
4ABB Automation
Description of opera-
tion
The feeder protection relay SPAS 348 C is a
secondary relay system to be connected to the
current and voltage transformers of the network
section to be protected.
The feeder protection relay includes three pro-
tection relay modules:
two directional overcurrent relay modules SPCS
4D11 and SPCS 4D12, and one directional
earth-fault relay module type SPCS 2D26.
Directional over-
current relay mod-
ules SPCS 4D11 and
SPCS 4D12
The directional overcurrent modules SPCS
4D11 and SPCS 4D12 are intended to be used
for single-phase or two-phase directional over-
current protection. When the two directional
overcurrent modules are used together three-
phase directional overcurrent protection is
achieved.
Each module includes three overcurrent stages:
two directional stages I>, I>> and one non-
directional stage I>>>. An overcurrent stage
starts, as soon as the current on one of the phases
exceeds the setting value of the stage and, if
directional operation is selected the directional
criteria must be fulfilled. Should the stage still be
started when the operate time selected for the
stage elapses, it trips the circuit breaker by
delivering the trip signal configured.
The low-set stages I> may have a definite time or
an inverse time characteristic, whereas the high-
set stages operate according to the definite time
characteristic only. The operation of the stages
can be totally blocked by means of the configu-
ration switches.
The directional control of the relay modules is
based on measuring the phase angle between the
phase current and the opposite phase-to-phase
voltage, say, L1 and U23.
To secure a reliable relay operation at close
three-phase faults characterized by an exremely
low phase-to-phase voltage, a memory function
is implemented. At sudden loss of voltage in a
fault situation this memory function gives the
directional stage an additional 2.5 s time to
operate after a total loss of voltage (=voltage level
below 7%).
Further, if the circuit breaker is closed against a
fault, which means that the voltage does not rise
to such a level that the direction of the current
can be determined, the high-set stage I>> will
operate non-directionally.
Directional earth-
fault relay module
SPCS 2D26
The directional earth-fault relay module SPCS
2D26 has two protection stages: a low-set stage
I01> and a high-set stage I02>. The start value of
the deblocking voltage U0b> is the same for both
I01> and I02>. The protection is based on
measuring the neutral current I0, the residual
voltage U0and the phase angle between these.
An earth-fault stage starts, if the neutral current
and the residual voltage exceed the set values and
the phase angle is within the specified operating
sector ϕb±∆ϕ. When these conditions remain
fulfilled during the set operate time, the stage
provides a trip signal.
The earth-fault relay module SPCS 2D26 can
also be configured to operate as a three-stage
residual voltage relay by replacing the two neu-
tral current stages by two voltage stages. The
three residual voltage stages measure the same
voltage, but they can be given separate start
values and operate times.
Circuit-breaker
failure protection
The circuit-breaker failure protection integrated
into the relay modules SPCS 4D11, SPCS 4D12
andSPCS2D26enablesasecuredcircuitbreaker
trip system. The breaker fail function is linked
to the output relay TS1, which means that if the
local circuit breaker fails to trip, the trip signal is
rerouted directly to the upstream circuit breaker.
Note ! When the relay SPAS 348 C is wired according
to a connection diagram of this user guide, the
operation direction "forward" is the direction of
the normal load current. If the relay is to trip
when the current starts flowing in the opposite
direction to the normal load current, the opera-
tion direction "reverse" shall be selected by
means of the SGF switches.