MAINTENANCE
ELECTRICAL WIRING
WARRANTY
Fig.2
Fig.3
Instructions Manual No. 00956 19.10 - Rev. 00
The conductors forming the signal carrying cable connected to the microswitch
( Fig.3 ) must have an adequate cross-section so that the current density,
in each conductor, is no higher than 4 A/mm². One of these is used only
The cross-section of the conductors must also be adequate in relation to the
the values prescribed by the regulations on the subject.
diameter for the fair-leads used ( not supplied ) to ensure a perfect seal of
the cable clamp on the signal carrying cable. Use exclusively cable entries
CAUTION: In the terminal board compartment, the connection for Faston type terminal whose position is marked
conductor ( green only for the USA ) of the signal carrying cable must be
connected to this terminal. The ground connection of the float level gauge,
through the yellow-green conductor, is compulsory.
CAMLOGIC float level gauges for liquids need no
routine maintenance. Take care the external cleaning
CAMLOGIC S.n.c., in addition to the terms of the
supply contract, guarantees its products for a
period of twenty-four ( 24 ) months from the date
of shipment.
This warranty is expressed only in the repair or
replacement free of charge of parts that, after
careful examination by the Manufacturer, turn out
to be difective.
Warranty, excluding all liability for direct or indirect
damage, is considered to be restricted to only
defects in materials and has no effect if the parts
returned turn out to have been anyhow dismantled,
tampered with or repaired by anyone other than
the Manufacturer.
Warranty likewise excludes damage deriving from
negligence, carelessness, bad or improper use of
the level gauge, or from bad handling by the
operator and faulty installation.
Warranty is moreover forfeit if non-genuine spare
parts have been used. A returned level gauge, even
if under warranty, must be shipped carriage free.
All the information contained in this manual is confidential and no
part of it may be disclosed without written authorization from CAMLOGIC S.n.c.
This manual, even after the sale of level gauge, is lent and remains the property of the Manufacturer.
for the earthing of the level gauge.
length of the cable used to avoid a drop in voltage along the cable over
It is likewise reccomended to use flexible cables with an adequate outside
by the ground symbol on the printed circuit ( Fig.3 ) is used for the earthing the level gauge. The yellow-green
On the external level gauge casing side, placed side by side to the cable
inlet, a second connection point is present for the external ground connection
executable with a screw M5 and an eyelet cable terminal.
-The external earthing has to be carried out by the installator.
-The equipment has to be protected against impact and electrostatic inside
-The user has to protect the equipment circuits with fuses against short circuit.
-The max. surface temperature is without dust and not safety distance.
the tank.
UE DECLARATION OF CONFORMITY
The manufacturer CAMLOGIC Snc declares under its own responsability that the product PFG-LP answers to the requisites
of the European Directive 2014/34/EU in consideration of the standards : IEC EN 60079-0 IEC EN 60079-1 IEC EN 61241-0 IEC EN 61241-1.
Marking: II 2GD Ex d IIB T4 Ex tD A21 IP65 T135 °C Marking IECEx: Ex d IIB T4 Gb - Ex tD A21 IIIC T135 °C Db IP65.
Notified corporate body that releases the examination TÜV NORD. Crt. number: TÜV 08 ATEX 362388 X - IECEx QAR TUN 08.0033.
Corporate body entrusted of the periodic overseeing TÜV ITALIA.
The permitted range ambient temperature is
REFERENCE FIGURES
ø 110
ø 150
4 holes ø 18 to 90° DN40 COUNTERFLANGE
ø 66
45°
45°
45°
45°
ø 150
170 ~
10°
10°
35° ~
Float ø 52 x150
18 60
137 255 ~
392 ~
47
M16 x 1.5
PFG-LP-C
Outside casing ground
10°
10°
ø 52
47
M16 x 1.5
18 60
137
45 150
255
392
3
ø 66 PFG-LP
Use Faston cable terminals ( 6.3 x 0.8 mm. ) to connect the microswitch terminals and the ground connection.
certified ATEX Exd IP65 or IECEx Exd IP65 M16x1.5.
of the level gauge, the dust accumulation doesn't
have to exceed a thickness of 5 mm.
Inside casing ground
1- N.o. contact
3- N.C. contact
2- Com. contact
123
Faston
6.3x0.8mm.