C&S MRN3 User manual

High-Tech Range
MRN3- Mains decoupling Relay
C&S Protection & Control Ltd.
L3
TRIP
ENTER
+
-
SELECT/RESET
RS
L2
L1
U<
U<<
1/3
U>
U>>
f
N
DQ
T
MRN3-1
FR
P2
D/Y
f
max
min
DQ
f
1
t
f1
f
2
f
3
t
f2
t
f3
t
U>>
t
U<<
t
U<
t
U>

22
22
2
Contents
1. Introduction and application
2. Features and characteristics
3. Design
3.1 Connections
3.1.1 Analog input circuits
3.1.2 Blocking input
3.1.3 Reset input
3.1.4 Output relays
3.1.5 Fault recorder
3.2 Parameter settings
3.3 LEDs
3.4 Front plate
4. Working principle
4.1 Analog circuits
4.2 Digital circuits
4.3 Voltage supervision
4.3.1 Selection of star or delta connection
4.4 Principle of frequency supervision
4.5 Measuring of frequency gradient (MRN3-2)(MRN3-2)
(MRN3-2)(MRN3-2)
(MRN3-2)
4.6 Vector surge supervision (MRN3-1)(MRN3-1)
(MRN3-1)(MRN3-1)
(MRN3-1)
4.6.1 Measuring principle of vector surge
supervision
4.7 Voltage threshold value for frequency
measuring
4.8 Blocking function
5. Operation and settings
5.1 Display
5.2 Setting procedure
5.3 Systemparameter
5.3.1 Display of residual voltage UEas primary
quantity (Uprim/Usec)
5.3.2 Δ/Y - Switch over
5.3.3 Setting of nominal frequency
5.3.4 Display of the activation storage (FLSH/
NOFL)
5.3.5 Parameterswitch / external trigger for the
fault recorder
5.4 Protection parameters
5.4.1 Parameter setting of over and under-
voltage supervision
5.4.2 Number of measuring repetitions (T) for
frequency functions
5.4.3 Threshold of frequency supervision
5.4.4 Tripping delays for the frequency elements
5.4.5 Parameter setting of vector surge
supervision (MRN3-1MRN3-1
MRN3-1MRN3-1
MRN3-1)
5.4.6 Parameter setting of frequency gradient
(MRN3-3MRN3-3
MRN3-3MRN3-3
MRN3-3)
5.4.7 Voltage threshold value for frequency and
vector surge measuring (df/dt at MRN3-2MRN3-2
MRN3-2MRN3-2
MRN3-2)
5.4.8 Adjustment of the slave address
5.4.9 Setting of Baud-rate (applies for Modbus
Protocol only)
5.4.10 Setting of parity (applies for Modbus
Protocol only)
5.5 Adjustment of the fault recorder
5.5.1 Number of the fault recordings
5.5.2 Adjustment of trigger occurences
5.5.3 Pre-trigger time (Tpre)
5.6 Adjustment of the clock
5.7 Additional functions
5.7.1 Setting procedure for blocking the
protection functions
5.8 Indication of measuring values
5.8.1 Measuring indication
5.8.2 Min./Max. values
5.8.3 Unit of the measuring values displayed
5.8.4 Indication of fault data
5.9 Fault memory
5.9.1 Reset
5.9.2 Erasure of fault storage
6. Relay testing and commissioning
6.1 Power-On
6.2 Testing the output relays
6.3 Checking the set values
6.4 Secondary injection test
6.4.1 Test equipment
6.5 Example of test circuit
6.5.1 Checking the input circuits and measuring
functions
6.5.2 Checking the operating and resetting values
of the over/undervoltage functions
6.5.3 Checking the relay operating time of the
over/undervoltage functions
6.5.4 Checking the operating and resetting values
of the over/underfrequency functions
6.5.5 Checking the relay operating time of the
over/underfrequency functions
6.5.6 Checking the vector surge function
6.5.7 Checking the external blocking and reset
functions
6.6 Primary injection test
6.7 Maintenance
7. Technical data
7.1 Measuring input circuits
7.2 Common data
7.3 Setting ranges and steps
7.3.1 Interface parameter
7.3.2 Parameters for the fault recorder
7.4 Output relays
8 Order form

33
33
3
1. Introduction and application
The MRN3MRN3
MRN3MRN3
MRN3 is a universal mains decoupling device and
covers the protection requirements from VDEW and most
other utilities for the mains parallel operation of power
stations.
zOver/ and undervoltage protection
zOver/ and underfrequency protection
zExtremely fast decoupling of generator in case of
mains failure ((
((
(MRN3-1MRN3-1
MRN3-1MRN3-1
MRN3-1))
))
) or
zRate of change of frequency df/dt ((
((
(MRN3-2MRN3-2
MRN3-2MRN3-2
MRN3-2))
))
)
Because of combination of three protectional functions in
one device the MRN3MRN3
MRN3MRN3
MRN3 is a very compact mains de-
coupling device. Compared to the standardly used single
devices it has a very good price/performance ratio.
For applications where the single protection functions are
required CSPCCSPC
CSPCCSPC
CSPC can offer the single MRMR
MRMR
MR-relays as follows:
zMRU3-1MRU3-1
MRU3-1MRU3-1
MRU3-1 four step independent over-/ and
undervoltage protection (also used for
generator earth fault protection)
zMRU3-2MRU3-2
MRU3-2MRU3-2
MRU3-2 two step independent over-/ and
undervoltage protection with
evaluation of the symmetrical voltage
components
zMRF3MRF3
MRF3MRF3
MRF3 four step independent over/ and
underfrequency protection and two
step frequency gradient supervision
df/dt
zMRG2MRG2
MRG2MRG2
MRG2 generator mains monitor / vector
surge detection
2. Features and characteristics
zMicroprocessor technology with watchdog,
zeffective analog low pass filter for suppressing
harmonics when measuring frequency and vector
surge,
zdigital filtering of the measured values by using
discrete Fourier analysis to suppress higher
harmonics and d.c. components induced by faults or
system operations
zintegrated functions for voltage, frequency and vector
surge in one device as well as single voltage,
frequency and vector surge devices,
ztwo parameter sets,
zvoltage supervision each with two step under-/ and
overvoltage detection
zFrequency supervision with three step under-/ or
overfrequency (user setting)
zCompletely independent time settings for voltage and
frequency supervision
zadjustable voltage threshold value for blocking
frequency and vector surge measuring.
zdisplay of all measuring values and setting
parameters for normal operation as well as tripping
via a alphanumerical display and LEDs
zdisplay of measuring values as primary quantities
zStorage of trip values and switching-off time (tCBFP) of
5 fault occurences (fail-safe of voltage),
zrecording of up to eight fault occurences with time
stamp
zfor blocking the individual functions by the external
blocking input, parameters can be set according to
requirement,
zuser configurable vector surge measurement 1-of-3
or 3-of-3,
zreliable vector surge measuring by exact calculation
algorithm
zsuppression of indication after an activation (LED
flash),
zfree assignment for output relays,
zdisplay of date and time,
zin complience with VDE 0435, part 303 and IEC
255,
zserial data exchange via RS485 interface possible;
alternatively with CSPC RS485 Pro-Open Protocol or
Modbus Protocol.

44
44
4
3.1.1 Analog input circuits
The analog input voltages are galvanically decoupled by
the input transformers of the device, then filtered and
finally fed to the analog digital converter. The measuring
circuits can be applied in star or delta connection (refer
to chapter 4.3.1).
3.1.2 Blocking input
The blocking function can be set according to
requirement. By applying the auxiliary voltage to D8/E8,
the previously set relay functions are blocked (refer to
4.8 and 5.7.1).
3.1.3 Reset input
Please refer to chapter 5.9.1
3.1.4 Output relays
The MRN3MRN3
MRN3MRN3
MRN3 is equipped with 5 output relays. Apart from
the relay for self-supervision, all protective functions can
be optionally assigned :
zRelay 1 : C1, D1, E1 and C2, D2, E2
zRelay 2 : C3, D3, E3 and C4, D4, E4
zRelay 3 : C5, D5, E5
zRelay 4 : C6, D6, E6
zRelay 5 : Signal self supervision (internal fault of the
unit) C7, D7, E7
All trip and alarm relays are working current relays, the
relay for self supervision is an idle current relay.
3.1.4 Output relays
The MRN3MRN3
MRN3MRN3
MRN3 has a fault value recorder which records the
measured analog values as instantaneous values.
The instantaneous values
UL1; UL2; UL3; for star connection
or U12; U23; U21 for delta connection
are scanned at a raster of 1.25 ms (at 50 Hz) and
possible to store 1-8 fault occurences with a total
recording time of 16 s (with 50 Hz) and 13.33 s (with 60
Hz) per channel.
Fig. 3.1 : Connection diagram MRN3-1 and MRN3-2Fig. 3.1 : Connection diagram MRN3-1 and MRN3-2
Fig. 3.1 : Connection diagram MRN3-1 and MRN3-2Fig. 3.1 : Connection diagram MRN3-1 and MRN3-2
Fig. 3.1 : Connection diagram MRN3-1 and MRN3-2
Storage division
Independent of the recording time, the entire storage
capacity can be divided int0 several cases of disturbance
with a shorter recording time each. In addition, the
deletion behaviour of the fault recorder can be
influenced.
No writing over
If 2, 4 or 8 recordings are chosen, the complete memory
is divided into the relevant number of partial segments. If
this max. number of fault event has been exceeded, the
fault recorder block any further recordings in order to
prevent that the stored data are written over. After the
data have been read and deleted, the recorder to ready
again for further action.
Writing over
If 1, 3, or 7 recordings are chosen, the relevant number
of partial segments is reserved in the complete memory.
If the memory is full, a new recording will always write
over the oldest one.
The memory part of the fault recorder is designed as
circulating storage. In this example 7 fault records can be
stored (written over).
1
3
8
7
6
54
2
Fig. 3.2 : Division of the memory into 8 segments,Fig. 3.2 : Division of the memory into 8 segments,
Fig. 3.2 : Division of the memory into 8 segments,Fig. 3.2 : Division of the memory into 8 segments,
Fig. 3.2 : Division of the memory into 8 segments,
for examplefor example
for examplefor example
for example
Memory space 6 to 4 is occupied.
Memory space 5 is currently being written in
A7
A6
A4
tdt
tf</tf>
f<</f>>
f
f</f>
t
tf<</tf>>
tu<</tu>>
E8D8CB
Blocking
input
External
Reset
L3L2L1
A3
A5
Serial Interface
N
G
PP
G
N
selfsupervision
Alarm
Relay 1
E2
C2
E1
C1
D2
D1
=
-
~
D9
E9
C9
L-/N
L+/L
t
U</U>
U
U<</U>>
TRIP
ENTER
-
+
SLECT/
REST
D4
D5
C4
E4
C5
E5
E6
C6
D6
D7
C7
E7
tu</tu>
a
A
Bb
cC
Power
supply
A8
Relay 2
df
dt
Q
D
df
dt
t
Relay 3
Relay 4
3. Design
3.1 Connections

55
55
5
Blocking function
PP
PP
Parameter Settingarameter Setting
arameter Settingarameter Setting
arameter Setting MRN3-1MRN3-1
MRN3-1MRN3-1
MRN3-1 MRN3-2MRN3-2
MRN3-2MRN3-2
MRN3-2
U< X X
U<< X X
U> X X
U>> X X
f1 X X
f2 X X
f3 X X
ΔΘ X
df/dt X
TT
TT
Table 3.3 : Blocking functionable 3.3 : Blocking function
able 3.3 : Blocking functionable 3.3 : Blocking function
able 3.3 : Blocking function
Parameters for the fault recorder
PP
PP
Parameter Settingarameter Setting
arameter Settingarameter Setting
arameter Setting MRN3-1MRN3-1
MRN3-1MRN3-1
MRN3-1 MRN3-2MRN3-2
MRN3-2MRN3-2
MRN3-2
Number of fault X X
events
Trigger events X X
Pre-Triggerzeit Tpre XX
TT
TT
Table 3.4 : Parameters for the fault recorderable 3.4 : Parameters for the fault recorder
able 3.4 : Parameters for the fault recorderable 3.4 : Parameters for the fault recorder
able 3.4 : Parameters for the fault recorder
Additional functions
PP
PP
Parameter Settingarameter Setting
arameter Settingarameter Setting
arameter Setting MRN3-1MRN3-1
MRN3-1MRN3-1
MRN3-1 MRN3-2MRN3-2
MRN3-2MRN3-2
MRN3-2
Relay assignment X X
Fault recorder X X
TT
TT
Table 3.5 : Additional functionsable 3.5 : Additional functions
able 3.5 : Additional functionsable 3.5 : Additional functions
able 3.5 : Additional functions
Date and time
PP
PP
Parameter Settingarameter Setting
arameter Settingarameter Setting
arameter Setting MRN3-1MRN3-1
MRN3-1MRN3-1
MRN3-1 MRN3-2MRN3-2
MRN3-2MRN3-2
MRN3-2
Year Y = 99 X X
Month M = 03 X X
Day D = 16 X X
hour h = 07 X X
minute m = 29 X X
second s = 56 X X
TT
TT
Table 3.6 : Date and timeable 3.6 : Date and time
able 3.6 : Date and timeable 3.6 : Date and time
able 3.6 : Date and time
The window for parameter setting is located behind the
measured value display. The parameter window can be
accessed via the <SELECT/RESET> key.
3.2 Parameter settings
System parameter
PP
PP
Parameter Settingarameter Setting
arameter Settingarameter Setting
arameter Setting MRN3-1MRN3-1
MRN3-1MRN3-1
MRN3-1 MRN3-2MRN3-2
MRN3-2MRN3-2
MRN3-2
Uprim/Usek XX
Δ/Y X X
fN X X
P2/FR X X
LED-Flash X X
TT
TT
Table 3.1 : System parametersable 3.1 : System parameters
able 3.1 : System parametersable 3.1 : System parameters
able 3.1 : System parameters
Protection parameters
Setting parameterSetting parameter
Setting parameterSetting parameter
Setting parameter MRMR
MRMR
MRN3-1N3-1
N3-1N3-1
N3-1 MRN3-2MRN3-2
MRN3-2MRN3-2
MRN3-2
U< X X
tU< XX
U<< X X
tU<< XX
U> X X
tU> XX
U>> X X
tU>> XX
TXX
f1XX
tf1 XX
f2XX
tf2 XX
f3XX
tf3 XX
df X
dt X
1/3 X
ΔΘ X
UB<XX
RS485/Slave X X
Baud-Rate* X X
Parity-Check* X X
TT
TT
Table 3.2: Protection parametersable 3.2: Protection parameters
able 3.2: Protection parametersable 3.2: Protection parameters
able 3.2: Protection parameters
* only Modbus
Since memory spaces 6, 7 and 8 are occupied, this
example shows that the memory has been assigned more
than eight recordings. This means that No. 6 is the oldest
fault recording and No. 4 the most recent one.
trigger occurrence
recording duration
T
pre
[s]
Fig. 3.3 : Basic set-up of the fault recorderFig. 3.3 : Basic set-up of the fault recorder
Fig. 3.3 : Basic set-up of the fault recorderFig. 3.3 : Basic set-up of the fault recorder
Fig. 3.3 : Basic set-up of the fault recorder
Each memory segment has a specified storage time which
permits setting of a time prior to the trigger event.
Via the interface RS485 the data can be read and
processed by means of a PC (HTL/PL-Soft4). The data is
graphically edited and displayed. Binary tracks are
recorded as well, e.g. activation and trip.

66
66
6
4. Working principle
4.1 Analog circuits
The input voltages are galvanically insulated by the input
transformers. The noise signals caused by inductive and
capacitive coupling are supressed by an analog R-C filter
circuit.
The analog voltage signals are fed to the A/D-converter
of the microprocessor and transformed to digital signals
through Sample- and Hold- circuits. The analog signals
are sampled with a sampling frequency of 16 x fN,
namely, a sampling rate of 1.25 ms for every measuring
quantity, at 50 Hz.
4.2 Digital circuits
The essential part of the MRN3MRN3
MRN3MRN3
MRN3 relay is a powerful
microcontroller. All of the operations, from the analog
digital conversion to the relay trip decision, are carried
out by the microcontroller digitally. The relay program is
located in an EPROM (Electrically-Programmable-Read-
Only-Memory). With this program the CPU of the
microcontroller calculates the three phase voltage in
order to detect a possible fault situation in the protected
object.
For the calculation of the voltage value an efficient digital
filter based on the Fourier Transformation (DFFT-Discrete
Fast Fourier Transformation) is applied to suppress high
frequency harmonics and d.c. components caused by
fault-induced transients or other system disturbances. The
microprocessor continuously compares the measured
values with the preset thresholds stored in the parameter
memory (EEPROM). If a fault occures an alarm is given
and after the set tripping delay has elapsed, the
corresponding trip relay is activated.
The relay setting values for all parameters are stored in
a parameter memory (EEPROM - Electrically Erasable
Programmable Read Only Memory), so that the actual
relay settings cannot be lost, even if the power supply is
interrupted.
The microprocessor is supervised by a built-in “watchdog”
timer. In case of a failure the watchdog timer resets the
microprocessor and gives an alarm signal via the output
relay “self supervision”.
4.3 Voltage supervision
The voltage element of MRN3MRN3
MRN3MRN3
MRN3 has the application in
protection of generators, consumers and other electrical
equipment against over/and undervoltage. The relay is
equipped with a two step independent three-phase
overvoltage (U>, U>>) and undervoltage (U<, U<<)
function with completely separate time and voltage
settings.
In delta connection the phase-to-phase voltages and in
star connection the phase-to-neutral voltages are
continuously compared with the preset thresholds.
For the overvoltage supervision the highest, for the
undervoltage supervision the lowest voltage of the three
phases are decisive for energizing.
3.3 LEDs
All LEDs (except LED RS, min. and max.) are two-
coloured. The LEDs on the left side, next to the alpha-
numerical display light up green during measuring and
red after tripping.
The LEDs below the push button <SELECT/RESET> are lit
green during setting and inquiry procedure of the setting
values which are printed on the left side next to the LEDs.
The LEDs will light up red after parametrizing of the
setting values next to their right side.
The LED marked with letters RS lights up during setting of
the slave address of the device for serial data
communication.
The LED marked with the letters FR is alight while the fault
recorder is being adjusted.
3.4 Front plate
L3
TRIP
ENTER
+
-
SELECT/RESET
RS
L2
L1
U<
U<<
1/3
U>
U>>
fN
DQ
T
MRN3-1
FR
P2
D/Y
f
max
min
DQ
f1tf1
f2
f3
tf2
tf3
tU>>
tU<<
tU<
tU>
L3
TRIP
ENTER
+
-
SELECT/RESET
RS
L2
L1
U<
U<<
df
U>
U>>
f
N
dt
T
MRN3-2
FR
P2
D/Y
f
max
min
df
f
1
t
f1
f
2
f
3
t
f2
t
f3
t
U>>
t
U<<
t
U<
t
U>
Fig. 3.5 : Front plate MRN3-2Fig. 3.5 : Front plate MRN3-2
Fig. 3.5 : Front plate MRN3-2Fig. 3.5 : Front plate MRN3-2
Fig. 3.5 : Front plate MRN3-2
Fig. 3.4 : Front plate MRN3-1Fig. 3.4 : Front plate MRN3-1
Fig. 3.4 : Front plate MRN3-1Fig. 3.4 : Front plate MRN3-1
Fig. 3.4 : Front plate MRN3-1

77
77
7
4.3.1 Selection of star or delta connection
All connections of the input voltage transformers are led
to screw terminals. The nominal voltage of the device is
equal to the nominal voltage of the input transformers.
Dependent on the application the input transformers can
be connected in either delta or star. The connection for
the phase-to-phase voltage is the delta connection. In star
connection the measuring voltage is reduced by 1/√3.
During parameter setting the connection configuration
either Y or Δhas to be adjusted.
Fig. 4.1: Input v.t.s in delta connectionFig. 4.1: Input v.t.s in delta connection
Fig. 4.1: Input v.t.s in delta connectionFig. 4.1: Input v.t.s in delta connection
Fig. 4.1: Input v.t.s in delta connection ((
((
(ΔΔ
ΔΔ
Δ))
))
)
Fig. 4.2: Input v.t.s in star connection (Y)Fig. 4.2: Input v.t.s in star connection (Y)
Fig. 4.2: Input v.t.s in star connection (Y)Fig. 4.2: Input v.t.s in star connection (Y)
Fig. 4.2: Input v.t.s in star connection (Y)
4.4 Principle of frequency supervision
The frequency element of MRN3 protects electrical
generators, consumers or electrical operating equipment
in general against over- or underfrequency. The relay
has independent three frequency elements f1- f3with a
free choice of parameters, with separate adjustable
pickup values and delay times.
The measuring principle of the frequency supervision is
based on the time measurement of complete cycles,
whereby a new measurement is started at each voltage
zero passage. The influence of harmonics on the
measuring result is thus minimized.
Fig. 4.3: Determination of cycle duration byFig. 4.3: Determination of cycle duration by
Fig. 4.3: Determination of cycle duration byFig. 4.3: Determination of cycle duration by
Fig. 4.3: Determination of cycle duration by
means of zero passagesmeans of zero passages
means of zero passagesmeans of zero passages
means of zero passages.
In order to avoid false tripping during occurence of
interference voltages and phase shifts the relay works with
an adjustable measuring repetition (see chapter 5.4.2)
Frequency tripping is sometimes not desired by low
measured voltages which for instance occur during
alternator acceleration. All frequency supervision
functions can be blocked with the aid of an adjustable
voltage threshold UBin case the measured voltage value
is below this value.
4.5 Measuring of frequency gradient
(MRN3-2)
Electrical generators running in parallel with the mains,
e.g. industrial internal power supply plants, should be
separated from the mains when failure in the intrasystem
occurs for the following reasons:
zIt must be prevented that the electrical generators are
damaged when mains voltage recovering
asynchrone, e.g. after a short interruption.
zThe industrial internal power supply must be
maintained.
A reliable criterion of detecting mains failure is the
measurement of the rate of change of frequency df/dt.
Precondition for this is a load flow via the mains coupling
point. At mains failure the load flow changing then
spontaneously leads to an increasing or decreasing
frequency. At active power deficit of the internal power
station a linear drop of the frequency occurs and a linear
increase occurs at power excess. Typical frequency
gradients during application of “mains decoupling” are in
the range of 0.5 Hz/s up to over 2 Hz/s. The MRN3
detects the instantaneous frequency gradient df/dt of each
mains voltage period in an interval of one half period
each. Through multiple evaluation of the frequency
gradient in sequence the continuity of the directional
change (sign of the frequency gradient) is determined.
Because of this special measuring procedure a high safety
in tripping and thus a high stabilty against transient
processes, e.g. switching procedure are reached. The
total switching off time at mains failure is between 60 ms
and 80 ms depending on the setting.
Sec. Winding of
mains V.T.
U31
U23
U12
b
a
A5
A3
A4
A6
A7
C
A8
A8
CA7
A6
A4
A3
A5
a
b
U1
U2
U3
Sec. Winding of
mains V.T.
u(t) T
T
t

88
88
8
The rotor displacement angle ϑbetween stator and rotor
is depending of the mechanical moving torque of the
generator shaft. The mechanical shaft power is balanced
with the electrical feeded mains power, and therefore the
synchronous speed keeps constant (Fig. 4.5).
Fig. 4.5: Voltage vectors at mains parallelFig. 4.5: Voltage vectors at mains parallel
Fig. 4.5: Voltage vectors at mains parallelFig. 4.5: Voltage vectors at mains parallel
Fig. 4.5: Voltage vectors at mains parallel
operationoperation
operationoperation
operation
4.6 Vector surge supervision (MRN3-1)
The vector surge supervision protects synchronous
generators in mains parallel operation due to very fast
decoupling in case of mains failure. Very dangerous are
mains auto reclosings for synchronous generators. The
mains voltage returning after 300 ms can hit the
generator in asynchronous position. A very fast
decoupling is also necessary in case of long time mains
failures. Generally there are two different applications:
a) Only mains parallel operation no singleOnly mains parallel operation no single
Only mains parallel operation no singleOnly mains parallel operation no single
Only mains parallel operation no single
operation:operation:
operation:operation:
operation:
In this application the vector surge supervision
protects the generator by tripping the generator
circuit breaker in case of mains failure.
b) Mains parallel operation and singleMains parallel operation and single
Mains parallel operation and singleMains parallel operation and single
Mains parallel operation and single
operation:operation:
operation:operation:
operation:
For this application the vector surge supervision trips
the mains circuit breaker. Here it is insured that the
gen.-set is not blocked when it is required as the
emergency set.
A very fast decoupling in case of mains failures for
synchronous generators is known as very difficult. Voltage
supervision units cannot be used because the synchronous
alternator as well as the consumer impedance support the
decreasing voltage.
For this the mains voltage drops only after some 100 ms
below the pickup threshold of voltage supervision relays
and therefore a safe detection of mains auto reclosings is
not possible with this kind of relay.
Frequency relays are partial unsuitable because only a
highly loaded generator decreases its speed within 100
ms. Current relays detect a fault only when shortcircuit
type currents exist, but cannot avoid their development.
Power relays are able to pickup within 200 ms, but they
cannot prevent power to rise to short-circuit values too.
Since power changes are also caused by sudden loaded
alternators, the use of power relays can be problematic.
Whereas the MRN3-1MRN3-1
MRN3-1MRN3-1
MRN3-1 detects mains failures within 60
ms without the restrictions described above because they
are specially designed for applications where very fast
decoupling from the mains is required.
Adding the operating time of a circuit breaker or contactor,
the total disconnection time remains below 150 ms. Basic
requirement for tripping of the generator/mains monitor
is a change in load of more than 15 - 20 % of the rated
load. Slow changes of the system frequency, for instance
at regulating processes (adjustment of speed regulator) do
not cause the relay to trip.
Trippings can also be caused by short-circuits within the
grid, because a voltage vector surge higher than the
preset value can occur. The magnitude of the voltage
vector surge depends on the distance between the short-
circuit and the generator. This function is also of
advantage to the Power Utility Company because the
mains short-circuit capacity and consequently the energy
feeding the short-circuit is limited.
To prevent a possible false tripping the vector surge
measuring can be blocked at a set low input voltage (refer
to 5.4.7). The undervoltage lockout acts faster then the
vector surge measurement.
Vector surge tripping is blocked by a phase loss so that a
VT fault (e.g. faulty VTs fuse) does not cause false tripping.
When switching on the aux. voltage or measuring voltage,
the vector surge supervision is blocked for 5 s (refer to
chapter 4.8).
Note:Note:
Note:Note:
Note:
In order to avoid any adverse interference voltage effects,
for instance from contactors or relays, which may cause
overfunctions, MRN3-1MRN3-1
MRN3-1MRN3-1
MRN3-1 should be connected separately
to the busbar.
4.6.1 Measuring principle of vector surge
supervision
When a synchronous generator is loaded, a rotor
displacment angle is build between the terminal voltage
(mains voltage U1) and the synchronous internal voltage
(Up). Therefore a voltage difference ΔU is built between
Up and U1 (Fig. 4.4).
Fig. 4.4: Equivalent circuit at synchronousFig. 4.4: Equivalent circuit at synchronous
Fig. 4.4: Equivalent circuit at synchronousFig. 4.4: Equivalent circuit at synchronous
Fig. 4.4: Equivalent circuit at synchronous
generator in parallel with the mainsgenerator in parallel with the mains
generator in parallel with the mainsgenerator in parallel with the mains
generator in parallel with the mains
UP
~
ΔU= .jX
d
I1
U1Z
~
Mains
I2
I1
ΔU= l
1
.jX
d
UP
U
1
Generator Mains / Load

99
99
9
Fig. 4.6: Equivalent circuit at mains failureFig. 4.6: Equivalent circuit at mains failure
Fig. 4.6: Equivalent circuit at mains failureFig. 4.6: Equivalent circuit at mains failure
Fig. 4.6: Equivalent circuit at mains failure
Fig. 4.7: Voltage vectors at mains failureFig. 4.7: Voltage vectors at mains failure
Fig. 4.7: Voltage vectors at mains failureFig. 4.7: Voltage vectors at mains failure
Fig. 4.7: Voltage vectors at mains failure
In case of mains failure or auto reclosing the generator
suddenly feeds a very high consumer load. The rotor
displacement angle is decreased repeatedly and the
voltage vector U1changes its direction (U1‘) (Fig. 4.6 and
4.7).
Fig. 4.8: Voltage vector surgeFig. 4.8: Voltage vector surge
Fig. 4.8: Voltage vector surgeFig. 4.8: Voltage vector surge
Fig. 4.8: Voltage vector surge
As shown in the voltage/time diagram the instantaneous
value of the voltage jumps to another value and the phase
position changes. This is named phase or vector surge.
The MRN3-1MRN3-1
MRN3-1MRN3-1
MRN3-1 measures the cycle duration. A new
measuring is started at each voltage zero passage. The
measured cycle duration is internally compared with a
quartz stable reference time and from this the deviation
of the cycle duration of the voltage signal is ascertained.
In case of a vector surge as shown in fig. 4.8, the zero
Application hint
Although the vector surge relay guarantees very fast and
reliable detection of mains failures under nearly all
operational conditions of mains parallel running
alternators, the following borderline cases have to be
considered accordingly:
a) None or only insignificant change of power flow at the
utility connection point during mains failures.
This can occur during peak lopping operation or in CHP
stations (Combined Heat and Power) where the power
flow between power station and the public grid may be
very low. For detection of a vector surge at parallel
running alternators, the load change must be at least 15
- 20 % of the rated power. If the active load at the utility
connection point is regulated to a minimal value and a
high resistance mains failure occurs, then there are no
vector surge nor power and frequency changes and the
mains failure is not detected.
This can only happen if the public grid is disconnected
near the power station and so the alternators are not
additionally loaded by any consumers. At distant mains
failures the synchronous alternators are abruptly loaded
by remaining consumers which leads directly to a vector
surge and so mains failure detection is guaranteed.
If such a situation occurs the following has to be taken into
account:
In case of an undetected mains failure, i.e. with the mains
coupling C.B. closed, the vector surge relay reacts upon
the first load change causing a vector surge and trips the
mains C.B.
For detecting high resistance mains failures a minimum
current relay with an adjustable trip delay can be used. A
trip delay is needed to allow regulating actions where the
current may reach “zero” at the utility connection point.
At high resistance mains failures, the mains coupling C.B.
is tripped by the minimum current relay after the time
delay.
To prevent asynchronous switching on, an automatic
reclosing of the public grid should be not possible during
this time delay.
passage occurs either earlier or later. The established
deviation of the cycle duration is in compliance with the
vector surge angle.
If the vector surge angle exceeds the set value, the relay
trips immediately.
Tripping of the vector surge is blocked in case of loss of
one or more phases of the measuring voltage.
TT
TT
Tripping logic for vector surge measurement:ripping logic for vector surge measurement:
ripping logic for vector surge measurement:ripping logic for vector surge measurement:
ripping logic for vector surge measurement:
The vector surge function of the MRN3-1 supervises vector
surges in all three phases at the same time. Tripping of the
relay can be adjusted for one phase vector surge (more
sensitive measurement). For this the parameter 1/3 has
to be set to “1Ph”. When the parameter 1/3 is set to
“3Ph”, tripping of the vector surge element occurs only if
the vector surge angle exceeds the set value in all three
phases at the same time.
UP~
ΔU’= l’
1.jXdl’1
U’
1Z
~
Mains
Δ
Load
Generator
U’1
U1
U
P
ΔU’= l’
1
.jXd
U(t)
Voltage vector surge
u
1
(t) u ’(t)
1
Trip
t
Dt~ DQ

4.7 Voltage threshold value for frequency
measuring
At low measuring voltages, e.g. during generator start-
up, frequency and vector surge or df/dt-measuring is
perhaps not desired.
By means of the adjustable voltage threshold value UB<,
functions f1- f3, df/dt or ΔΘ are blocked if the measured
voltage falls below the set value.
Blocking function set in compliance with require-
ments :
The MRN3MRN3
MRN3MRN3
MRN3 has an external blocking input. By applying
the auxiliary voltage to input D8/E8, the requested
protection functions of the relay are blocked (refer to
5.7.1).
A further measure could be, that the load regulation at
the utility connection point guarantees a minimum power
flow of 15 - 20 % of rated power.
b) Short circuit type loading of the alternators at distant
mains failures
At any distant mains failure, the remaining consumers
cause sudden short circuit type loading of the power
station generators. The vector surge relay detects the
mains failure in about 60 ms and switches off the mains
coupling C.B. The total switch off time is about 100 - 150
ms. If the generators are provided with an extremely fast
1010
1010
10
4.8 Blocking function
No.No.
No.No.
No. DynamicDynamic
DynamicDynamic
Dynamic BehaviourBehaviour
BehaviourBehaviour
Behaviour U</<<U</<<
U</<<U</<<
U</<< U>/>>U>/>>
U>/>>U>/>>
U>/>> ff
ff
f11
11
1, f, f
, f, f
, f22
22
2, f, f
, f, f
, f33
33
3ΔΔ
ΔΔ
ΔΘΘ
ΘΘ
Θdf/dtdf/dt
df/dtdf/dt
df/dt
1 voltage to external free program- free program- free program- free program- free program-
blocking input is mable mable mable mable mable
applied
2 blocking input is released released released after released after released after
released instantaneously instantaneously 1 s 5 s 5 s
3 supply voltage is blocked for blocked for blocked for 1 s blocked for 1 s blocked for 1 s
switched on 200 ms 200 ms
4 3ph measuring volt. released released blocked for 1 s blocked for 5 s blocked for 5 s
is suddenly applied
5 one or several released released blocked blocked blocked
measuring voltages
are switched off
suddenly (phase
failure)
6 measuring voltage released released blocked blocked blocked
smaller UB< (adjust-
able voltage thresh-
old value)
TT
TT
Table 4.1: Dynamic behaviour of MRN3 functionsable 4.1: Dynamic behaviour of MRN3 functions
able 4.1: Dynamic behaviour of MRN3 functionsable 4.1: Dynamic behaviour of MRN3 functions
able 4.1: Dynamic behaviour of MRN3 functions
short circuit protection e.g. able to detect di/dt, the
alternators might be switched off unselectively by the
generator C.B., which is not desireable because the power
supply for the station is endangered and later on
synchronized changeover to the mains is only possible
after manual reset of the overcurrent protection.
To avoid such a situation, the alternator C.B.s must have
a delayed short circuit protection. The time delay must be
long enough so that mains decoupling by the vector surge
relay is guaranteed.

1111
1111
11
5.1 Display
Function Display shows Pressed pushbutton Corresponding Type of relay
LED
Normal operation CSPC all types
Measured operating values Actual measured value <SELECT/RESET> one time L1, L2, L3,
Min. and max. values of for each value f, min, max
voltage, frequency and
ΔΘ
MRN3-1
vector surge df MRN3-2
Transformer ratio of the CT’s (SEK) 1.01-6500=prim <SELECT/RESET><+><-> L1, L2, L3
Setting values: Y/DELT <SELECT/RESET><+><->
Δ
/Y
star/delta connection
Parameter switch/ext. Trigger for FR SET1, SET2, B_S2, R_S2, <SELECT/RESET><+><-> P2
B_FR, R_FR, S2_FR
Switch-over LED flash FLSH <SELECT/RESET><+><->
No LED flash NOFL
undervoltage (low set) setting value in volt <SELECT/RESET><+><-> U<
tripping delay of low set element setting value in seconds one time for each value t
U<
undervoltage (high set) setting value in volt <SELECT/RESET><+><-> U<<
tripping delay of high set element setting value in seconds one time for each value t
U<<
overvoltage (low set) setting value in volt <SELECT/RESET><+><-> U>
tripping delay of low set element setting value in seconds one time for each value t
U>
overvoltage (high set) setting value in volt <SELECT/RESET><+><-> U>>
tripping delay of high set element setting value in seconds one time for each value t
U>>
rated frequency setting value in Hz <SELECT/RESET><+><-> f
N
frequency measuring repitition setting value <SELECT/RESET><+><-> T
frequency element f1 setting value in Hz <SELECT/RESET><+><-> f
1
tripping delay of frequency element f1 setting value in seconds one time for each value t
f1
frequency element f2 setting value in Hz <SELECT/RESET><+><-> f
2
tripping delay of frequency element f2 setting value in seconds one time for each value t
f2
frequency element f3 setting value in Hz <SELECT/RESET><+><-> f
3
tripping delay of frequency element f3 setting value in seconds one time for each value t
f3
1-of-3/3-of-3 measurement 1Ph/3Ph <SELECT/RESET><+><-> 1/3 MRN3-1
threshold for vector surge setting value in degree <SELECT/RESET><+><->
ΔΘ
MRN3-1
setting value df/dt setting value in Hz/s <SELECT/RESET><+><-> df MRN3-2
measuring repitition df/dt setting value in periods one time for each value dt
Blocking EXIT <+> until max. setting value LED of blocked
parameter
Undervoltage blocking of setting value in Volt <SELECT/RESET><+><-> f,
ΔΘ
, df
frequency and vector surge meas-
uring (df/dt for MRN3-2)
Slave address of serial interface 1 - 32 <SELECT/RESET><+><-> RS
Baud-Rate
1)
1200-9600 <SELECT/RESET><+><-> RS
Parity-Check
1)
even odd no <SELECT/RESET><+><-> RS
Recorded fault data: tripping values in Volt <SELECT/RESET><+><-> L1, L2, L3,
star—connection: one time for each phase U<, U<<,
U1, U2, U3 U>, U>>
delta-connection: tripping values in Volt <SELECT/RESET><+><-> L1, L2, L3
U12, U23, U31 one time for each phase U<, U<<,
U>, U>>
frequency tripping values in Hz <SELECT/RESET><+><-> f, f1, f2, f3
one time for each phase
rate of change of frequency tripping value in Hz/s <SELECT/RESET><+><-> df MRN3-2
vector surge tripping value in degree <SELECT/RESET><+><->
ΔΘ
+L1,L2 or L3 MRN3-1
one time for each phase
Delet failure memory wait <-><SELECT/RESET>
Enquiry failure memory FLT1; FLT2.... <+><-> L1, L2, L3, U<
U<<, U>, U>>
f, Ddf/dt,
ΔΘ
Save parameter? SAV? <ENTER>
Save parameter! SAV! <ENTER> for about 3 s
5. Operation and settings
1)
only Modbus

1212
1212
12
Function Display shows Pressed pushbutton Corresponding Type of relay
LED
Trigger signal for the fault recorder TEST, P_UP, A_PI, TRIP <SELECT/RESET><+><-> FR
Number of fault occurences S=2, S=4, S=8 <SELECT/RESET><+><-> FR
Display of date and time Y=99, M=10, D=1, <SELECT/RESET><+><->
h=12, m=2, s=12
Software version First part (e.g. D02-) <TRIP>
Sec. part (e.g. 6.01) one time for each part
Manual trip TRI? <TRIP>
three times
Inquire password PSW? <SELECT/RESET>/
<+>/<->/<ENTER>
Relay tripped TRIP <TRIP> or fault tripping
Secret password input XXXX <SELECT/RESET>/
<+>/<->/<ENTER>
System reset CSPC <SELECT/RESET>
for about 3 s
TT
TT
Table 5.1: possible indication messages on the displayable 5.1: possible indication messages on the display
able 5.1: possible indication messages on the displayable 5.1: possible indication messages on the display
able 5.1: possible indication messages on the display
5.2 Setting procedure
In this paragraph the settings for all relay parameters are
described in detail. For parameter setting a password has
to be entered first (please refer to 4.4 of description “MR-
Digital Multifunctional Relays”).
5.3 Systemparameter
5.3.1 Display of residual voltage UEas
primary quantity (Uprim/Usec
The residual voltage can be shown as primary measuring
value. For this parameter the transformation ratio of the
VT has to be set accordingly. If the parameter is set to
“sek”, the measuring value is shown as rated secondary
voltage.
Example :
The voltage transformer used is of 10 kV/100V. The
transformation ratio is 100 and this value has to be set
accordingly. If still the rated secondary voltage should be
shown, the parameter is to be set to 1.
5.3.2 ΔΔ
ΔΔ
Δ/Y - Switch over
Depending on the mains voltage conditions, the input
voltage transformers can be operated in delta or Y
connection. Change-overs are effected via the <+> and
the <-> keys and stored with <ENTER>.
5.3.3 Setting of nominal frequency
For proper functioning it is necessary to first adjust the
rated frequency (50 oder 60 Hz).
For this a distinction has to be made between the settings
v = 50 Hz / f = 50 Hz or v = 60 Hz / f = 60 Hz
The difference lies in the method of voltage measuring.
With the setting “v” = 50/60 Hz voltage measuring is
independent of the existing frequency. This means, the
voltage value can be correctly measured between 30 Hz
and 80 Hz without adverse effects from the frequency.
With the setting “f” = 50/60 Hz the measured voltage
value is influenced by the frequency. (see Table 5.2)
This difference in settings is required for the fault
recorder. If the fault recorder is to be used, the setting
must be f = 50 Hz or f = 60 Hz.
The different designations “f” or “v” have no influence on
any of the other functions.
All frequency functions are determined by setting the
nominal frequency, i.e. whether the set frequency
thresholds are evaluated as over or under frequency (see
also chapter 5.4.4). Also the cycle duration (20 ms at 50
Hz and 16.67 ms at 60 Hz) derives from this setting which
determines the minimum tripping delay for frequenc y
elements f1- f3with an adjustable multiplier (see also
chapter 5.4.5).
During setting of the nominal frequency a value in Hz is
shown on the display.
Declination of measuring value at 50Hz
Declination of measuring value at 60Hz
[%]
100.5
100.0
44 46 48 50 52 54 56
[Hz]
99.5
99.0
98.5
98.0
97.5
54 56 58 60 62 64 66
[Hz]
[%]
100.5
100.0
99.5
99.0
98.5
98.0
97.5

1313
1313
13
SettingSetting
SettingSetting
Setting v = 50v = 50
v = 50v = 50
v = 50 f = 50f = 50
f = 50f = 50
f = 50 v = 60v = 60
v = 60v = 60
v = 60 f = 60f = 60
f = 60f = 60
f = 60
Rated frequency 50 Hz 50 Hz 60 Hz 60 Hz
Influence on voltage none 0.5..1%/Hz (see none 0.5..1%/Hz (see
measurement table 5.2) table 5.2)
Fault recorder Recording Recording Recording Recording
distorted** distorted*** distorted** distorted***
Influence on all other functions none none none none
TT
TT
Table 5.2 : Deviation of measured value at 50 or 60 Hzable 5.2 : Deviation of measured value at 50 or 60 Hz
able 5.2 : Deviation of measured value at 50 or 60 Hzable 5.2 : Deviation of measured value at 50 or 60 Hz
able 5.2 : Deviation of measured value at 50 or 60 Hz
* Setting is important for differentiation between over-and underfrequency.
** Sample rate is variably adjusted to the momentarily measured frequency. 16 samples are always measured in one period.
*** Sample rate setting is fixed to 50 Hz or 60 Hz. 16 samples per 20 ms or 16.67 ms are always measured.
5.3.4 Display of the activation storage
(FLSH/NOFLE)
If after an activation the existing current drops again
below the pickup value, e.g. U<, without a trip has been
initiated, LED U< signals that an activation has occured by
flashing fast. The LED keeps flashing until it is reset again
(push button <RESET>. Flashing can be suppressed
when the parameter is set to NOFL.
5.3.5 Parameterswitch / external trigger
for the fault recorder
By means of the parameter-change-over switches it is
possible to activate two different parameter sets. Switching
over of the parameter sets can either be done by means
of software or via the external inputs RESET or blocking
input. Alternatively, the external inputs can be used for
Reset or blocking and for the triggering of the fault
recorder.
SoftwareSoftware
SoftwareSoftware
Software Blocking inputBlocking input
Blocking inputBlocking input
Blocking input RESET inputRESET input
RESET inputRESET input
RESET input
parameterparameter
parameterparameter
parameter used asused as
used asused as
used as used asused as
used asused as
used as
SET1 Blocking input RESET input
SET2 Blocking input RESET input
B_S2 Parameter switch RESET input
R_S2 Blocking input Parameter switch
B_FR External trigger- RESET input
ing of the fault
recorder
R_FR Blocking input External trigg-
ering of the
fault recorder
R_FR Parameter switch External trigg-
ering of the
fault recorder
With the settings SET1 or SET2 the parameter set is
activated by software. Terminals C8/D8 and D8/E8 are
then available as external reset input or blocking input.
With the setting B_S2 the blocking input (D8, E8) is used
as parameter-set change-over switch. With the setting
R_S2 the reset input (D8, E8) is used as parameter-set
change-over switch. With the setting B_FR the fault
recorder is activated immediatelay by using the blocking
input. On the front plate the LED FR will then light up for
the duration of the recording. With the setting R_FR the
fault recorder is activated via the reset input. With the
setting S2_FR parameter set 2 can be activated via the
blocking input and/or the fault recorder via the reset
input. The relevant function is then activated by applying
the auxiliary voltage to one of the external inputs. With the
setting R_FR the fault recorder is activated via the reset
input. With the setting S2_FR parameter set 2 can be
activated via the blocking input and/or the fault recorder
via the reset input.
The relevant function is then activated by applying the
auxiliary voltage to one of the external inputs.
Important note :
When functioning as parameter change over facility, the
external input RESET is not available for resetting. When
using the external input BLOCKING the protection
functions must be deactivated by software blocking
separately (refer to chapter 5.7.1).
5.4 Protection parameters
5.4.1 Parameter setting of over-and
undervoltage supervision
The setting procedure is guided by two coloured LEDs.
During setting of the voltage thresholds the LEDs U<,
U<<, U> and U>> are lit green. During setting of the
trip delays tU>, tU>>, tU< and tU<< the according LEDs light
up red.
Thresholds of the voltage supervisionThresholds of the voltage supervision
Thresholds of the voltage supervisionThresholds of the voltage supervision
Thresholds of the voltage supervision
During setting of the threshold U>, U>>, U< and U<<
the displays shows the voltages directly in volt. The
thresholds can be changed by the <+><-> push buttons
and stored with <ENTER>.
The undervoltage supervision (U< and U<<) as well as
the overvoltage supervision (U> and U>>) can be
deactivated by setting the threshold to “EXIT”.

1414
1414
14
TT
TT
Tripping delay of voltage supervisionripping delay of voltage supervision
ripping delay of voltage supervisionripping delay of voltage supervision
ripping delay of voltage supervision
During setting of the tripping delays tU<, tU<<, tU> and tU>>
the display shows the value directly in seconds. The
tripping delay is changed via the push button <+> and
<-> in the range of 0.04 s to 50 s and can be stored with
the push button <ENTER>.
When setting the tripping delay to “EXIT” the value is infinit
meaning only warning, no tripping.
5.4.2 Number of measuring repetitions (T)
for frequency functions
In order to avoid false tripping of the unit at short voltage
drops of the system voltage or interference voltages,
MRN3 works with an adjustable measuring repetition.
When the instantaneous frequency measuring value
exceeds (at overfrequency) or falls below (at
uncremented, otherwise the counter is decremented
down to the minimum value of 0. Only when the counter
exceeds th value adjusted at T, alarm is given and after the
tripping delay of the frequency element has elapsed the
tripping command is given.
The setting range for T is between 2-99.
Recommendation for setting :Recommendation for setting :
Recommendation for setting :Recommendation for setting :
Recommendation for setting :
For short tripping times, e.g. for machine prptection or for
mains decoupling T should be set in the range from 2-5.
At precision measurements, e.g. exact measurement of
the system frequency a setting of T in the range from 5-
10 is recommended.
5.4.3 Threshold of frequency supervision
The frequency supervision of MRN3MRN3
MRN3MRN3
MRN3 has three frequency
elements independent from each other. Acc. to settin the
pickup value above or below the nominal frequency,
these elements can be used for over- or underfrequency
supervision.
Dependent on the preset nominal frequency fNthe pickup
values from 30 Hz up to 70 Hz at fN= 50 Hz and from
40 Hz to 80 Hz at fN= 60 Hz can be set. During settin
of the pickup values f1-f3the display shows the values in
Hz. A value of for instance 49.8 Hz is indicated with
“4980”.
The function of the individual frequency elements can be
deactivated by settin the pickup values to “EXIT”. The
setting value “EXIT” corresponds to the rated frequency.
5.4.4 Tripping delays for the frequency
elements
Tripping delays tf1-tf3 of the four frequency elements can
be set independently from tf1min-50 s. The minimum
tripping delay tf1min of the relay depends upon the number
of set measuring repetitions T (periods) and amounts to :
Tt
f,min
2....49 (T+1).20 ms
50...69 (T-49).50 ms + 1 s
70...99 (T-69).100 ms + 2 s
When setting the tripping delay to “EXIT” by pressing push
button <+> up to the maximum setting value, the
corresponding tripping relay is blocked. Pickup of the
frequency element is however displayed on the front plate
by the corresponding LED, an assigned alarm relay is also
activated. This setting applies to 50 Hz and 60 Hz.
5.4.5 Parameter setting of vector surge
supervision MRN3-1)
Both the vector surge angle ΔΘ as well as the tripping
logic concerning the vector surge have to be adjusted for
a vector surge supervision.
If the tripping logic is set to 1-of-3 (=”1Ph” on the
display), the relay trips as soon as the measured vector
surge angle has exceeded the set value ΔΘ in one of the
three phases. This is the more sensitive adjustment when
compared with the three phase tripping logic 3-of-3
(=”3Ph” on the display), where tripping occurs only if the
vector surge angle exceeds the set value in all three
phases.
We recommend to choose the one phase tripping logic
“1Ph”. Only if this adjustment is too sensitive, adjustment
“3Ph” should be used.
The recommended setting of the vector surge angle ΔΘ
in a low impedance mains is 4-6 degrees. This setting is
sufficient in most cases, because low impedace mains do
not have a vector surge greater than this value. In case of
an auto reclosing, this value is exceeded. In high
impedance mains the setting should be 100to 120to
avoid failure tripping when switching on or switching off
big consumer loads.
The vector surge function of this device can be checked
as follows :
a) Generator in isolated operation: Switching off and on
of loads (approx. 20% of the nominal generator
capacity) must trip the relay. Later in normal isolated
operation the tripping of the relay is inhibited.
b) In mains parallel operation switching on and
switching off of consumer loads and controlling the
governor of the prime mover should not trip the
relay.
If possible the test described under a) and b) should be
double checked by a real auto reclosing.
Threshold for the vector surge supervisionThreshold for the vector surge supervision
Threshold for the vector surge supervisionThreshold for the vector surge supervision
Threshold for the vector surge supervision
When the pickup value of the vector surge supervision is
set, a value in angular degree is indicated at athe display.
The pickup value requested can be adjusted by
pushbuttons <+> and <-> in the range of 20to 220.
LED ΔΘ lights up red during this procedure.

1515
1515
15
5.4.6 Parameter setting of frequency
gradient (MRN3-2)
The pickup value of frequency gradient (parameter df)
can be set between 0.2 to 10 Hz/s. The number of
measuring repetitions (parameter dt) can be set between
2-64 cycles. This parameter defines the number of df/dt
measurements, which have to exceed the set value, before
tripping.
Setting information :
The power difference after mains failure causes a change
in frequency, which can approximately be calculated as
follows :
df fN
= . ΔP
dt TA
with
fN = rated frequency in Hz
TA = starting time at rated torque
ΔP = per unit power deficit with reference to the
rated active power of the generator
If the inertia time constant is known and a power
difference given, the frequency gradient can be estimated
by the a.m. equation. At a supposed power difference of
20% and an inertia time constant of 10 s, the frequency
gradient is 1 Hz/s.
To prevent false trippings at loading, deloading or failure
signals, we would recommend a setting value for dt of
minimum 4 cycles.
5.4.7 Voltage threshold value for
frequency and vector surge
measuring (df/dt at MRN3-2)
Correct frequency measuring or vector surge measuring
cannot be obtained if the system voltage is very low, for
instance during generator start up or voltage failure. False
tripping of the MRN3MRN3
MRN3MRN3
MRN3 in such cases is prevented by an
adjustable voltage threshold UB. If the system voltage is
below this threshold, these functions of the relay are
blocked.
During adjustment of UB< LEDs f and ΔΘ or df light up in
the upper display part.
5.4.8 Adjustment of the slave address
By pressing push buttons <+> and <-> the slave address
can be set in the range of 1-32. During this adjustment
the LED RS lights up.
5.4.9 Setting of Baud-rate (applies for
Modbus Protocol only)
Different transmission rates (Baud rate) can be set for data
transmission via Modbus Protocol.
The rate can be changed by push buttons <+> and <-
> and saved by pressing <ENTER>.
5.4.10 Setting of parity (applies for
Modbus Protocol only)
The following three parity settings are possible :
z“even” = even
z“odd” = odd
z“no” = no parity check
The setting can be changed by push buttons <+> and <-
> and saved by pressing <ENTER>.
5.5 Adjustment of the fault recorder
The MRI3 is equipped with a fault recorder (see chapter
3.7). Three parameters can be determined.
5.5.1 Number of the fault recordings
The max. recording time is 16 s at 50 Hz or 13.33 s at
60 Hz.
The number of max. recordings requested has to be
determined in advance. There is a choice of (1)* 2, (3)*
4 or (7)* 8 recordings and dependent on this the duration
of the individual fault recordings is defined, i.e.
(1)* 2 recordings for a duration of 8 s (with 50 Hz)
(6.66 s with 60 Hz)
(3)* 4 recordings for a duration of 4 s (with 50 Ha)
(3.33 s with 60 Hz)
(7)* 8 recordings for a duration of 2 s (with 50 Hz)
(1.66 s with 60 Hz)
* is written over when a new trigger signal arrives
Caution :
If the fault recorder is used, the frequency should be set
to f = 50 Hz or f = 60 Hz (see chapter 5.3.3).
5.5.2 Adjustment of trigger occurences
There is a choice between four different occurences :
P_UP (PickUP) Storage is initiated after recognition
of a general activation.
TRIP Storage is initiated after a trip has
occured.
A_PI (After Pickup) Storage is initiated after the last
activation threshold was fallen short
of.
TEST Storing is activated by simultaneous
actuation of the keys <+> and <->.
During the recording time the display
shows “Test”.
5.5.3 Pre-trigger time (Tpre)
By the time Tpre it is determined which period of time prior
to the trigger occurence should be stored as well. It is
possible to adjust a time between 0.05s and the max.
recording interval (2, 4 and 8s). With keys <+> and <-
> the values can be changed and with <ENTER> be
saved.

1616
1616
16
5.6 Adjustment of the clock
When adjusting the date and time, LED l light up. The
adjustment method is as follows:
Date : Year Y = 00
Month M = 00
Day D = 00
Time : Hour h = 00
Minute m = 00
Second s = 00
The clock starts with the set date and time as soon as the
supply voltage is switched on. The time is safeguarded
against short-term voltage failures (min. 6 minutes).
Note :
The window for parameter setting is located behind the
measured value display. The parameter window can be
accessed via the <SELECT/RESET> key.
5.7 Additional functions
5.7.1 Setting procedure for blocking the
protection functions
The blocking function of the MRN3MRN3
MRN3MRN3
MRN3 can be set according
to requirement. By applying the aux. voltage to D8/E8,
the functions chosen by the user are blocked. Setting of
the parameter should be done as follows:
zWhen pressing push buttons <ENTER> and <TRIP>
at the same time, message “BLOC” is displayed (i.e.
the respective function is blocked) or “NO_B” (i.e. the
respective function is not blocked). The LED allocated
to the first protection function U< lights red.
zBy pressing push buttons <+> <-> the value
displayed can be changed.
zThe changed value is stored by pressing <ENTER>
and entering the password.
zBy pressing the <SELECT/RESET> push button, any
further protection function which can be blocked is
displayed.
zThereafter the menu is left by pressing <SELECT/
RESET> again.
zIf the <SELECT/RESET> key is actuated again, the
blocking menu is left and the assignment mode is
accessed∧.
FunctionFunction
FunctionFunction
Function DescriptionDescription
DescriptionDescription
Description DisplayDisplay
DisplayDisplay
Display LEDLED
LEDLED
LED
U< Undervoltage step 1 BLOC red
U<< Undervoltage step 2 BLOCK red
U> Overvoltage step 1 NO_B red
U>> Overvoltage step 2 NO_B red
f1 Frequency step 1 BLOC red
f2 Frequency step 2 BLOC red
f3 Frequenzstufe 3 NO_B red
DQ Vector surge BLOC red
df/dt Frequency changing rate BLOC red
TT
TT
Table 5.3 : Blockadefunktion fur twei parametersatzeable 5.3 : Blockadefunktion fur twei parametersatze
able 5.3 : Blockadefunktion fur twei parametersatzeable 5.3 : Blockadefunktion fur twei parametersatze
able 5.3 : Blockadefunktion fur twei parametersatze
Assignment of the output relays :
Unit MRN3MRN3
MRN3MRN3
MRN3 has five output relays. The fifth output relay
is provided as permanent alarm relay for self supervision
is normally on. Output relays 1-4 are normally off and
can be assigned as alarm or tripping relays to the voltage
functions which can either be done by using the push
buttons on the front plate or via serial interface RS485.
The assignment of the output relays is similar to the setting
of parameters, however, only in the assignment mode.
The assignment mode can be reached only via the
blocking mode.
By pressing push button <SELECT/RESET> in blocking
mode again, the assignment mode is selected. The relays
are assigned as follows : LEDs U<, U<<, U>, and U>>,
f1, f2, f3 are two-coloured and light up green when the
output relays are assigned as alarm relays and tU<, tU<<,
tU>, tU>>, tf1, tf2, tf3 df/dt and ΔΘ red as tripping relays.
Definition :Definition :
Definition :Definition :
Definition :
Alarm relaysAlarm relays
Alarm relaysAlarm relays
Alarm relays are activated at pickup.
TT
TT
Tripping relaysripping relays
ripping relaysripping relays
ripping relays are only activated after elapse of the
tripping delay.
After the assignment mode has been activated, first LED
U< lights up green. Now one or several of the four output
relays can be assigned to under voltage element U< as
alarm relays. At the same time the selected alarm relays
for under voltage element 1 are indicated on the display.
Indication “1_ _ _” means that output relay 1 is assigned
to this under voltage element. When the display shows
“_ _ _”, no alarm relay is assigned to this under voltage
element. The assignment of output relays 1-4 to the
current elements can be changed by pressing <+> and
<-> push buttons. The selected assignment can be stored
by pressing push button <ENTER> and subsequent input
of the password. By pressing push button <SELECT/
RESET>, LED U< light up red. The output relays can now
be assigned to this voltage element as tripping relays.
Relays 1-4 are selected in the same way as described
before. By repeatedly pressing of the <SELECT/RESET>
push button and assignment of the relays all elements can
be assigned separately to the relays. The assignment
mode can be terminated at any time by pressing the
<SELECT/RESET> push button for some time (abt. 3 s).
Note :
zThe function of jumper J2 described in general
description “MR Digital Multifunctional Relays” does
not apply for MRN3MRN3
MRN3MRN3
MRN3. For relays without assignment
mode this jumper is used for parameter setting of
alarm relays (activation at pickup or tripping).
A form is attached to this description where the setting
requested by the customer can be filled-in. This form is
prepared for telefax transmission and can be used for
your own reference as well as for telephone queries.

1717
1717
17
Relay functionRelay function
Relay functionRelay function
Relay function Output relayOutput relay
Output relayOutput relay
Output relay Display IndicationDisplay Indication
Display IndicationDisplay Indication
Display Indication Corresponding LEDCorresponding LED
Corresponding LEDCorresponding LED
Corresponding LED
11
11
122
22
233
33
344
44
4
U< alarm X _2_ _ U<; green
tU< tripping X 1_ _ _ tU< red
U<< alarm X _2_ _ U<< green
tU<< tripping X 1_ _ _ tU<< red
U> alarm X _2_ _ U> green
tU> tripping X 1_ _ _ tU> red
U>> alarm X _2_ _ U>> green
tU>> tripping X 1_ _ _ tU>> red
f1 alarm X _ _3_ f1 green
tf1 tripping X 1_ _ _ tf1 red
f2 alarm X _ _3_ f2 green
tf2 tripping X 1_ _ _ tf2 red
f3 alarm X _ _3_ f3 green
tf3 tripping X 1_ _ _ tf3 red
ΔΘ tripping X _ _ _4 ΔΘ red
df/dt tripping X _ _ _4 df/dt red
TT
TT
Table 5.4 :able 5.4 :
able 5.4 :able 5.4 :
able 5.4 : Example of assignment matrix of the output relay (default settings).Example of assignment matrix of the output relay (default settings).
Example of assignment matrix of the output relay (default settings).Example of assignment matrix of the output relay (default settings).
Example of assignment matrix of the output relay (default settings).
5.8 Indication of measuring values
5.8.1 Measuring indication
In normal operation the following measuring values can
be displayed.
Voltages (LED L1, L2, L3 green)
zIn star connection all phase-to-neutral voltages
zIn delta connection all phase-to-phase voltages
Frequency (LED f green MRN3-1)
Vector surge (LED ΔΘ green)
Frequency gradient df/dt (LED df green;
MRN3-2MRN3-2
MRN3-2MRN3-2
MRN3-2)
Min. and max. values prior to the last reset :
zFrequency (LED f + min or f + max)
zVector surge (LED ΔΘ + min or ΔΘ + max)
zFrequency gradient (LED df + min or df + max)
5.8.2 Min./Max.- values
The MRN3MRN3
MRN3MRN3
MRN3 offers a minimum/maximum storage each for
the measuring values of the vector surge as well as the
frequency gradient. These min./max. values are mainly
used to appraise the system quality. Always the highest
and lowest values of each cycleeach cycle
each cycleeach cycle
each cycle are measured and
stored until the next reset.
Min./max. frequency measuring :
The MRN3MRN3
MRN3MRN3
MRN3 ascertains the actual frequency from each
cycle of the system voltage. These measuring values are
entered into the min./max. storage. The latest entered
min./max. values replace the previously stored values.
Dependent on the adjustment of dt and tripping delay, it
is possible that the stored min./max. values are higher
than the tripping threshold without causing a trip. The
reason for this is storage of instantaneous values.
Min./Max. measuring of the frequency gradient:
The procedure described above applies also to storage of
min./max. values of df/dt measurement. Since each
instantaneous df/dt value is stored, high values can occur
which, however, do not cause any tripping.
This can for instance happen during switching procedures
where high positive and negative df/dt values occur, but
they do not cause any tripping due to the special
measuring method.
Min./max. vector surge measuring :
The procedure described above applies also to storage of
min./max. values of vector surge measuring. Since each
instantaneous ΔΘ value is stored, also here high values
are possible which, however, do not cause any tripping.
These min./max. measurements are of great advantage
for long-time analysis of the grid quality.
As to operation :
After each reset (ref. 5.9.1) the min./max. storages are
cleared. As from this instant there is no time limit for the
min./max. storage until the next reset.
By repeatedly pressing the <SELECT/RESET> push
button, the measuring values of the min./max. storage
can be queried. The respective LEDs light up at the same
time; e.g. during minimum frequency is displayed, LEDs
“f” and “min” light up.

1818
1818
18
5.8.3 Unit of the measuring values
displayed
The measuring values can optionally be shown in the
display as a multiple of the “sec” rated value (x In) or as
primary current (A). According to this the units of the
display change as follows :
Indication asIndication as
Indication asIndication as
Indication as RangeRange
RangeRange
Range UnitUnit
UnitUnit
Unit
sec. voltage 000V - 999V V
primary voltage .000 - 999V V
1K00 - 9K99 KV
10K0 - 99K9 KV
100K - 999K KV
1M00 - 3M00 MV
TT
TT
Table 5.5 : Units of the displayable 5.5 : Units of the display
able 5.5 : Units of the displayable 5.5 : Units of the display
able 5.5 : Units of the display
5.8.4 Indication of fault data
All faults detected by the relay are indicated on the front
plate optically. For this purpose, the four LEDs (L1, L2, L3,
f) and the four function LEDs (U<, U<<, U>, U>>, f1,
f2, f3, ΔΘ and df/dt) are equipped at MRN3. Not only
fault messages are transmitted, the display also indicates
the tripped protection function. If, for example an
overcurrent occurs, first the respective phase LED will
light up. LED I> lights up at the same time. After trippiung
the LEDs are lit permanently.
5.9 Fault memory
When the relay is energized or is energized or trips, all
fault data and times are stored in a non-volatile memory
manner, The MRN3 is provided with a fault value
recorder for max. five fault occurrences. In the event of
additional trippings always the oldest data set is written
over.
For fault indication not only the trip values are recorded
but also the status of LEDs. Fault values are indicated
when push buttons <-> or <+> are pressed during
normal measuring value indication.
zNormal measuring values are selected by pressing
the <SELECT/RESET> button.
zWhen then the <-> button is pressed, the latest fault
data set is shown. By repeated pressing the <->
button the last but one fault data set is shown etc. For
indication of fault data sets abbreviations FLT1, FLT2,
FLT3, ... are displayed (FLT1 means the latest fault
data set recorded). At the same time the parameter
set active at the occurence is shown.
zBy pressing <SELECT/RESET> the fault measuring
values can be scrolled.
zBy pressing <+> it can be scrolled back to a more
recent fault data set. At first FLT8, FLT7, ... are
always displayed. When fault recording is indicated
(FLT1 etc), the LEDs flash in compliance with the
stored trip information, i.e. those LEDs which showed
a continuous light when the fault occured are now
blinking blinking to indicate that it is not a current
fault. LEDs which were blinking blinking during trip
conditions, (element had picked up) just briefly flash.
zIf the relay is still in trip condition and not yet reset
(TRIP is still displayed), no measuring values can be
shown.
zTo delete the trip store, the push button combination
<SWLWCT/RESET> and <->, has to be pressed for
about 3s. The display shows “wait.
Recorded fault data :
MeasuringMeasuring
MeasuringMeasuring
Measuring Displayed valueDisplayed value
Displayed valueDisplayed value
Displayed value Correspon-Correspon-
Correspon-Correspon-
Correspon-
ding LEDding LED
ding LEDding LED
ding LED
Voltage L1; L2; L3; L1/L2; L1; L2; L3
L2/L3; L3/L1
Frequency f; f min f max f; min; max
Frequency df df
changing rate
Vector surge DQ DQ
Time stamp
Date : Y = 99
M = 03
D = 10
Time : h = 17
m = 21
s = 14
5.9.1 Reset
All relays have the following three possibilities to reset the
display of the unit as well as the output relay at jumper
position J3=ON.
Manual Reset
zPressing the push button <SELECT/RESET> for some
time (about 3 s)
Electrical Reset
zThrough applying auxiliary voltage to C8/D8
Software Reset
zThe software reset has the same effect as the
<SELECT/RESET> push button (see also
communication protocol of RS485 interface)
The display can only be reset when the pickup is not
present anymore (otherwise “TRIP” remains in display).
During resetting of the display the parameters are not
affected.
5.9.2 Erasure of fault storage
To delete the trip store, the push button combination
<SELEC/RESET> and <-> has to be pressed for about
3s. The display shows “wait”.

1919
1919
19
6. Relay testing and commissioning
The following test instructions should help to verify the
protection relay performance before or during
commissioning of the protection system. To avoid a relay
damage and to ensure a correct relay operation, be sure
that:
zthe auxiliary power supply rating corresponds to the
auxiliary voltage on site.
zthe rated frequency and rated voltage of the relay
correspond to the plant data on site.
zthe voltage transformer circuits are connected to the
relay correctly.
zall signal circuits and output relay circuits are
connected correctly.
6.1 Power-On
Note!
Prior to switch on the auxiliary power supply, be sure that
the auxiliary supply voltage corresponds to the rated data
on the type plate.
Switch on the auxiliary power supply to the relay and
check that the message “CSPC” appears on the display
and the self supervision alarm relay (watchdog) is
energized (Contact terminals D7 and E7 closed). It may
happen that the relay is tripped because of under- voltage
condition after power-on. (The message “TRIP” on the
display and LED L1, L2, L3 and U< light up red). An
undervoltage condition has been detected after power-
on, because no input voltages are applied to the relay. In
this case:
zPress the push button <ENTER>, thus entering into
the setting mode. Now set the parameters U< and
U<< to “EXIT” to block the undervoltage functions.
After that, press the <SELECT/RESET> for app. 3 s
to reset the LEDs and “TRIP” message.
zThe undervoltage tripping after power on can also be
eliminated by applying three phase rated voltages
after power-on and reset the LED and “TRIP”
message.
zApply auxiliary voltage to the external blocking input
(Terminals E8/D8) to inhibit the undervoltage
functions (refer to 6.5) and press the <SELECT/
RESET> for app. 3 s to reset the LEDs and “TRIP”
message.
6.2 Testing the output relays
NOTE!
Prior to commencing this test, interrupt the trip circuit to
the circuit breaker if tripping is not desired.
By pressing the push button <TRIP> once, the display
shows the first part of the software version of the relay
(e.g. “D08-”). By pressing the push button <TRIP> twice,
the display shows the second part of the software version
of the relay (e.g. “4.01”). The software version should be
quoted in all correspondence. Pressing the <TRIP> button
once more, the display shows “PSW?”. Please enter the
correct password to proceed with the test. The message
“TRI?” will follow. Confirm this message by pressing the
push button <TRIP> again. All output relays should then
be activated and the self supervision alarm relay
(watchdog) be deenergized one after another with a time
interval of 1 second. Thereafter, reset all output relays
back to their normal positions by pressing the push button
<SELECT/RESET>.
6.3 Checking the set values
By repeatedly pressing the push button <SELECT>, all
relay set values may be checked. Set value modification
can be done with the push button <+><-> and
<ENTER>. For detailed information about that, please
refer to chapter 4.3 of the description “MR - Digital
Multifunctional relays”.
As relay input energizing quantities, three phase voltage
should be applied to MRN3 relay input circuits. Depending
on the system conditions and the voltage transformer
used, three voltages can be connected to the relay input
circuits with either star or delta connection. In case of a
star connection the phase-to-neutral voltage will be
applied to the voltage input circuits, while the phase-to-
phase voltageswill be connected to the voltage input
circuits in case of a delta connection. The voltage input
connection must be set as a parameter, and should
correspond with the actual voltage input connection:
Star connection : Phase-to-neutral voltages will be
measured and evaluated.
Delta connection : Phase-to-phase voltages will be
measured and evaluated.
6.4 Secondary injection test
6.4.1 Test equipment
zVoltmeter and frequency meter with class 1 or better,
zauxiliary power supply with the voltage corresponding
to the rated data on the type plate,
zthree-phase voltage supply unit with frequency
regulation (Voltage : adjustable from 0 to 2 x UN;
Frequency : adjustabe from 40 - 70 Hz),
ztimer to measure the operating time (Accuracy class
±10ms),
zswitching device and
zTest leads and tools

2020
2020
20
6.5 Example of test circuit
For testing of the MRN3MRN3
MRN3MRN3
MRN3 relay, a three phase voltage
source with adjustable voltage and frequency is required
Figure 6.1 shows an example of a three-phase test circuit
energizing the MRN3MRN3
MRN3MRN3
MRN3 relay during test. The three phase
voltages are applied to the relay in Y-connection.
For testing the vector surge function of the relay, a test
circuit which can produce phase angle change (vector
surge) is required to simulate mains failures (please refer
to chapter 6.5.6).
For testing the df/dt function of the relay, a special test
equipment is required, which produces a constant rate of
change of frequency.
6.5.1 Checking the input circuits and
measuring functions
Apply three voltages of rated value to the voltage input
circuits (terminals A3 - A8) of the relay. Check the
measured voltages, frequency and vector surge on the
display by pressing the push button <SELECT/RESET>
repeatedly. The displayed measuring voltages (shown in
Volt) are dependent on the wiring of the input voltage
converters and the set transformation ratio.
The voltages are indicated on the display in volts
At YAt Y
At YAt Y
At Y--
--
-connection:connection:
connection:connection:
connection:
zPhase-to-neutral voltages: LED L1, L2, L3
At Delta-connection:At Delta-connection:
At Delta-connection:At Delta-connection:
At Delta-connection:
zPhase-to-phase voltages: LED L1+L2, L2+L3,
L3+L1
The frequency is indicated on the display in Hz: LED f
(system frequency = 50.01Hz, Indication = 5001) The
vector surge is indicated on the display in degrees (for
MRN3-1MRN3-1
MRN3-1MRN3-1
MRN3-1): LED ΔΘ (Indication ΔΘ in °)
The rate of change of frequency (LED df) is indicated on
the display in Hz/s (for MRN3-2)
Change the voltages around the rated value and check
the measured voltages on the display. Change the system
frequency around the rated frequency and check the
measured frequency on the display.
Compare the voltage and frequency on display with the
signal on voltmeter and frequency meter. The deviation
for the voltage must not exceed 1% and for frequency <
<0.01 Hz.
By using an RMS-RMS-
RMS-RMS-
RMS-metering instrument, a greater
deviation may be observed if the test voltage contains
harmonics. Because the MRN3MRN3
MRN3MRN3
MRN3 relay measures only the
fundamental component of the input signals, the
5
E6
C6
D6
+
Blocking
input
External
Reset
E8
D8
C8
=
-
~
D9
E9
C9
L-/N
L+/L
L+/L L-/N L+/L
A7
A8
A5
A6
A4
A3
MRN1
U3E
U2E
U1E
~
~
~
L3
L2
Warning
Alarm
f
DQ df/dt
u
E7
C7
D7
D5
C5
E5
E4
C4
D4
D1
D2
C1
E1
C2
E2
Trip Signal
selfsupervision
P
G
N
Serial Interface
v
Start
+
Timer
4
L1
N
Voltage Supply
P
G
N
3
2
1
-
-
Stop
1. Variable voltage source
with frequency regulation
2. Switching device
3. Voltmeter
4. Timer
5. Relay under test
Fig. 6.1 : TFig. 6.1 : T
Fig. 6.1 : TFig. 6.1 : T
Fig. 6.1 : Test circuitest circuit
est circuitest circuit
est circuit
Table of contents
Other C&S Relay manuals
Popular Relay manuals by other brands

ABB
ABB CVE Instruction leaflet

Pilz
Pilz PNOZ X13 operating manual

Kyongbo Electric
Kyongbo Electric K-PAM 10 Series user manual

ABB
ABB REL 356 quick start guide

ABB
ABB SPAS 348 C User manual and technical description

Schweitzer Engineering Laboratories
Schweitzer Engineering Laboratories SEL-421-4 instruction manual