BTR BCR - 2 A Installation and operation manual

RWA-Control Unit BCR - 2 A / 4 A / 8 A / 12 A
Installation and Commissioning
Instructions
Control Unit BCr

2
RWA - Control Unit BCR
08
07
06
05
04
03
02
01
Contents
Abbreviations
Warning and Safety Symbols
Target Groups, Intended Use
Safety Instructions
Data sheet RWA Control Unit BCR - 2 A
Data sheet RWA Control Unit BCR - 4 A
Data sheet RWA Control Unit BCR - 8 A
Data sheet RWA Control Unit BCR - 12 A
Technical Data
Preparing assembly
Connection Facilties / Cabling
instAllAtion step 1: Connection of drives and ventilation
instAllAtion step 2: Connection of automatic and manual smoke detectors
instAllAtion step 3: Connection of wind sensors and rain sensors
instAllAtion step 4: Connecting power supply
instAllAtion step 5 LED´s and DIP switches
instAllAtion step 6: Enabling operation / Completing installation
Troublshooting and repair
Fuses
Indicator and Control elements
Maintenance and Modication
Warranty and Customer Service
Demounting
Liability
Disposal
Certicates
3 - 8
9 - 10
11 - 12
13 - 16
17 - 19
20 - 21
22 - 23
24 - 27
2 A
4 A
8 A
12 A

3
RWA - Control Unit BCR
Warning and safety symbols in these instructions:
The symbols used in the instructions shall be strictly observed and have the following meaning:
Caution / Warning
Danger due to electric current.
Caution / Warning
Risk of crushing and entrapment during device opera-
tion.
Attention / Warning
Risk of damage to / destruction of drives and / or
windows.
!
Warning
!
caution
note
!
Once the assembly and commissioning has been
completed, the installer of a machine „power-
operated window“ shall hand these instructions
over to the end-user.
The end-user shall store these instructions in a
safe place over the whole lifecycle and use it for
further reference, if required.
!
Warning
Failure to comply with the warning notes can
result in irreversible injuries or death.
Failure to comply with the warning notes can
result in minor or moderate (reversible) injuries.
Failure to comply with the warning notes can
lead to damage to property.
Preliminary remark
Useful note
for an optimum installation.
abbreviations
Scale units
°C Degree Celsius
A Amps
Ah Amp-hours
kg Kilogram
m Metres
min Minutes
mm Millimeters
N Newtons
s Seconds
Pcs. Pieces
V Volts
PU Packaging Units
Vpp Residual ripple (Voltage Peak-Peak)
W Watts
Ω / k Ω Ohm / kilo-Ohm
Figures
AC Alternating current (50Hz / 60Hz)
DC Direct current
I Electric current
L Length
ME Module space unit (1 ME = 23 mm)
NC Contact „close“ (normally close)
NO Contact „open“ (normally open)
P Electric power
R Electrical resistance
U Electric voltage
Um Change over switch
Colour
BK black OG orange
BN brown RD red
BU blue VT violet
GN green WH white
GY grey YE yellow
01
Index of abbreviations
These abbreviations are used consistently throughout these
assembly & operating instructions. Unless stated differently, all
dimensions indicated in this document are in mm.
General tolerances in accordance with DIN ISO 2768-m.
aP Surface mounting
WxHxD Width x Height x Depth
COM Common connection
DIN German Institute for Standardisation
EN European Standard
IN Input
OUT Output
RAL Central European Colour Standard
RWA Smoke and heat exhaust ventilation

4
RWA - Control Unit BCR
01
Preliminary remark
These instructions are intended for trained personnel and
operators of systems for natural smoke and heat exhaust
ventilation systems (RWA) and natural ventilation via
windows, who are knowledgeable of operating modes as
well as the remaining risks of the system.
This device is not intended for use by per-
sons (including children) with physical,
sensory or mental limitations or lacking experience and / or
knowledge, unless they are supervised by a person who is
responsible for the safety or were instructed by him on the
usage of this equipment. Children should be supervised to
ensure that they are not playing with this device.
Cleaning and operator’s maintenance may not be per-
formed by children without supervision.
target group
!
Warning
By attaching an electric operating drive to
a movable element of a window and con-
necting it to a power supply a so-called
“power-operated window” is created which,
according to the Machinery Directive
2006 / 42 / EG, represents a machine. The
control device is designated for driving such
a window. Where it seems reasonable, these
installation instructions point out sensibly
predictable hazards and risks resulting from a
power operated window.
By connecting the window drives with
a control device and their operation the
constructor of the complete system beco-
mes the manufacturer of the power-ope-
rated window! If necessary, he is obliga-
ted to perform a risk assessment of the
complete system in accordance with the
Machinery Directive 2006/42/EG when
the utilization or operation of the control
device or the connected window drives
deviate from their intended use!
Attention must be paid to possible
hazards when used with tilting or
rotating windows, whose secondary
closing edges are located at less than
2,5 m installation height above the oor,
under consideration of the Control Unit
and usage!
note
note
!
Warning
intended use
Area of application / Scope of application
This control device is intended for power-feeding and con-
trolling of electromotive operated windows in facade or
roof areas. The prime task of this product, in combina-
tion with the electromotive window, is to evacuate hot
smoke and combustion gases in case of re to save
human lives and protect material assets. Furthermore, the
electromotive operated window ensures fresh air supply
for the natural ventilation of the building.
Intended use
The control device is intended for stationary installation and
electrical connection as part of a building.
In accordance with the attached Declaration of Con-
formity the control device, in combination with electro-
motive drives from Btr, is released for its proper use at a
power-operated window for the following use:
• Application for natural ventilation
with an installation height of the drive and
the bottom side of casement of at least 2,5 m above
the oor, or
with an opening width at the HSK of the driven
part of < 200 mm by a simultaneous speed of
< 15 mm/s at the HSK in closing direction.
• Application as NRWA (natural smoke and heat
exhaust ventilator(s) in accordance with EN12101-2
without dual purpose for ventilation.
We as manufacturers are well aware of our duties and
responsibilities regarding the development, manufactu-
ring and placing of safe window drives on the market and
consistently implement them. Ultimately, however, we have
no direct inuence on the usage of our drives. Therefore,
as a precaution, we point out the following:
• The constructor or his agent (architect, specialist
planner) are obligated by law to evaluate the
hazards to persons, originating from the usage,
installation position, opening parameters as well as
the planned type of installation of the power
operated window and the external Control Unit,
already in the planning phase and to establish
necessary protective measures.
• The constructor / manufacturer of the machine
“power-operated window” must implement the
planned protective measures at the installation site
or, if not yet established, determine them by theire
own responsibility and detect or minimize possible
remaining risks.

5
RWA - Control Unit BCR
01
Preliminary remark
The need for a risk assessment at the installation site
due to the reasonably foreseeable misuse.
A risk assessment in accordance with the Machinery
Directive 2006 / 42 / EG by activation of the power-
operated window for natural ventilation is absolutely
necessary under the following conditions:
• the installation height of the drive or of the „HSK / main
closing edge“ (parallel to hinge) < 2,5 m above the oor
and one of the following conditions:
• the opening width at the HSK is > 200 mm, or
• the closing speed at the HSK is > 15 mm/s, or
• the opening speed at the HSK is > 50 mm/s, or
• the closing force at the HSK is > 150 N
The following ow chart can be applied, which also includes
the protective measures in accordance with EN 60335-2-
103/2016-05.
Hold-to-run switch:
stops movement at HSK < 20 mm
at a closing force of > 150 N at HSK
(20.ZAA.5)
Operating element in
direct range of vision:
a.) Key switch or
b.) other switch,
then: installation > 1,5 m,
inaccessible for public
(7.12.1)
Keep people away during closing!
!
Caution
NRWA in accordance
with EN12101-2
without dual purpose for ventilation
Observe danger at NSK
< 2,5 m above oor!
!
Caution
Keep people away during closing!
!
Caution
In the environment with children /
people in need of protection
Hazard analysis according to DIN EN 60335-2-103
Contact-free anti-trap protection
(20.ZAA.8.1)
Passive infra-red and active light sensors
or
pressure mats
Protection devices
!
Caution
Using drives
Natural ventilation
Installation height of drive and lower
edge of casement: > 2,5 m above oor
(ZAA.20.2)
Opening at HSK: < 200 mm and
Speed at HSK:
CLOSE <15 mm/s / OPEN < 50 mm/s
(20.ZAA.2)
No
No
The information in the brackets
refer to the chapters of DIN EN 60335-2-103.
Risk analysis according to the
Machinery Directive required
Contact-based anti-trap protection
(20.ZAA.8.2)
Pressure-sensitive safety switch strips
or
Motor current monitoring systems
(internal and external)
NRWA in accordance
with EN12101-2
with dual purpose for ventilation
(1.Z.109)
Yes
Yes No
risc assessment
required
Declaration of Conformity
power operated window
+ CE label

6
RWA - Control Unit BCR
safety instruCtions
Crush and shear points
To avoid injuries, crushing and shear points between
casement and frame must be secured against entrapment
up to an installation height of 2,5 meters above the
oor with appropriate measures. This can be achieved e.g.
by using contact-based or contactless protective devices
against entrapment, which stop the motion through contact
or through interruption by a person. A warning symbol at
the opening element must indicate this clearly.
Routing cables and electrical connection
Routing or installing electrical lines and connections may
be performed only by approved specialist companies. Never
operate drives, Control Units, operating elements and sen-
sors at operating voltages and connections contrary to the
specications of the manufacturer.
!
Warning
Area of application
The control device shall only be used according to its inten-
ded use. For additional applications consult the manufactu-
rer or his authorized dealer.
Installation
These instructions address expert and safety-conscious
electricians and / or qualied personnel knowledgeable of
the electrical and mechanical installation of drives and con-
trol systems.
The Control Unit BCR must be installed in a safe place,
protected from the inuence of re and smoke.
Mounting material
The required mounting material must be modied to t the
occurring load.
safety instructions
It is important to follow these instruc-
tions for the safety of persons. These
instructions shall be kept in a safe place
for the entire service life of the products.
Risk of crushing and entrapment!
Electromotive operated windows can
close automatically!
The compressive force is absolutely
sufcient to crush ngers in case of
carelessness.
01
The planning and calculation of the
wiring system is the responsibility of
the builder or his agent or the authori-
zed constructor and must be performed
according to the statutory provisions.
All relevant national instructions shall be observed for the
installation.
note
We recommend using exclusively sys-
tem components by btr, because
their compatibility is carefully checked
in the factory. btr shall not assume
liability for the system-compatible func-
tioning of third party components.
Applications and connections other than
explicitly described in these instructions
require the express written consent of
btr. Utilization of applications and com-
ponents not expressly authorized by btr
are considered as unintended use even
if their perfect functioning is proven at
commissioning (e.g. approval under buil-
ding law).
note
Basic functions of RWA (smoke and heat exhaust sys-
tem) control devices:
• Control of electromotive window drives for smoke
and heat exhaust in case of re and for “natural
ventilation”.
• Evaluation of trigger signals of manual and automatic
smoke detectors as well as of re alarm systems.
• Emergency power supply provided by accumulators
for maintaining safety functions if power
supply is interrupted in case of re.
• Monitoring the power supply of all important con-
nections for malfunctions.
• Diverse automatic and manual control options for con-
trolling natural ventilation (e.g. via wind and rain
sensors).
• Transmission of signals of all essential operating states
for external evaluation (may require additional com-
ponents).

7
RWA - Control Unit BCR
safety instruCtions
The types of cable, cable lengths and cross-sections shall
be selected in accordance with the manufacturer’s technical
data. If necessary, the cable types shall be coordinated with
the competent local authorities and energy supply com-
panies. Low-voltage lines (24 V DC) shall be routed
separate from the high-voltage lines. Flexible cables may
not be ush-mounted. Freely suspended cables shall be
equipped with strain reliefs.
Clamping points shall be checked for tightness of threa-
ded connections and cable ends. Access to junction boxes,
clamping points and external drive control systems shall be
ensured for maintenance work.
Commissioning, operation and maintenance
After the installation and after each modication in
the set up all functions shall be checked with a trial run.
After the installation of the system is completed the
end-user shall be instructed in all important operating
steps. If necessary,he must be advised of all remaining risks /
dangers.
The end-user shall be instructed in intended use of the
drives and, if necessary, the safety instructions.The end-user
shall be specically instructed that no additional forces,
except for the pressure and tension in the opening and
closing direction of the casement, may be applied to the
spindle, chain or lever of the drive.
The power line on-site must be secured sepa-
rately and provided with all poles separators.
After opening of the system housing voltage
carrying parts are exposed. The system must
be separated from the power supply and ac-
cumulator voltage before each intervention in
the Control Unit of the system.
Cables must be laid such way that they cannot
be sheared off, twisted or bent during operati-
on. It is recommended to perform an insulati-
on measurement of the system’s line network
and to document this.
!
Warning
It is imperative that the information
provided in the installation instructions
of the controlled window drives are ob-
served and adhered to!
01
note Post warning signs!
During the proper assembly of drives with mounting
elements at a window, and the connection to an external
Control Unit, the interfaces resulting from mechanical and
electrical performance characteristics of single elements
shall be observed.
Other persons must be kept away from
the casement when a hold-to-run switch
(pushbutton) is operated or when a
window, which has been opened by a
smoke and heat exhaust system, is clo-
sing!
The operating element of hold-to-run
switches must be installed within di-
rect view from the window, but apart
from moving elements. If the switch is
not a key-operated switch it must be
installed at a minimum height of 1,5 m
and inaccessible to the public!
Do not allow children to play with
permanently mounted control devices
and keep remote controls out of reach
for children!
!
caution
!
caution
!
caution
Before working on the system it must be com-
pletely disconnected from the power supply
and emergency power supply (e.g. accumu-
lators) and secured against unintentional re-
activation. While working in the Control Unit
the workplace must be secured to prevent
unauthorized access. It must be ensured that
unauthorized personnel are unable to open
the Control Unit.
!
Warning Check all functions of the system before
releasing it for operation.
The installation instructions of system components (smo-
ke detector, natural smoke and heat exhaust ventilators,
drives, etc.) are part of the documentation for the complete
system and must be kept accessible for authorized quali-
ed personnel, together with the installation and operating
instructions, for the entire service life of the system.

8
RWA - Control Unit BCR
safety instruCtions
Ambient conditions
The product may not be subjected to impacts or falls, or
to vibrations, moisture, aggressive vapors or other harmful
environments, unless the manufacturer released it for one
or more of these environmental conditions.
• Operation:
Ambient temperature: -5 °C … +40°C
Relative humidity: < 90% less 20°C;
< 50% less 40°C;
no formation of condensation
• Transport / Storage:
Storage temperature: 0°C … +30°C
Relative humidity: < 60%
Accident prevention regulations and workmen’s
compensation insurance guidelines
For work on or in a building or building part the provisi-
ons and instructions of the respective accident prevention
regulations (UVV and workmen’s compensation insurance
guidelines (BGR /ASR) shall be observed and adhered to.
01
Declaration of Conformity
The control device is manufactured and inspected for its
intended use in accordance with the European guidelines.
The respective Declaration of Conformity is on hand. In
case the use or operation of the control device or the con-
nected window drives deviate from this a risk assessment
must be performed for the complete system of power-
operated windows and a Declaration of Conformity ac-
cording to Machinery Directive 2006/42/EG issued as well
as a CE labeling obtained.
guidelines and standards
The most recent state of country-specic laws, regulations,
provisions and standards must absolutely be observed du-
ring the installation and for electrical connections.
These are for instance:
State building code with special construction regulations
such as:
- Industrial construction guideline
- Venue regulations, etc.
MLAR - Sample Guideline on Conduits German desig-
nation
Provisions of the re protection authorities
TAB (technical connection conditions) of Utility com-
panies
German Regulations for Occupational Insurance
Schemes, such as:
- ASR A1.6 and 1.7(substitute for BGR 232)
Additional standards and guidelines, such as:
EN 60335-2-103 Safety of household and similar elec-
trical appliances
EN 60730-1 Automatic electrical controls
EN 12101-10 / prEN 12101-9 (ISO 21927-9/10)
Smoke and heat control systems
DIN 4102-12 Functional integrity of electric cable
systems
VDE 0100 Installation of high-voltage systems up
to 1000 V
VDE 0298 Use of cables
VDE 0815 Wiring cables (for telecommunication
and data processing systems)
VDE 0833 Alarm systems
VdS-Guidelines: 2593, 2581, 2580, 2592
Accident prevention regulations, in particular:
- VBG 1 „General rules“ and
- VBG 4 „Electrical systems and equipment“.
For placing on the market, the installation and the operati-
on outside Germany the relevant national laws, regulations,
standards and safety provisions apply.
The constructor is responsible for the proper installation or
operation and the issuing of a Declaration of Conformity
according to European guidelines.

9
RWA - Control Unit BCR
Data sheet: 2 A And 4 A
4 A2 A
Control Unit BCR2A - 0101
Article Application
Compact Control Unit for smoke and heat exhaust ventilation systems operating
with 24 V DC voltage, suitable for staircases.
Technical Data (Rated values)
Operating voltage:
Max. power consumption:
Output voltage:
Output current:
Ambient temperature range:
Protection rating:
Housing:
Dimensions (WxHxD):
Connection terminals:
Motherboard:
Part.-No. 60.100
230 V AC (195 – 253 V AC, 50 / 60 Hz)
128 W
24 V DC (20 – 28 V DC / 0,5 Vpp)
2,0 A
-5°C … + 40°C
IP30
Surface mounting, steel sheet,
RAL 7035 (light grey)
316 x 305 x 112 mm
1,5 mm² / Drives: 2,5 mm² (rigid wire)
1 RWA group / 1 Vent group
Feature / Equipment
Cable entry from above / below / behind
Prepared for 2maintanance-free backup accumulators 2x 12 V / 2,3 Ah (Part. Nr. 60.304)
Control Unit BCR4A - 0101
Article Application
Compact Control Unit for smoke and heat exhaust ventilation systems operating
with 24 V DC voltage, suitable for staircases.
Technical Data (Rated values)
Operating voltage:
Max. power consumption:
Output voltage:
Output current:
Ambient temperature range:
Protection rating:
Housing:
Dimensions (WxHxD):
Connection terminals:
Motherboard:
Part.-No. 60.101
230 V AC (195 – 253 V AC, 50 / 60 Hz)
276 W
24 V DC (20 – 28 V DC / 0,5 Vpp)
4,0 A
-5°C … + 40°C
IP30
Surface mounting, steel sheet,
RAL 7035 (light grey)
316 x 305 x 112 mm
1,5 mm² / Drives: 2,5 mm² (rigid wire)
1 RWA group / 1 Vent group
Feature / Equipment
Cable entry from above / below / behind
Prepared for 2maintanance-free backup accumulators 2x 12 V / 2,3 Ah (Part. Nr. 60.304)
2 A
4 A
data sheet rWa - control unit BCR - 2 A
data sheet rWa - control unit BCR - 4 A

10
RWA - Control Unit BCR
Data sheet: 8 A And 12 A
Control Unit BCR8A - 0102
Article Application
Compact Control Unit for smoke and heat exhaust ventilation systems operating
with 24 V DC voltage, suitable for staircases.
Technical Data (Rated values)
Operating voltage:
Max. power consumption:
Output voltage:
Output current:
Ambient temperature range:
Protection rating:
Housing:
Dimensions (WxHxD):
Connection terminals:
Motherboard:
Part.-No. 60.102
230 V AC (195 – 253 V AC, 50 / 60 Hz)
299 W
24 V DC (20 – 28 V DC / 0,5 Vpp)
8,0 A
-5°C … + 40°C
IP30
Surface mounting, steel sheet,
RAL 7035 (light grey)
316 x 305 x 112 mm
1,5 mm² / Drives: 2,5 mm² (rigid wire)
1 RWA group / 2 Vent groups
Feature / Equipment
Cable entry from above / below / behind
Prepared for 2maintanance-free backup accumulators 2x 12 V / 7 Ah (Part. Nr. 60.305)
Control Unit BCR12A - 0102
Article Application
Compact Control Unit for smoke and heat exhaust ventilation systems operating
with 24 V DC voltage, suitable for staircases.
Technical Data (Rated values)
Operating voltage:
Max. power consumption:
Output voltage:
Output current:
Ambient temperature range:
Protection rating:
Housing:
Dimensions (WxHxD):
Connection terminals:
Motherboard:
Part.-No. 60.103
230 V AC (195 – 253 V AC, 50 / 60 Hz)
460 W
24 V DC (20 – 28 V DC / 0,5 Vpp)
12,0 A
-5°C … + 40°C
IP30
Surface mounting, steel sheet,
RAL 7035 (light grey)
316 x 305 x 112 mm
1,5 mm² / Drives: 2,5 mm² (rigid wire)
1 RWA group / 2 Vent groups
Feature / Equipment
Cable entry from above / below / behind
Prepared for 2maintanance-free backup accumulators 2x 12 V / 7 Ah (Part. Nr. 60.305)
8A
12 A
data sheet rWa - control unit BCR - 8 A
data sheet rWa - control unit BCR - 12 A
12 A8 A
02

11
RWA - Control Unit BCR
Electrical data and connected loads
Operating voltage, primary:
Frequency
Nominal current
(secondary) / Current
consumption (primary)
Output (volt-free contact)
Current output
(short-time duty)
Constant current
consumption
Output voltage, drives
Residual ripple
Number of detectors
(manual / automatic)
Line output
Accumulator voltage
Accumulator nominal
capactiy
195…..253 V AC
50….60 Hz
Version 2A / 128W
Version 4A / 276W
Version 8A / 299W
Version 12 A / 460W
max. load 42V / 0,5A
Nominal current 30%
max. duty ratio
30 % max. of nominal current
(depending on version)
24V DC nominal (20….28 V DC)
max. 0,5 Vpp
10 units per detector line
18….26 V (detector voltage)
2 x 12 V
2,3 or 7,0 Ah
(depending on version)
Environmental Conditions (operation)
Ambient temperature
range:
Maximum relative air
humidity:
-5…+40 °C (according to
EN 12101 Class 1 & ISO 21927-9
Environment Class 1)
75 % (mean value over lifetime)
90 % (for max. 96 hours)
Mechanical Data
Surface mounted housing:
Protection class:
Device type:
Housing dimensions
(W x H x D):
steel plate painted in RAL 7035
IP 30
Type D
316 x 305 x 112 mm
all dimensions given without lock
PreParing assembly
preparing assemblytechnical data
!
Warning
Important instructions for safe assem-
bly: Fully observe all instructions, incorrect
assembly may lead to serious injuries.
Before starting the installation please check with the delivery note
that the delivery is complete and correct, any complaints received
later cannot be considered. It is required to keep a logbook for
the BCR which must be accessible to authorized staff at all times.
The available internal emergency power supply
(back-up accumulators), if correctly rated and ser-
viced at regular intervals, ensures that the control-
ler of the Control Unit moves the connected drives
open at least twice and close at least once after 72
hours of mains power supply loss.
!
03
Scope of delivery: RWA - Control Unit BCR
• Installation and Commissioning Instructions
• Test report according to VDE 0113
• Drive line end module
• Resistors
• Key

12
RWA - Control Unit BCR
Formula to calculate the required wire cross-section of a infeed line
A = cross-section of the wire in mm2
L = line length in m
I = current of connected drives in A
∆U = line voltage drop = 2 V DC
PreParing assembly
Legend
1Output for drive line 1, 24 V DC for smoke and heat exhausting and natural ventilation
2Input for ventilation line 1 (max. 10 vent buttons)
3Output for drive line 2 (only available for BCR 8A and BCR 12A)
4Input for ventilation line 2 (max. 10 vent buttons) (only available for BCR 8A and BCR 12A)
5Housing of control unit
6Connections for wind and rain sensor (disabled in case of alarm and power loss)
7Input for smoke detectors (max. 10)
8Input for signal from external re alarm system (alternative connection) to smoke detectors
9Input for break-glass units (HSE – max. 10)
10 Output for signal transduction 1 (alarm release)
11 Output for signal transduction 2 (collective fault)
----- only available for BCR 8A and BCR 12A
RAUCHABZUG
O K
!
RAUCHABZUG
O K
!
BMA
1
2
4
3
11
10
6
9
8
7
Operating voltage, primary
195 ... 253 V AC
Route via external fuse and
switching component!
INFO
INFO
min. 3 x A
(see formula) Cable: 5 x 1,5 or 7 x 1,5 mm2
Length: max. 200 m
Cable: 2 x 2 x 0,8 mm2
Length: max. 400 m
Cable: 2 x 2 x 0,8 mm2
Length: max. 400 m
Cable: 4 x 2 x 0,8 mm2
Length: max. 400 m
Cable: 4 x 2 x 0,8 mm2
Length: max. 400 m
Cable: 2 x 2 x 0,8 mm2
Length: max. 400 m
Cable: 2 x 2 x 0,8 mm2
Length: max. 400 m
min. 3 x A
(see formula)
5
12 A8 A4 A2 A
03
connection facilities / cabling

13
RWA - Control Unit BCR
instAllAtion step 1:
ConneCting Drives anD ventilation
4 A2 A
instAllAtion step 1:
BCR 2 A und BCR 4 A connecting: drives and ventilation
Connection of drives and ventilation: BCR 2 A - 0101 and BCR 4 A - 0101
04
reset
close close
red: open
green: close
Drive 1
Drives 24V
GND
alarm
operation
fault
GND
GND
OPEN
CLOSE
REL 6 -
REL 6 -
REL 6 -
REL 7 -
REL 7 -
REL 7 -
com
n.c.
n.o.
com
n.c.
n.o.
button L2 -
button L2 -
LED -
LED -
LED -
Alarm
Fault
(inverted)
~ 1 s
=
=
-
+
+
-
1 2Terminal
M1
M2
2
1
BU
BN
BN
BU
BK
BK
OG
BU
BN
Install
drive line end module
at the last drive
in the line!

14
RWA - Control Unit BCR
instAllAtion step 1:
ConneCting Drives anD ventilation
Connection of drives and ventilation: BCR 8 A - 0102 and BCR 12 A - 0102
instAllAtion step 1:
BCR 8 A und BCR 12 A connecting: drives and ventilation
reset
red: open
green: close
Drive 1 Drive 2
Drives 24V Drives 24V
GND
alarm
operation
fault
GND
GND
OPEN
CLOSE
REL 6 -
REL 6 -
REL 6 -
REL 7 -
REL 7 -
REL 7 -
com
n.c.
n.o.
com
n.c.
n.o.
button L2 -
button L2 -
LED -
LED -
LED -
Alarm
Fault
(inverted)
~ 1 s
GND
alarm
reset
GND
smoke detector
GND
GND
+24 V
GND
rain
GND
wind
OPEN
CLOSE
button L1 -
button L1 -
HSE -
HSE -
~ 1 s
=
=
-
+
+
-
1 2Terminal
M1
M2
2
1
BU
BN
BN
BU
BK
BK
OG
BU
BN
=
=
-
+
+
-
1 2Terminal
M1
M2
2
1
BU
BN
BN
BU
Install
drive line end module
at the last drive
in the line!
BK
BK
OG
BU
BN
12 A8 A
04

15
RWA - Control Unit BCR
instAllAtion step 2:
ConneCting smoke DeteCtors anD breakglass units
Connection of automatic and manual smoke detectors / BMZ
12 A8 A4 A2 A
reset
red: open
green: close
(same as HSE reset)
Drive 1 Drive 2
GND
alarm
operation
fault
GND
GND
OPEN
CLOSE
REL 6 -
REL 6 -
REL 6 -
REL 7 -
REL 7 -
REL 7 -
com
n.c.
n.o.
com
n.c.
n.o.
button L2 -
button L2 -
LED -
LED -
LED -
GND
alarm
reset
GND
smoke detector
GND
GND
+24 V
GND
rain
GND
wind
OPEN
CLOSE
button L1 -
button L1 -
HSE -
HSE -
Alarm
Fault
(inverted)
+
smoke detector
OK
!
1 2 3 4 5 6 7 8 9 1110
OK
!
1 2 3 4 5 6 7 8 9 1110
R
E
1 2312 3 4
1 2 3 4 5 6 7 8 9 10 11
HSE - Break-glass unit
instAllAtion step 2:
connection: automatic and manual smoke detectors
04
!
The re detector connection is closed-circuit moni-
tored for line failures. Therefore, both the last smoke
detector and the last breakglass unit in the line must
be provided with a 10 kΩ resistor (RE).

16
RWA - Control Unit BCR
instAllAtion step 3:
ConneCting WinD anD rain sensors
12 A8 A4 A2 A
instAllAtion step 3:
connecting: Wind sensors and rain sensors
Connection of wind sensors and rain sensors
reset
wind
T / SH
ML - A
HSE - A
RM - A
NF - A
BF - A
GND
F2 F3
L1
open
L2
open
L1
close
L2
close
red: open
green: close
Reset Button
(same as HSE reset)
Wind-Speed (reshold)
[m/s]
Drive 1 Drive 2
GND
alarm
reset
GND
smoke detector
GND
GND
+24 V
GND
rain
GND
wind
OPEN
CLOSE
button L1 -
button L1 -
HSE -
HSE -
24 V
1 2 3 4 5
rain
wind
04
!
In case of re (emergency-OPEN) or failure of power supply (accumu-
lator operation) the ventilation control via wind and rain sensors is
deactivated.
Before mounting and positioning the wind sensors / rain
sensors carefully read the safety and assembly instruc-
tions provided with the products. They are part of the
system documentation and must be adhered to and kept
accordingly (e.g. for servicing purposes).

17
RWA - Control Unit BCR
instAllAtion step 4:
ConneCting PoWer suPPly
4 A2 A
instAllAtion step 4:
BCR 2 A und BCR 4 A connecting: poWer supply
Connection of power supply
reset
wind
T / SH
ML - A
HSE - A
RM - A
NF - A
BF - A
Battery
GND
Battery
F2
Power Supply 24V
2 x back-up battery 2,3 Ah, 12V
L1
open
L2
open
L1
close
L2
close
red: open
green: close
Wind-Speed (reshold)
[m/s]
Drive 1
Ensure correct polarity
when connecting!
blue red
Operating voltage, primary
195 ... 253 V AC
-
-
05
Route line voltage supply via external fuse and
switching component. Only connect supply voltage
and accumulator set when disconnected from the mains
power supply! Switch off power supply and secure
against reconnection!
!
It is essential to ensure correct polarity when connecting
the accumulator set! Incorrectly connected accu-
mulators will cause damage to the controller!

18
RWA - Control Unit BCR
instAllAtion step 4:
ConneCting PoWer suPPly
12 A8 A
instAllAtion step 4:
BCR 8 A und BCR 12 A connecting: poWer supply
Connection of power supply
reset
wind
T / SH
ML - A
HSE - A
RM - A
NF - A
BF - A
Battery
GND
Battery
F2 F3
Power Supply 24V
2 x back-up battery 7 Ah, 12V
L1
open
L2
open
L1
close
L2
close
red: open
green: close
Wind-Speed (reshold)
[m/s]
Drive 1 Drive 2
Ensure correct polarity
when connecting!
blue red
Operating voltage, primary
195 ... 253 V AC
-
-
Route line voltage supply via external fuse and
switching component. Only connect supply voltage
and accumulator set when disconnected from the mains
power supply! Switch off power supply and secure
against reconnection!
!
It is essential to ensure correct polarity when connecting
the accumulator set! Incorrectly connected accu-
mulators will cause damage to the controller!
05

19
RWA - Control Unit BCR
DIP switch function
switch ON OFF
DIP 1 Mode to:
Vent switches BIASED BIASED OFF
DIP 2 Fault motor lines
triggers alarm disabled
Fault to motor lines is only displayed
DIP 3 Fault breakglass unit lines
triggers alarm disabled
DIP 4 Fault smoke detector lines
triggers alarm disabled
DIP 5 Fault power supply
triggers alarm disabled
DIP 6 Fault back-up accumulators
triggers alarm disabled
instAllAtion step 5:
leD´sanD DiP sWitChes
wind
T / SH
ML - A
HSE - A
RM - A
NF - A
BF - A
Wind-Speed (reshold)
[m/s]
instAllAtion step 5:
LED´sand dip sWitches
LED`s from motherboard LED`s from breakglass unit (HSE)
State B S A Operation Fault Emergency-
OPEN
Standby ON OFF OFF ON OFF OFF
Emergency-OPEN / alarm (power supply operation) ON OFF ON ON OFF ON
Emergency-OPEN / alarm (back-up accumulators mode) OFF ashes ON OFF ashes ON
Power failure (highest priority) OFF ashes OFF OFF ashes OFF
Fault breakglass unit lines OFF ON OFF (*) OFF ON OFF (*)
Fault smoke detector lines OFF blinks slowly OFF (*) OFF ON OFF (*)
Fault motor-line 1 OFF blinks (4x) OFF (*) OFF blinks slowly OFF (*)
Fault motor-line 2 OFF blinks (5x) OFF (*) OFF blinks slowly OFF (*)
Fault HSE reset OFF blinks (6x) OFF OFF blinks slowly OFF
Fault back-up accumulators (lowest priority) OFF blinks fast OFF OFF blinks fast OFF
Maintenance due ON blinks (2x) OFF ON blinks (2x) OFF
Rain active ON blinks (3x) OFF ON OFF OFF
Wind active ON blinks (4x) OFF ON OFF OFF
Wind and rain active ON blinks (5x) OFF ON OFF OFF
Smoke detector still active after reset X X blinks slowly X X blinks slowly
(*) = Depending on the conguration „Fault Emergency-OPEN“ ON or OFF
05

20
RWA - Control Unit BCR
instAllAtion step 6:
enabling oPeration / ComPleting installation / troublshooting
instAllAtion step 6: enabling operation/completing installation
For safety reasons the Control Unit is supplied with
„deadman“ pre-setting for ventilation. You require the
software for switching over to „latching“. It is abso-
lutely necessary to ensure that all safety-relevant re-
quirements for the „latching“ mode are guaranteed
according to the information provided by the manu-
facturers of the connected opening components.
RWA systems require a logbook, in which all important master data have
to be entered prior to operation enable and all operational events during
the period in operation.The logbook is part of the system documents and
must be stored and available to authorized staff at all times.
We advise to perform an insulation measurement of the cable network
before enabling operation of the plant and to keep a written record of
this test.
Provided that the factory default conguration has been changed using
the system software, all alterations have to be taken into
account in the operating manual. It might be required to prepare an ope-
rating manual for non-specialist users that is easy to follow and well
understandable.
In case of re the system saves lives. Therefore
immediately remedy or have any fault or mal-
function remedied by specialists!
Depending on the storage period the back-up accumu-
lators require some time to be fully charged. Therefore,
bridging time (see chapter „Data sheet“) for the power
failure might not be ensured after connecting the
back-up accumulators and the back-up accumulators
rst need some charging time in mains operation
to reach the maximum charge status (min. 8 hours).
The Control Unit must not be enabled for operation
unless all system components work properly. This also
applies to system components that do not come under
our producer responsibility or whose installation had not
been commissioned but are still components of
the RWA system. Upon completion of the installation,
all functions of the Control Unit must be checked
for correct functionality with utmost care. Even
if there is no fault indication this does not mean that all
components function faultlessly.
!
Warning
Before the installer is allowed to enable the operation of the Control Unit,
the complete performance range of the system must be checked with
utmost care. The chapter „Troublshooting anD repair“ provides support
for the localisation of possible faults and malfunctions.
On the last page you nd an overview of all external connections where
the current assignments can be entered.
Modications of the system using the system software should take place
after the complete installation of the Control Unit and all components
being connected. When required, the system conguration and status
can be saved or printed using the system software. In the case of faults
or malfunctions of system components it might also be necessary to
thoroughly check the system conguration (computer to be connected
using system software).
!
!
!
Follow the instructions in the chapter „safety in-
struCtions“.
!
!
Before changing the operating mode check and pay
attention to danger zones at the window!
06
troublshooting and repair
All functions and system components that are important for the
RWA operation are constantly monitored for faults. A fault indication
signals the type of fault and, respectively, possible errors when connecting
system components (such as back-up accumulators, detectors, drives)
during commissioning of the Control Unit.
The overview below details some of the possible faults and problem
cases and their causes. „Indicator B“ means the green operating indi-
cator which does not light up in case of a fault. The yellow “Indicator S”
signals the type of fault.
You nd a list of all indicators in chapter „leD´sanD Dip switChes“ - on
the previous page.
This manual suits for next models
3
Table of contents