Miniature Low Pressure Transmitter
Installation and Operation
#NSA-HH/MLP2-001-W-U-A-A-0P-C, NSA-HH/MLP2-002-W-U-A-A-0P-C, NSA-HH/MLP2-003-W-U-A-A-0P-C
NSA-HH/MLP2-004-W-U-A-A-0P-C, NSA-HH/MLP2-005-W-U-A-A-0P-C, NSA-HH/MLP2-010-W-U-A-A-0P-C
NSA-HH/MLP2-2D5-W-U-A-A-0P-C, NSA-HH/MLP2-D10-W-U-A-A-0P-C, NSA-HH/MLP2-D25-W-U-A-A-0P-C, NSA-HH/MLP2-D50-W-U-A-A-0P-C –11/14/2019
Specifications subject to change without notice.
Catalog No. 11-808-764-01 Page 1of 4
Overview
The Miniature Low Pressure Transmitter (MLP2) Series Low Differential Pressure transmitters are
designed for use in OEM or high density panel mounting applications. Key installation features include
an integral 35 mm Din rail mounting foot, vertically orientated wiring and pressure connections, and a
pushbutton zero function conveniently located on the front cover. The MLP2 incorporates a high
accuracy, piezoresistive, silicon sensing element which senses differential pressure and provides a
linear 4 to 20 mA or DC voltage output equal to the specified pressure range. This technology reduces
warmup shift while also reducing the effect of package stress for increased long term stability. In
addition, the unit contains a de-pluggable terminal block that can be removed for ease of installation.
This unit must be ordered with a single uni or bi-directional pressure range and output signal from +/-
0.1” of water column to a maximum pressure of +/- 40” of water column depending on your application.
All MLP2 Series pressure transmitters are calibrated using NIST Certified equipment. Optional 3 or 5
point NIST Certificates are available and must be specified when placing your order.
Applications: Building and Duct Static Pressure, Filter Monitoring, Air Flow Measurement, Process
Control, Roof Top Units, Air Handlers, Clean Rooms, Isolation Rooms, Data Centers
Part Numbers
NSA-HH/MLP2-001-W-U-A-A-0P-C NSA-HH/MLP2-002-W-U-A-A-0P-C NSA-HH/MLP2-003-W-U-A-A-0P-C
NSA-HH/MLP2-004-W-U-A-A-0P-C NSA-HH/MLP2-005-W-U-A-A-0P-C NSA-HH/MLP2-010-W-U-A-A-0P-C
NSA-HH/MLP2-2D5-W-U-A-A-0P-C NSA-HH/MLP2-D10-W-U-A-A-0P-C NSA-HH/MLP2-D25-W-U-A-A-0P-C
NSA-HH/MLP2-D50-W-U-A-A-0P-C
Specifications
0-5 VDC Output: +12-36 VDC | 0-10 VDC Output: +16-36 VDC
4-20 mA Output: +16-36 VDC (250 Ohm Load) | +21-36 VDC (500 Ohm Load)
Supply Current mA (Power
Consumption):
4-20 mA Output: 23 mA minimum (0.83 VA)
VDC Output Signals: 5 mA maximum (0.18 VA)
4-20 mA: 2-wire Loop Powered (output limited to 20.5 mA maximum)
4-20 mA: 3-Wire, VAC Powered (output limited to 20.5 mA maximum)
0-5 VDC or 0-10 VDC: 3-Wire, VAC or VDC Powered (output limited to 5.25 & 10.25
VDC)
D10 = 0.10 | D25 = 0.25 | D50 = 0.50 | 001 = 1.00 | 002 = 2.00 | 2D5 = 2.50
003 = 3.00 | 004 = 4.00 | 005 = 5.00 | 010 = 10.00
+/- 0.5% FSO (Default) | +/- 0.25% (Optional) for all ranges except 0.1” and +/- 0.1“ wc
Sensor Compensated Temp Range:
+/- 0.056% FSO/ºF (+/- 0.10% FSO/ºC)
Pushbutton Zero Function (Recommended after 15 minutes warm up)
Proof Pressure | Burst Pressure:
Ranges < 1” wc (248.84 pa): Proof: 270” wc (67.2 kPa) | Burst: 415” wc (103.3 kPa)
Ranges > 1” wc (0.2488 kPa) to < 10” wc (2.488 kPa): Proof: 350” wc (87.12 kPa) |
Burst: 550” wc (136.9 kPa)
Ranges > 10” wc (2.488 kPa) to < 40” wc (9953.6 kPa): Proof: 562” wc (140 kPa) |
Burst: 1004.7” wc (250 kPa)
Operating Temperature | Humidity:
32 to 185ºF (0 to 85ºC) | 10 to 95% RH, non-condensing
Storage Temperature | Humidity:
-40 to 176ºF (-40 to 80ºC) | 10 to 95% RH, non-condensing
Intended for use with non-corrosive, non-ionic gases, such as air and other dry gases
Enclosure Material | Flammability
Rating:
Polycarbonate | UL 94 V-0