Instruction sheet for SATK60193HE
Product range
Cod. SATK60193HE
Function
The heat interface unit code SATK60193HE is designed to provide indirect heating (hydraulic
separation by means of a plate heat exchanger) to both low temperature and high temperature
heating systems. SATK60193HE does not need any dedicated connection kit and can be used
to replace existing old recessed modules.
Specifications
For functional and performance-related features, please refer to the instruction sheet code
78202 and technical brochure 01212 supplied with the module. The product corresponding to
SATK60193HE is code SATK60103HE
SATK60 series
© Copyright 2020 Caleffi
H0009183
www.caleffi.com
Code for replacement of
existing modules Standard code Main specifications
SATK60193HE SATK60103HE Heating range 25-75 °C
DHW production and optional functions
Dimensions / electric specifications
Code DHW temperature
and flow rate range Main optional functions
SATK60193HE 42–60 °C max 18 l/min DHW preheating function
Code Dimensions (W x H x D) Electric specifications
SATK60193HE 570 x 590 x 110 mm
Max operating pressure: 16 bar.
Power supply 230 V (AC) - 50 Hz.
Max power consumption: 80 W
recess mounted heat interface unit for indirect heating, 40 kW heat
exchanger, heating circuit regulating temperature 25–45 °C (low temperature
range) or 45–75 °C (high temperature range).
Installation notes
These instructions must be observed and applied during installation, to prevent problems from
arising during fitting or normal operation. Before proceeding with installation, CAREFULLY read
brochure 01212 and instruction sheet code 78202 (available on the website www.caleffi.com).
You should therefore:
A) Carefully measure the dimensions of heat interface unit SATK60 so that it is ideally positioned
on the wall.
B) Use at least 6 wall anchors (not supplied) to secure the SATK60. The wall anchors must be
chosen in accordance with the type of structure to which the HIU will be fitted.
C) The hydraulic connections listed in the “Description of connections” section and indicated must
be strictly observed using the means you believe most suitable and reliable for maintaining the
hydraulic seal over time.
D) Fill the system by slowly opening the shut-off valves (not supplied) and venting the HIU using
the relevant cocks.
E) If necessary, enable the domestic hot water preheat function (see instruction sheet 78202).
Power up the HIU and proceed with setting the correct DHW and heating set points.
Description of connections
When performing the hydraulic and electrical connections, observe all the
safety notes provided below
WARNINGS
These instructions must be read and understood before installing and
servicing the device.
IMPORTANT! FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN A
SAFETY HAZARD!
1 The device must be installed, commissioned and maintained by qualified technical personnel
in accordance with national regulations and/or relevant local requirements.
2 If the device is not installed, commissioned and maintained correctly in accordance with the
instructions provided in this manual, in instruction sheet code 78202 and in brochure 01212,
it may not work properly and may endanger the user.
3 Clean the pipes of any particles, rust, incrustations, limescale, welding slag and any other
contaminants. The hydraulic circuit must be clean.
4 Make sure that all connection fittings are watertight.
5 When performing the hydraulic connections, take care not to subject the threads to excessive
mechanical stress. Over time, this could result in breakage, resulting in leaks that cause
damage and/or injury.
6 Water temperatures higher than 50 °C may cause severe burns. When installing, commissioning
and servicing the device, take the necessary precautions so that these temperatures will not
be hazardous for people.
7 In the case of particularly hard or impure water, adequate water filtration and treatment must
be assured upstream from the device inlet, in accordance with current legislation. Otherwise
the device may be damaged and will not work properly.
8 Any use of the device other than its intended use is prohibited.
9 Any combination of the device with other system components must be made taking the
operational characteristics of both units into consideration.
10 An incorrect combination coupling could compromise the operation of the device and/or
system.
IMPORTANT: Risk of electric shock. Live parts. Shut off the electric supply before opening the
device enclosure.
1 During installation and maintenance operations, always avoid direct contact with live or
potentially hazardous parts.
2 The device must not be exposed to dripping water or humidity, direct sunlight, weather
conditions, heat sources or high-intensity electromagnetic fields. This device cannot be used
in areas at risk of explosion or fire.
3 The device must be connected to an independent two-pole switch. If work has to be carried
out on the device, cut off the electric supply first. Do not use devices with automatic or time
reset, or which may be reset accidentally.
4 Use suitable automatic protective devices in accordance with the electrical specifications for
the zone in which the device is installed and in compliance with current legislation.
5 The device must always be earthed before it is connected to the electric supply. If the device
needs to be removed, always disconnect the earth connection after disconnecting the
electric supply conductors. Check that the earth connection has been made to the highest of
standards under current legislation.
6 Electrical installation must only be carried out by a qualified technician, in accordance with
legal requirements.
7 The appliance does not contain asbestos or mercury.
Caleffi S.p.A.
S.R. 229 n° 25 - 28010 - Fontaneto d’Agogna - Italy
8 The device is not designed for use by persons of reduced mental, physical or sensory
capacity (including children) or persons lacking experience, unless they are supervised or
instructed in use of the device by a person responsible for their personal safety.
SAFETY INSTRUCTIONS / NOTES:
1 Install water hammer arrester devices to compensate for any overpressure in the domestic
hot water circuit;
2 In the presence of hot water recirculation or if a check valve is fitted at the domestic cold
water inlet, suitable devices must be used to accommodate the expansion of the medium
contained within the system and the heat interface unit;
3 All hydraulic connections must be visually checked during pressurisation. Vibration during
transport may cause the connections to become loose. If a fitting needs to be tightened apply
a proper tightening torque, otherwise the components may be damaged by overtightening.
For the updated version of the technical documentation refer to www.caleffi.com.

This manual suits for next models

1

Other CALEFFI Heating System manuals

CALEFFI SATK22107 Guide

CALEFFI

CALEFFI SATK22107 Guide

CALEFFI 5026 series User manual

CALEFFI

CALEFFI 5026 series User manual

CALEFFI SATK50 Series User manual

CALEFFI

CALEFFI SATK50 Series User manual

CALEFFI SATK32105 Guide

CALEFFI

CALEFFI SATK32105 Guide

Popular Heating System manuals by other brands

Roberts Gorden CoRayVac CRV-B-2 Installation, operation & service manual

Roberts Gorden

Roberts Gorden CoRayVac CRV-B-2 Installation, operation & service manual

MAXA OTA1 micro E Series Technical manual

MAXA

MAXA OTA1 micro E Series Technical manual

Riello 20083502 manual

Riello

Riello 20083502 manual

Alde Compact 3020 HE operating instructions

Alde

Alde Compact 3020 HE operating instructions

Vent-Axia HR500D Installation and wiring instructions

Vent-Axia

Vent-Axia HR500D Installation and wiring instructions

Vasco Energy plus Installation, use and maintenance instructions

Vasco

Vasco Energy plus Installation, use and maintenance instructions

Steffes Comfort Plus Hydronic 5120 Owner's and installer's manual

Steffes

Steffes Comfort Plus Hydronic 5120 Owner's and installer's manual

Napoleon Condo Pack CAGMMA installation instructions

Napoleon

Napoleon Condo Pack CAGMMA installation instructions

Aqua-Hot 400 series Use and care guide

Aqua-Hot

Aqua-Hot 400 series Use and care guide

Rinnai Energysaver 309FT3 Operation and installation guide

Rinnai

Rinnai Energysaver 309FT3 Operation and installation guide

KEXIN KX-5188A160 quick start guide

KEXIN

KEXIN KX-5188A160 quick start guide

Glen EC532 Installation and operating instructions

Glen

Glen EC532 Installation and operating instructions

MSA SOA-1022 operating manual

MSA

MSA SOA-1022 operating manual

Biddle HR 25 manual

Biddle

Biddle HR 25 manual

Viessmann Vitodens 100-W operating instructions

Viessmann

Viessmann Vitodens 100-W operating instructions

Heatit Z-Push Button 8 quick start guide

Heatit

Heatit Z-Push Button 8 quick start guide

flamco Flexcon P Installation and operating instructions

flamco

flamco Flexcon P Installation and operating instructions

Lennox VRB Series Installation & operation instructions

Lennox

Lennox VRB Series Installation & operation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.