
IOM-P1
2
SECTION IV
IV. STARTUP
SECTION V
V. SHUTDOWN
SECTION III
III. PRINCIPLE OF OPERATION
1. Movement occurs as pressure variations register
on the diaphragm (7.1). The registering pressure
is the outlet, P2, or downstream pressure. The
range spring (15) opposes diaphragm move-
ment. As outlet pressure drops, the range spring
pushes the diaphragm (7.1) down, opening the
port; as outlet pressure increases, the diaphragm
(7.1) pushes up and the port opening closes.
2. A complete diaphragm (7.1) failure will cause the
regulator to fail open.
The maximum outlet pressure is stamped on the
body as the upper range spring pressure level, and
is the recommended “upper operative limit” for the
sensing diaphragm (see Section IV. Startup, Step 7).
Higher pressures could damage the diaphragm. (Field
hydrostatic tests frequently destroy diaphragms. DO
NOT HYDROSTATIC TEST THROUGH AN INSTALLED
UNIT; ISOLATE FROM TEST.)
CAUTION
1. Start with the block valves closed. A bypass
valve may be used to maintain outlet pressure
in the downstream system without changing the
following steps.
2. Relax the range spring (15) by turning knob (4)
counter clockwise (CCW) until rotation comes to
a complete stop.
3. If it is a “hot” piping system, and equipped with
a bypass valve, slowly open the bypass valve
to preheat the system piping and to allow slow
expansion of the piping. Closely monitor outlet
(downstream) pressure via gauge to ensure not
over-pressurizing. NOTE: If no bypass valve is
installed, extra caution should be used in starting
up a cold system; i.e. do everything slowly.
4. Crack open the outlet (downstream) block valve.
5. Slowly open the inlet (upstream) block valve ob-
serving the outlet (downstream) pressure gauge.
Determine if the regulator is flowing. If not, slowly
rotate knob (4) clockwise (CW) until flow begins.
6. Continue to slowly open the inlet (upstream) block
valve until fully open.
7. Continue to slowly open the outlet (downstream)
block valve, especially when the downstream pip-
ing system isn't pressurized. If the outlet (down-
stream) pressure exceeds the desired pressure,
close the block valve and go to Step 2, then return
to Step 4.
8. When flow is established steady enough that the
outlet (downstream) block valve is fully open,
begin to slowly close the bypass valve if installed.
9. Develop system flow to a level near its expected
normal rate, and reset the regulator set point by
turning knob (4) CW to increase outlet pressure,
or CCW to reduce outlet pressure.
10. Reduce system flow to a minimum level and
observe set point. Outlet pressure will rise from
the set point of Step 9. The maximum rise in
outlet pressure on decreasing flow should not
exceed the stated upper limit of the range spring
by greater than 10%. Example: with 2-100 psig
(.14-6.9 Barg) range spring at low flow the outlet
pressure should not exceed 110 psig (7.6 Barg),
if it does, consult factory.
Do not walk away and leave a bypassed
regulator unattended.
CAUTION
1. On systems with a bypass valve, and where sys-
tem pressure is to be maintained as the regulator
is shut down, slowly open the bypass valve while
closing the inlet (upstream) block valve. Fully
close the inlet (upstream) block valve. (When on
bypass, the system pressure must be constantly
observed and manually regulated. Close the
outlet (downstream) block valve.
2. If the regulator and system are to both be shut
down, slowly close the inlet (upstream) block
valve. Close the outlet (downstream) valve only
if regulator removal is required.