•Installation and setup of the unit should be undertaken by a trained specialist. Room or area
where the unit is to be installed must meet workplace requirements of the local building code.
•The unit must not be operated in outdoor environments. Do not expose to weather conditions
(rain, temperature fluctuations, proximity of heating equipment, direct sunlight etc).
•Air at workplace should be free of corrosive vapors, airborne dust, and fibrous matter.
•To provide access to the unit for maintenance and repair purposes, respect the following
clearances between the unit and building structures: 20 inches to the left or right, 8 inches
above.
•Electrical connections must comply with the local electrical code. Make sure to follow applicable
grounding and insulation rules.
•Supply, drain, and delivery pipework must comply with local plumbing code and have sufficient
flow capacity. Drain line of the unit must be separated from floor drain with an air gap.
•Construction material or inside lining of permeate tank must be resistant to water corrosion (e.
g. stainless steel, polypropylene). Tank should be installed next to the unit.
•Antiscalant pump suction line length should not exceed 60 inches.
5.1 Operator of the unit must strictly follow these guidelines and general electrical safety
precautions.
If power supply cord is damaged, it must be replaced by the manufacturer, its service
agent or similarly qualified person in order to avoid hazard.
5.2 When operating the unit, ensure that pressure and flow rates are within specification
limits and that power supply is clean and uninterrupted.
5.3 Perform the following at least once a month:
•verify that readings on pressure gauges and rotameters fall within the specified range per
operating parameters specification (Table 1 and 2);
•verify tightness of hydraulic connections and integrity of parts
5.4 In order to monitor performance of the RO machine, regularly keep record of operation and
write down parameter readings. Use membrane manufacturer’s software tools for normalization to
control for fluctuations of pressure, temperature, and other operating conditions.
5.5 Change prefilter’s polypropylene cartridge when it becomes clogged. Pressure drop of 15
PSI or greater over the sediment prefilter indicates that the prefilter cartridge is clogged and must
be replaced.
5.6 Perform CIP or another suitable chemical cleaning protocol when any of the following
conditions are encountered:
•normalized permeate flow rate drops 10-15% of its initial value;
•normalized conductivity of permeate increases 10-15% of initial value, raw water conductivity
remaining at the same level;
•normalized pressure drop over the membrane vessel increases 10-15% of its initial value.
‘Normalized’ parameter means a parameter measured at exactly the same operating pressure,