
13
Step 2 — Check Unit
Upon receipt of shipment at the jobsite, carefully check the ship-
ment against the bill of lading. Make sure all units have been
received. Inspect the carton or crating of each unit, and inspect
each unit for damage.
INSPECT UNIT
To prepare the unit for installation, complete the procedures listed
below:
1. Verify that the correct unit has been received. Check the
unit capacity (tonnage), voltage, orientation, and
configuration.
2. Compare the electrical data on the unit nameplate with to ver-
ify the jobsite power feed (voltage, amperage, MCA) and
power protection (MOCP).
3. Verify that the unit is the correct model for the entering water
temperature of the job (standard or extended range).
4. Remove the unit packaging, keeping the unit attached to the
shipping pallet. Do not destroy packaging. Save for re-
installation on the unit if the unit will not be fully installed.
5. Open a unit access panel. Verify that the refrigerant tubing is
free of kinks or dents, and that it does not touch other unit
components.
6. Check the water piping and piping connections to make sure
they are free from defects, kinks, dents, and appear to be
water tight. Verify system operating water pressure.
7. Inspect the blower assembly. Verify that the blower has not
come loose during shipping. Verify clearance between the
blower wheel and the blower housing. Verify free blower
rotation.
8. Inspect all electrical connections. Be sure connections are
clean and tight at the terminals.
9. Check unit controls. If Complete C, or Deluxe D, verify field
provided thermostat or DDC control is available. If WSHP
Open, verify proper sensors have been provided and a com-
missioning interface will be available.
10. 50HQP Only - Locate the hanging bracket kit located in the
compressor compartment.
11. 50HQP Only - Horizontal units ordered with a VFD will be
provided with the VFD shipped loose for field installation.
The unit will ship with the VFD secured to the top of the unit
(see Fig. 1). The VFD is provided in a VFD enclosure along
with the VFD manufacturers installation manual. Inspect for
shipping damage prior to installation of the VFD. See Step 8
“Wire Field Power Supply” on page 18 for field wiring
instructions.
NOTE: Any work required to gain full access to the unit for repair
or service is not covered under the scope of the product warranty.
Step 3 — Locate Unit
• Locate the unit in an indoor area that allows easy removal
of the filter and access panels, and has enough room for
service personnel to perform maintenance or repair.
• Provide sufficient room to make fluid, electrical, and duct
connection(s).
• If the unit is located in a confined space such as a closet, pro-
visions must be made for return air to freely enter the space.
• Unit condensate drains are not internally trapped. Allow
room below the unit base for horizontal models for an ade-
quate condensate trap.
• Horizontal units include two condensate drain connections
to allow flexibility in unit sloping for proper drainage.
Only one connection needs to be used. The unused connec-
tion must be plugged.
• These units are not approved for outdoor installation; there-
fore, they must be installed inside the structure being condi-
tioned. Do not locate units in areas that are subject to freezing.
• Units must be installed in conditioned space that is not
subject to extremes of temperature or humidity to avoid
cabinet sweating and/or equipment damage.
• Do not use units for temporary heating, air conditioning or
ventilation during construction or remodeling, especially
when plastering, sanding or painting or when replacing
carpet or flooring. Dust and debris can clog the coil and
blower. Chemical vapors can lead to formicary corrosion
and damage the coil. Ensure adequate ventilation and de-
bris collection during construction or remodeling.
PROTECTION
Once the units are properly positioned on the jobsite, cover them
with either a shipping carton, vinyl film, or an equivalent protec-
tive covering. Cap open ends of pipes stored on the jobsite. This
precaution is especially important in areas where painting, plaster-
ing, or spraying of fireproof material, etc. is not yet complete. For-
eign material that accumulates within the units can prevent proper
start-up and require costly clean-up operations. Before installing
any of the system components, be sure to examine each pipe, fit-
ting, and valve, and remove any dirt or foreign material found in
or on these components.
TAKE APART CONSTRUCTION ASSEMBLY
Vertical units ordered with the take apart construction option will
be constructed in a manner that allows for field splitting of the unit
for ease of installation and rigging. The units are split into an air
coil/fan section and a water coil/compressor section.
These units will ship as an assembled single piece with pre-cut
interconnecting piping (including WSE piping if equipped) and
coiled up blower motor wiring to be installed in the field. Wiring
and interconnecting piping can be found in the air coil/fan section.
Each section will be factory charged with nitrogen. Refrigerant
must be provided and charged in the field per the unit's data plate
(See Table 1). See take apart construction dimensional drawing for
size and weights of the two sections.
DISASSEMBLY INSTRUCTION
The unit can be taken apart by removing the 4 brackets located on
the corner posts between the two sections. See Fig. 10.
ASSEMBLY INSTRUCTION
1. Locate the precut interconnecting piping and coiled blower
wiring in the air coil/fan section of the unit.
2. Connect the blower motor wiring labeled 1, 2, 3. For units
without a VFD the wiring to be connected in the field is the
wiring from the blower to be connected to the Blower Relay
(BR) terminals labeled T1, T2, T3. For units with a VFD the
wiring to be connected in the field is the wiring from the VFD
CAUTION
Failure to remove shipping brackets from spring-mounted
compressors will cause excessive noise and could cause
component failure due to added vibration.
IMPORTANT: Care must be taken to prevent the introduction of
dust, paint, debris, or chemicals into the unit, which can cause
damage to the unit, delay start-up, and may impact unit
longevity.