Caroma II Series User manual

IS1393 C PAGE 1 OF 4
Electronic Flush Valve - Series II
User Manual
The Caroma Electronic Flush valve – Series II has several modes to allow the installer to configure the device,
as well as monitor its performance and assist in servicing of the product.
Please ensure that the product has been installed according to the supplied Installation Instructions.
Installation must be done in accordance with AS/NZS 3500.2
Note: All changes to the unit’s settings will be retained in the event of a power outage.
Flush Volume Setting
Default: 0.8L per Flush at 300kPa Supply Pressure.
Allow the installer to select the unit’s flush volume.
•Press & HOLD Button for 1 second to CYCLE
through the preset volumes, in the following
sequence:
0.8L (Default) 2 Flashes
1.0L 3 Flashes
1.5L 4 Flashes
2.0L 5 Flashes
0.5L 1 Flash
•The indicator LED will flash to indicate the selected
Flush Volume.
Inlet Pressure Setting
Default: 300kPa Supply Pressure
This setting will allow the installer to select the current
water supply pressure to the unit. This information is
used by the controller to determine the duration
required to achieve the preset Flush Volume.
•Press and HOLD button for 5 seconds to enter
Pressure Setting function.
•The indicator LED will activate once for 5 seconds to
acknowledge that the Pressure Setting function has
been selected.
•Release the button.
•The LED will flash to indicate the current pressure
setting:
300kPa = 1 LONG Flash; 500kPa = 2 SHORT Flashes
•Press & HOLD button for 5 seconds to CYCLE
through the two preset pressure settings;
300kPa (DEFAULT) and 500kPa.
•Release the button.
•The LED will flash to indicate the selected pressure
setting:
300kPa = 1 LONG Flash; 500kPa = 2 SHORT Flashes

IS1393 C PAGE 2 OF 4
Usage Statistics Mode
Allows the installer to identify the number of uses the
product has experienced per day during the previous
30 day period.
•Press and HOLD button for 10 seconds to
enter Usage Statistics mode.
•Whilst holding the button, the indicator LED will flash
once after 5 seconds, and then flash again at 10
seconds.
•Release the button.
•The indicator LED will activate for 2 seconds to
acknowledge that Statistics Mode has been activated.
•The indicator LED will now flash in a sequence to
indicate the number of uses the unit has experienced
during the previous 30 day period.
0-20 uses per day 1 flash
21-50 uses per day 2 flashes
51-100 uses per day 3 flashes
101-150 uses per day 4 flashes
Greater than 150 uses per day 5 flashes
Diagnostic Mode:
The controller can perform internal diagnostic checks
of the main system components and display their
current status.
•Press and HOLD button for 15 seconds to enter
Diagnostics mode.
•Whilst holding the button, the indicator LED will flash
once after 5 seconds, then again at 10 seconds and
again at 15 seconds.
•Release the button.
•The indicator LED will activate for 2 seconds to
acknowledge that Diagnostics Mode has been
activated.
•The controller will check, in the following sequence, the
status of these components:
oSolenoid
oBattery
oSensor
The controller will provide feedback for each
component by flashing the indicator LED in the
following sequence:
1 LONG flash (3 seconds) indicates component is OK.
3 SHORT flashes indicate an FAULT.

IS1393 C PAGE 3 OF 4
Setting: Usage Duration
Default: 5 seconds.
The sensor will sense urinal usage for a pre-
determined duration before sending a signal to the
flush valve. This duration can be changed if required.
Duration:
The (Default) short duration (5 seconds) should
be sufficient for most installations and can be
specified if a small amount of urine is required to
activate the valve.
A medium duration (7 seconds) can be selected
to minimise accidental flushes.
A long duration (9 seconds) can be selected in
sub optimal environmental conditions such as
small rooms without ventilation or poor drainage.
•Press and hold button for 1 second to CYCLE
through the Sensor Duration settings.
•The indicator LED will flash to confirm the current
Duration setting.
Short Duration (5 seconds): 1 Flash
Default Duration (7 seconds): 2 Flashes
Long Duration (9 seconds): 3 Flashes
Setting: Stadium Mode
Default: ENABLED.
To conserve water in HIGH FREQUENCY usage
environments (i.e.: 5 uses in less than 60 seconds),
the product will automatically switch to water
conserving “Stadium Mode”.
When in the unit has entered Stadium Mode, it will activate
a flush at regular intervals of 180 seconds, regardless of
the number of uses it receives during this period.
If there is no further use within a period of 180 seconds,
the unit will automatically switch back to its Default
operation.
•Press and HOLD button for 5 seconds to set
the STATUS of Stadium Mode.
•The indicator LED will indicate that current status for
Stadium Mode:
ENABLED (1 LONG flash) or
DISABLED (2 SHORT flashes).

IS1393 C PAGE 4 OF 4
“Smart Flush” Mode
Default: DISABLED.
A new water saving mode “Smart Flush” is available
to minimise the product’s water usage.
During normal use (i.e.: a minimum of 10 minutes
between uses) the water will flush after every use.
With Smart Flush mode enabled, the unit will monitor the
use of the urinal. If the unit detects a higher usage rate
during the period, the unit will:
On the next immediate use, activate a flush.
Any subsequent use within a 10 minute period,
activate a flush.
Then, if no further flushes occur after 10 minutes,
a flush will only be activated after 1 hour or 20
uses (whichever comes first).
•“Smart Flush” mode can be manually ENABLED or
DISABLED by pressing and holding the button
for 10 seconds. The indicator LED will flash at 5
seconds, and again at 10 seconds.
•Release the button.
•The indicator LED will indicate confirm that the
“Smart Flush” Mode is: ENABLED (1 LONG flash) or
DISABLED (2 SHORT Flashes).
RESET : Factory Default Settings
This function will restore the unit to the factory preset
defaults.
•Press & HOLD both buttons i.e.: +
SIMULTANEOUSLY for 5 seconds.
•The LED will flash once.
•Release the buttons.
•The indicator LED will flash 2 times to acknowledge
that the unit has been reset to the default settings.
Default Settings:
Flush Volume: 0.8 l/flush
Inlet Pressure: 300 kPa
Usage Duration: Short (5 seconds)
Stadium Mode: ENABLED
Smart Flush Mode: DISABLED