 8’ 64 sq. ft.
PH-34
34,000 BTU/H 8’-6” to 10’-0” 9’ x 9’ 81 sq. ft.
Note: This chart is provided as a guideline. Actual conditions dictate variances from this data.
9

WARNING!
Heater Mounting
2.0 Installation • Heater Mounting
Improper suspension of the infra-red heater may result in collapse and persons being crushed.
Always suspend from a permanent part of the building structure that can support the total force and
weight of the heater.
Failure to maintain minimum clearance to combustibles may result in re and/or explosion, property
damage, serious injury or death. Always maintain minimum clearances and post signs or provide
tags where needed. Signs should state the hazards for the particular application and be legible for
the building occupants. Consult the factory or a factory representative for additional information on
signage compliance.
The heater can be suspended with chains or rigid threaded rod. Local codes, or conditions such as wind drafts or
other variables, can cause movement of the heater and may require rigid threaded rod. Avoid excessive movement
and/or vibration of the gas connection by rigidly mounting the heater (see Figure 2.4). The Brant Radiant optional patio
heater mounting brackets (P/N: PH-BKT) can be used in place of rigid threaded rods. Consult all applicable codes
before installation.
The heater must be level from side to side and can be set at an angle betwen 0° and 30° from horizontal. The gas
connection and power cord must be located on the lower side (see Figure 2.3).
Figure 2.3 •Heater Orientation
When mounting the heater
on an angle, the gas inlet and
power cord must be located
towards the lower side of the
heater (towards the oor).
Optional mounting
bracket (P/N: PH-BKT)
10

2.0 Installation • Heater Mounting
Figure 2.4 shows different types of mounting congurations. Depending on the type of mounting you
use, be sure to:
Prepare mounting surface. If necessary, weld blocks to mounting structure, drill holes, etc.
Fasten beam clamp, screw hook or other type of suspension anchor to hanging point.
Attach and close S-Hook (P/N: S-HOOK) and #1 double-loop (P/N: BR-CS includes 5 ft.
chain and 2 S-hooks, 4 required) to anchor. Check that it is securely attached.
Attach heater to chains. Adjust chain lengths until the heater is level and equal weight
distribution is achieved. Chains must be straight up and down, do not install chains at an
angle.
Figure 2.4 •Heater Mounting
I-Beam
Optional mounting
bracket (P/N: PH-BKT)
attached to ceiling.
Wood Beam Concrete Beam
Steel C-clamp
Screw Hook
S-Hook and
#1 double-loop
chain (recommended)
Bar Joist Clip
Rigid threaded rod
and turnbuckle
(eld supplied).
0° Mounting Angle 30° Mounting Angle
30° Mounting Angle
0° Mounting Angle
0-30° 0-30° 0-30°
0-30°
0-30°
Optional mounting
bracket (P/N: PH-BKT)
attached to sidewall.
11
1
2
3

WARNING!
Gas Supply
2.0 Installation • Gas Supply
Improperly connected gas lines may result in re, explosion,
poisonous fumes, toxic gases, asphyxiation and death.
Connect gas lines in accordance with national, provincial and local
codes.
The gas supply to the infra-red heater must be connected and tested in accordance with national, provincial and local
codes along with the guidelines in the Brant Radiant Heaters PH Series Manual. Refer to the latest edition of the CAN/
CSA B149.1 and 2.
Important! Before connecting the gas supply to the infra-red heater(s):
• Check for conditions such as drafts or other variables with might cause excessive movement of the unit
and cause damage to the gas connection. Ensure that the unit is securely mounted and connect the gas
with an approved connection device suitable for the environment of use.
• Check that the gas piping and service has the capacity to handle the load of all heaters being installed, as
well as any other gas appliances being connected to the supply line.
• Check that the main gas supply line is of proper diameter to supply the required fuel pressures.
• If utilizing used pipe, verify that its condition is clean and comparable to a new pipe. Test all gas supply
lines in accordance with local codes.
• Test and conrm that the inlet pressures are correct. Refer to the rating plate for required minimum and
maximum pressures. The gas supply pipe must be of sufcient size to provide the required
capacity and inlet pressure to the heater (if necessary, consult the local gas company).
• For pressure in excess of 1/2 psig (3.5 kPa), the heater and ball shutoff valve must be disconnected from
the gas supply piping system during any pressure testing.
• For test pressures equal to or less than 1/2 psig (3.5 kPa), the heater must be isolated from the gas
supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas
supply piping system.
Chart 2.2 •Manifold Pressure
Type of Gas Required Manifold
Pressure
Minimum Inlet
Pressure
Maximum Inlet
Pressure
Natural 5.0 in. W.C.P. 6.0 in. W.C.P. 14.0 in. W.C.P.
Liquied Petroleum 10.0 in. W.C.P. 11.0 in. W.C.P. 14.0 in. W.C.P.
Note: Check manifold pressure at tap on ball shutoff valve. Readings will be above atmospheric pressure during
operation.
Pressure Equivalents: 1 in. W.C.P. equals .058 oz./sq. in. equals 2.49 Mbar.
12

WARNING!
Failure to install, operate or service this appliance in the approved manner may result in property
damage, injury or death. This heater must be installed and serviced by trained gas installation and
service personnel only.
The installation of this heater must conform with local building codes or, in the absence of such
codes, the CAN/CSA B149.1 and 2.
The gas outlet must be in the same room as the appliance and be accessible. It may not be concealed within or run
through any wall, oor or partition.
Install a sediment trap / drip leg if condensation may occur at any point of the gas supply line. This will
decrease the possibility of loose scale or dirt in the supply line entering the heater’s control system and
causing a malfunction. Note: High pressure gas above 14.0 W.C.P. (water column pressure) requires a high
pressure regulator and ball valve (eld supplied).
A Stainless Steel Gas Connnector (field supplied) formed into a smooth C-shape is recommended (Figure
2.5). If local codes prohibit the use of a gas hose, then a swing joint may be used.
Attach the ball valve (field supplied) to the gas supply pipe. Apply pipe compound to NPT adapter threads to
seal the joint. Use only pipe compound resistant to liquid petroleum.
Note: Provide a 1/8 in. NPT plugged tapping, accessible for test guage connection, immediately upstream of
gas connection to the heater (provided on ball valve, when supplied).
Attach a gas connector (field supplied) to the adapter and the heater’s gas inlet. Seal the joints.
Important! The ttings (nuts) on the exible connector (eld supplied) must be connected to an adapter.
They may not be directly connected to the gas supply pipe.
Excessive torque on the manifold may misalign the orifice. Always use two wrenches to tighten mating pipe
connections.
Final assembly must be tested for gas leaks according to CAN/CSA B149.1 and 2 or local codes.
WARNING!
Testing for gas leaks with an open ame or other source of ignition may lead to re or explosion and
cause serious injury or death. Test in accordance with CAN/CSA B149.1 and 2 or local codes.
To connect the gas:
To disconnect gas:
Disconnect the power to the heater.
Turn off the gas supply to the heater and “bleed” the gas line.
Using two wrenches, slowly loosen the ttings. Excessive torque on the manifold may misalign the orice.
Inspect the hose and ttings for abrasion, wear or damage. Replace if necessary.
2.0 Installation • Gas Supply
13
1
2
3
4
5
6
1
2
3
4

WARNING!
Failure to disconnect the electricity to the heater before disconnecting the gas supply may result
in explosion, re, property damage, injury or death.
WARNING!
Conditions such as wind drafts or other variables can cause movement of the heater and may require
it to be rigidly mounted. Avoid excess movement and/or vibration of the gas connection by rigidly
mounting the heater.
2.0 Installation • Gas Supply
Figure 2.5 • Gas Connection (shown installed with a exible hose)
Regulator
(eld supplied
when required)
Shut off valve
(eld supplied)
Drip leg / Sediment trap
(eld supplied)
Shut off valve / inlet tap
Stainless steel gas connector
(eld supplied), formed into
smooth C-shape.
Optional
mounting
bracket
(P/N: PH-BKT)
Elbows
(eld supplied)
14

WARNING!
Incorrect or improper wiring may result in shock, injury or death. Field wiring to the heater must be
connected and grounded in accordance with national, provincial, local codes and to the guidelines
in this manual. Refer to the most current revisions to the CAN/CSA B149.1 and 2.
2.0 Installation • Electrical Requirements
NOTICE
Radiant heat may damage the flexible power cord. Always keep the flexible power cord away from the heater. Do not allow
the power cord to be subjected to radiant heat.
Control systems are initilized by either 120V or optional 24V control voltage. A 120V system can be operated directly
with 120V to the heater. Heaters with the optional relay can be controlled with 24V.
Transformers (sold seperately) must be used to supply power of sufcient VA rating for single or multiple connected
installations.
Important! Proper grounding and polarity are essential. If the system is not properly grounded, it cannot determine
the presence of a ame and will lockout and shut off.
For wiring of controls see Figure 2.7 below. It is recommended that the control be installed on the hot side of a fused
supply line and have a sufcient ampere capacity rating for the heater(s) it will control (see Figures 3.1 & 3.2).
Figure 2.7 •Typlical Field Wiring
Optional
mounting
bracket
(P/N: PH-BKT)
Optional
mounting
bracket
(P/N: PH-BKT)
120V black
power cord
120V black
power cord
PH Series
Heater
PH Series
Heater
24V yellow
control cord
120V thermostat,
timer or switch
(eld supplied)
Hot
Neutral
+ Hot
- Neutral
120V 24V
Transformer
PH Series 120V PH Series 120V with 24V Control (PH-24VAO)
15

WARNING!
Ventilation
2.0 Installation • Ventilation
Improper or insufcient ventilation may result in explosion, re, health problems,
carbon monoxide poisoning or death. Vent enclosed spaces and buildings according
to national, provincial and local codes.
The infra-red heater must be vented in accordance with national, provincial and local codes and the guidelines in the
Brant Radiant Heaters PH Series manual. Refer to the lastest edition of the CAN/CSA B149.1 and 2.
It is required that the upper levels of the space to be heated are properly ventilated to supply combustion air to the
heaters and to sufciently dilute the products of combustion. It is also important to keep the ue discharge area clear
of gas piping and electrical wiring (see Figure 2.6).
Provisions must also be made to provide sufcient fresh air intake area and exhaust air outlet area. Natural or
mechanical means shall be provided to supply and exhaust at least 4.0 C.F.M. per 1000 BTU/H of natural gas input,
4.5 C.F.M per 1000 BTY/H of L.P. gas input. Exhaust openings for the removal of ue products must be above the
level of the heater(s).
When insufcient air movement exists, induced air displacement is required. A balanced system is essential to avoid
negative building pressure which causes excessive inltration, unfavorable drafts and affects combustion efciency.
Air displacement may be accomplished by either gravity or mechanical means. Mechanical exhausters are preferred
and typically mounted at high points in the ceiling over where stagnant air accumulates inside. For a at roof,
considerations of prevailing winds, high and low pressure areas, and distribution of air movement must be taken into
consideration when locating exhausters.
Best air distribution is accomplished by using a number of small exhausters versus one large exhauster. Provide a
minimum of one square inch of inlet area per 1000 BTU/H for combustion air supply. Inlet openings in the building
should be well distributed, located high on the wall and should direct incoming air upward to dilute products of
combustion while preventing drafts at lower levels. Inlets are typically 1 to 3 sq. ft.
In certain applications, local codes may require that mechanical exhaust systems be interlocked with the heater(s) to
enable both to function simultaneously or allow control of exhausters with a ceiling mounted humidistat.
Figure 2.6 •Hot Flue Discharge
16
Discharge released from side
air channels. Keep area clear of
gas piping and electrical wiring.

Improper operation of the heater may result in explosion, re, shock and carbon
monoxide poisoning. Follow all guidelines and warnings in this manual and national,
provincial and local codes. Always conduct safety checks before operating this
heater. Do not operate the heater in unsafe conditions.
3.0 Operation
WARNING!
3.0 Installation • Sequence of Operation
Important! Before operating this heater, conduct the following safety procedures:
• Check for any possible gas leaks.
• Alert all persons about the hazard of high surface temperature and to keep a safe distance away in order
to avoid burns and possible clothing ignition.
• Provide supervision when young children are in the area of the heater.
• Check to make sure that clothing isn’t hung from the heater and that ammable materials are not placed
on or near the heater.
• Check that all guards or protective devices are in place and secure.
• Check the hose assembly for excessive abrasion, wear or damage. If necessary replace. The
replacement hose must be that specied by Brant Radiant Heaters Limited.
• Check control compartment, burners and circulating air passages for debris. If necessary, remove the
debris.
Sequence of Operation:
Starting Circuit:
When voltage is applied to L1 and L2, a circuit is completed from L1 via the blower motor to L2. The blower fan
is mounted in the control box and rated to supply sufcient air for combustion. Air pressure generated by the
blower fan will cause the normally open pressure switch to close. Another circuit is completed from L1 to the spark
ignition module and back to L2. After a seven (7) second pre-purge, the spark electrode and gas valve energize
simultaneously. The trial for ignition is fteen seconds.
Running Circuit
After ignition, the ame rod monitors the ame. As long as a ame is present, the valve is held open. If the ame is
lost, the control acts to close the valve within seconds, and a new trial sequence identical to that at start-up is initiated.
If proof of ame is not established within the 15 second trial for ignition, the unit will retry two additional times before
entering lockout mode. If lockout occurs, the control can be reset by briey interrupting the power source.
17

Lighting Instructions:
Rotate heater’s valve to “ON” position.
Close electrical circuit (usually thermostat).
If the heater fails to light, turn “OFF” gas, open electrical circuit and wait 5 minutes before repeating.
Shutdown Instructions
Open electrical circuit (usually thermostat).
Turn off electrical power if service is to be performed.
Rotate heater’s valve knob to “OFF” postion.
3.0 Operation • Wiring Diagrams
Wiring Diagrams
Figure 3.1 •PH Series 120V
Amp draw:
120V- .25 starting, .24 running
Figure 3.2 •PH Series 120V with 24V control
Amp draw:
24V- .10 starting
120V- .25 starting, .24 running
18
1
2
3
1
2
3

Always wear clothing that protects the body and use protective glasses when
maintaining the heater.
Electrical shock or explosion may occur when conducting maintenance while the
heater is connected to the power source and gas supply. Disconnect power and gas
supply to heater before servicing.
Burner malfunction may result in explosion or re. Never operate the heater if there
are any signs of malfunction, excessive wear or damage. Call a professional for
assistance.
4.0 Maintenance
WARNING!
4.0 Maintenance
Before each use:
• Check the gas supply line and hose assembly for any possible gas leaks or damage.
• Check heater elements for debris. Visually check burner ames.
• Keep the heated area clear and free of combustible materials, gasoline and ammable vapours and
liquids. Ensure there is no obstruction of the ow of combustion and ventilation.
Periodic maintenance:
• Clean the heater with cleaning agent suitable for the unit’s construction material (i.e. stainless steel
cleaner).
• Lubricate moving parts.
• Inspect the gas supply piping system for any signs of corrosion or failure. Replace if necessary.
Before conducting maintenance on the heater disconnect the power and gas supply. When pressure testing
the gas supply piping system, follow these guidelines:
• At a test pressure in excess of 1/2 psig (3.5 kPa) the heater and ball shutoff valve must be disconnected
from the gas supply piping system during any pressure testing of the system.
• At a test pressure equal or less than 1/2 psig (3.5 kPa) the heater must be isolated from the gas supply
piping system by closing it’s individual manual shutoff valve during any pressure testing of the gas supply
piping system.
Cleaning the main burner:
Gently use an air hose to blow any accumulated dust and/or dirt off the heater. Air hose pressure should
not exceed 30 psig.
Gently, pass an air hose over entire exposed area of the ceramic. A distance of 2’ to 4’ from unit is
recommended.
Gently place the air hose outlet into the venturi tube and allow the air to flow for approximately one minute.
During long periods of non-usage, remove or cover heater with a polyethylene bag and shut off gas supply. If
further service to the heater is desired, contact your representative or the factory.
NOTICE
Cleaning the heater elements with high pressure air may cause damage to the elements and equipment failure.
Do not blow out heating elements with high pressure air.
19

Symptom Possible Cause Corrective Action
Burning of gas-air mixture inside
plenum (ashback).
• Heater mounted at incorrect angle.
• Excessive drafts.
• Gas leaking at orifice.
• Separation of ceramic grids.
• Ceramic grids cracked.
• Mounting angle 0° - 30°.
• Relocate or shield from draft.
• Check with leak detector solution.
• Replace burner.
• Replace burner.
Delayed ignition. • Electrode out of specication.
• Low gas pressure.
• Partially blocked orice.
• Improper orice size.
• Incorrect gas.
• See ignition system insert.
• See section 2.0, Gas Supply.
• Clean or replace.
• Consult dealer.
• See unit nameplate.
Low ceramic surface temperature or
excessive rollout.
• Dirty or plugged burner ceramics.
• Partially blocked orice.
• Low inlet gas pressure.
• High or low manifold gas pressure.
• Foreign matter in venturi tube.
• Excessive dark spots in burner.
• Gas supply piping too small.
• Incorrect gas.
• See periodic maintenance instructions.
• Remove and clean.
• See Section 2.0, Gas Supply.
• Adjust main valve regulator as specied.
• See periodic maintenance instructions.
• See periodic maintenance instructions.
• Increase inlet pressure or replace piping.
• See unit nameplate.
Control system overheating. • Heater not mounted correctly.
• Heater mounted too close to
ceiling.
• Mounting angle 0° - 30°. Level left to right.
• Observe clearance to combustibles.
Gas odor. • Loose pipe connection. • Check connections. Tighten as necessary.
Heater cycles repeatedly. • Heater located in drafty area.
• Low gas pressure.
• Thermostat located in drafty area.
• Defective ame electrode or circuit
board.
• Relocate or shield from draft.
• See Section 2.0, Gas Supply.
• Relocate thermostat.
• Replace.
No spark; no ignition. • Lack of 120V or 24V incoming voltage.
• Open high voltage wire.
• Fan not operating.
• Improper electrode gap.
• Loose or open wire connection.
• Pressure switch not satised.
• Poor or no equipment ground.
• Unit in “safety lockout” mode.
• Defective “gaslighter” control.
• Check power supply.
• Isolate an ohm for resistance, replace if 0.
• Locate source of electrical problem or
replace faulty fan.
• See Ignition System specications.
• Check all wires, tighten or replace.
• Verify fan operation. Remove obstructions.
• Check all connections, provide positive earth
ground.
• Interrupt power source, repeat trial for
ignition.
• Replace.
Heater lights and “locks out” after
approximately 10 seconds.
• Poor or no equipment ground.
• Polarity is reversed.
• Low gas pressure.
• Electrode not sensing.
• Heater mounted at incorrect angle.
• Defective “gaslighter” control.
• Check all connections, provide positive earth
ground.
• 120V to black, neutral to white.
• See Section 2.0, Gas Supply.
• Relocate or replace if defective.
• Mounting angle 0° - 30°.
• Replace.
Spark is present. No main gas op-
eration. Unit “locks out”.
• Gas valve in “OFF” position.
• Defective gas valve.
• Defective “gaslighter” control.
• Turn to “ON” positon.
• Isolate and check for resistance, replace if 0.
• Replace.
Heater will not shut off. • Defective thermostat or wiring.
• Gas valve stuck or open.
• High gas pressure.
• Replace or repair.
• Replace.
• See Section 2.0, Gas Supply.
4.0 Maintenance • Troubleshooting Guide
Figure 4.1 •Troubleshooting Guide
20
Table of contents