CentraLine EAGLEHAWK NX Operation manual

EAGLEHAWK NX Controller Product Data
® U.S. Registered Trademark
Copyright © 2019 Honeywell Inc. • All Rights Reserved EN0Z-1039GE51 R0319
GENERAL
EAGLEHAWK NX is a BACnet-compliant heating, ventilation,
air conditioning (HVAC) building controller.
It runs the CentraLine Niagara NX framework, integrating all
trades in a building.
Thus, EAGLEHAWK NX is the ideal solution for HVAC con-
trols requiring combination with lighting, shading, access
control, and security applications.
It provides unparalleled energy efficiency through the use of a
vast HVAC Application Library.
EAGLEHAWK NX enables uniform graphical operation, con-
trol, data logging, alarming, scheduling, and network man-
agement functions for HVAC and non-HVAC applications.
Through its integrated web server, it allows real-time access
to all information through web-based graphical views.
EAGLEHAWK NX supports full remote engineering, including
changes to the control program and the graphical user inter-
face. This greatly supports reduction of life cycle and
maintenance cost.
OPERATION IN IP NETWORKS
When operating EAGLEHAWK NX in IP networks, either
private (e.g., VPN) networks must be used or protection
against the open Internet (e.g., by means of external firewalls)
must be ensured. See "Network Security" on pg. 6.
3RD-PARTY SOFTWARE LICENSES
This product contains software provided by third parties. See
also EAGLEHAWK NX Controller – Third-Party Software
Licenses (Product Literature No.: EN2Z-1041GE51).
FEATURES
Reduced total installed cost: Existing standard Ether-
net/LAN infrastructure is used for communication between
EAGLEHAWK NX controllers, 3rd-party BACnet® con-
trollers, and BACnet® front-ends. Costs are further re-
duced by the flexible and optional use of Panel Bus I/Os
(which allow manual override independent of the controller,
thus obviating the need for external switches) and of
onboard I/Os.
Panel Bus I/Os allow for wiring lengths of up to 800 m, thus
obviating the need to lay wire from field devices all the way
back to the controller.
Reduced life cycle cost: EAGLEHAWK NX supports the
highly reliable CentraLine Panel Bus I/O modules, which
allow for plugging and replacing without any need for re-
wiring or engineering, thus minimizing system down-time.
The Panel Bus is polarity-insensitive, thus reducing poten-
tial wiring errors. Furthermore, Panel Bus I/O modules
allow the predefinition of output safety positions, ensuring
safe operation even if communication with EAGLEHAWK
NX is disrupted.
Universal operation: Via Internet browser, EAGLEHAWK
NX can be operated from any place, from any PC and/or
mobile device connected to the (EAGLEHAWK NX) net-
work! (Optionally, via the onboard or detached HMI, the
controller can be operated independently of any network
connection.)
Vendor independence: Multiple international communi-
cation standards are supported, e.g.: BACnet/IP (ISO
16484-5); BACnet MS/TP (ISO 16484-5); LONWORKS (ISO
14908); Modbus RTU and Modbus TCP; M-Bus (EN 1434-
3); oBIX; SNMP; etc.
Trending: Datapoints can be trended and historical values
stored and viewed.
Reliable control performance: Embedded QNX ensures
reliable, independent, and secure operation, especially for
systems with Internet access.
Embedded e-mail alarming: Configurable e-mail
alarming options allow alarms to be sent (via network or
Internet-DSL connection) to e-mail accounts and thus also
to mobile device using SMTP protocol.
Optional SMS alarming: SMS alarming via GSM modem
using the optional SMS driver.
CentraLine application library: Enables highly-effective
application generation for optimal energy-efficient control
applications.
Flexible mounting options: Mounting onto wall or onto
panel back wall, into panel door, onto panel rail, and into
sub-panels (fuse boxes).
Direct 24 VAC power supply: No batteries, no movable
parts – thus does not require regular maintenance.

EAGLEHAWK NX CONTROLLER – PRODUCT DATA
EN0Z-1039GE51 R0319 2
OPERATOR INTERFACE
EAGLEHAWK NX is operated via a standard browser. By
default, an integrated web-server provides all freely pro-
grammable operation pages for full browser-based operation.
Operating devices can be laptops, desktops PCs, or touch
screen PCs for direct flush mounting into electrical panel
doors (IP65).
Fig. 1. EAGLEHAWK NX PC homepage (example)
For mobile devices, there is a separate corresponding
operator interface.
Fig. 2. EAGLEHAWK NX mobile device homepage
(example)
For network-independent operation, the EAGLEHAWK NX
can be operated either via its onboard HMI (option 1) or via
an external HMI (option 2) connected to the dedicated HMI
port of those models not equipped with an onboard HMI.
The operating menu can be customized to suit the building
operator's needs.
Fig. 3. CLEAHMI21 External HMI
Programming
EAGLEHAWK NX is freely programmable using the graphic
COACH NX Engineering Tool and is thus ideal for all Inte-
gration, Building Control, and Building Management tasks.
Password Protection
EAGLEHAWK NX allows the definition of a large number of
user levels with defined read and write rights. Several users
with individual passwords can be defined for each user level.
And different views can be assigned to the individual users.
COMMUNICATION PROTOCOLS
BACnet/IP – ISO 16484-5 and EN 13321-1
Communication with other EAGLEHAWK NX and EAGLE
controllers, 3rd-party BACnet devices and ARENA NX Super-
visors is possible.
EAGLEHAWK NX conforms to the BACnet Building Controller
(B-BC) profile. For details, see Protocol Implementation
Conformance Statement (PICS) (Product Literature No.:
EN0Z-1042GE51).
BACnet MS/TP – ISO 16484-5 and EN 13321-1
Communication with other BACnet controllers is based on the
international BACnet Protocol. Optionally, one or both of the
onboard RS485 interfaces can be used for communication via
BACnet MS/TP.
LonTalk® - ISO 14908
Optionally, communication with physical I/O modules, with
room and zone controllers, and with CentraLine PANTHER,
TIGER, and LION controllers can utilize LonTalk.
LONWORKS communication requires the IF-LON2 LONWORKS
interface.
Modbus
Optionally, the two onboard RS485 interfaces can be used
(even simultaneously) for communication via Modbus RTU.
Modbus TCP communication is supported via the two on-
board Ethernet RJ45 interfaces. See also EAGLEHAWK NX –
Installation & Commissioning Instructions (Product Literature
No.: EN1Z-1039GE51) for details.
M-Bus – EN 1434-3
Optionally, M-Bus communication is possible via the onboard
RS232 interface. See also EAGLEHAWK NX – Installation &
Commissioning Instructions (Product Literature No.: EN1Z-
1039GE51) for details.
Panel Bus
Optionally, one or both of the onboard RS485 interfaces can
be used for Panel Bus communication with CentraLine Panel
Bus I/O modules.
Up to 64 Panel Bus I/O modules can be operated via each
RS485 interface, thus permitting 1,000+ Panel Bus / onboard
I/O points (see Table 5 on pg. 10 for information on
upgrades).

EAGLEHAWK NX CONTROLLER – PRODUCT DATA
EN0Z-1039GE51 R0319
3
HTTPS
Secure web browser communication is supported for web
access via standard web browsers.
SMTP
Simple Mail Transfer Protocol is used for e-mail alarming via
network and Internet-DSL connection.
Open Niagara Drivers
Optionally, all available interfaces can also be used with any
open Niagara driver. For example: KNX driver can be used
via the TCP/IP – KNX interface.

EAGLEHAWK NX CONTROLLER – PRODUCT DATA
EN0Z-1039GE51 R0319 4
BUS AND PORT CONNECTIONS
WARNING
Risk of electric shock or equipment damage!
► Do not touch any live parts in the cabinet!
► Disconnect the power supply before making connections
to or removing connections from terminals of the
EAGLEHAWK NX controller or Panel Bus I/O modules.
► Do not reconnect the power supply until you have com-
pleted installation.
► Due to the risk of short-circuiting (see Fig. 9), it is strongly
recommended that the EAGLEHAWK NX controller be
supplied with power from a dedicated transformer. How-
ever, if the EAGLEHAWK NX controller is to be supplied
by the same transformer powering other controllers or
devices (e.g., the PW M-Bus Adapter), care must be
taken to ensure that correct polarity is observed.
► Observe the rules regarding electrostatic discharge.
24V-0
24V~
1
7 8
2
9
DO1
DO2
DO3
IN
IN4
DO4
DO5
IN5
IN6
DO6
DO7
IN7
IN8
DO8
GND
AO1
AO2
AO3
5 6 7 8 9 10 1112131415161718 19202122
AO4
23
24 25 26 27 28 29 30 31 32
56
GND1
485-1+
485-1-
n.a.
n.a.
GND2
485-2+
485-2-
n.a.
1 2 3 4
RS232
RS485-1
END
BIAS
MID
BI1
BI2
BI3
BI4
GND
UI1
UI2
UI3
UI4
UI5
UI6
UI7
33 34 35 36 37 38 39 40 41 42 43 44 45 46
UI8
47
UI9
UI10
21
Fig. 4. Top view (with HMI and full complement of
onboard I/Os)
1 2
END
BIAS
MID
4
3
Fig. 5. Side view
Legend
1 RS232 / RJ45 socket (for connection of M-Bus and
other RS232-based protocols; factory debugging)
2 Three-position slide switch (for setting bias and
termination resistance of RS485-1)
3 Two Ethernet / RJ45 sockets (for BACnet IP com-
munication); 10/100 Mbit/s; 1 "link" LED + 1 "activity"
LED
4 USB 2.0 Host Interface (for connection of IF-LON2);
max. 200 mA, high speed
5 RS485-1* (isolated; for BACnet MS/TP, Panel Bus,
Modbus RTU communication, etc.)
6 RS485-2* (non-isolated; for BACnet MS/TP, Panel
Bus, Modbus RTU communication, etc.)
7 LEDs
8 USB 2.0 Device Interface (for connection to COACH
NX web browsers, and 3rd-party touch panels)
9 HMI (or RJ45 socket for connection of portable HMI)
*Modbus RTU Master/Slave communication is possible on the
two RS485 interfaces.
WARNING
Risk of electric shock or equipment damage!
► It is prohibited to connect any of the RJ45 sockets of the
EAGLEHAWK NX controller to a so-called PoE-enabled
device ("Power over Ethernet").
M-Bus Connection
The EAGLEHAWK NX controller supports M-Bus Master
functionality via its onboard RS232 / RJ45 socket. It uses
standard PW3/PW20/PW60 converters to connect to the M-
Bus devices.
Wiring Topology
Max. bus length is 350 meters. M-Bus devices are connected
to the bus cable in parallel.
EAGLEHAWK NX
SLAVE 1 SLAVE 2 SLAVE 3
PW
CONVERTER
Fig. 6. Allowed M-Bus wiring topology
Cables
See section "M-Bus Connection" in EAGLEHAWK NX Con-
troller – Installation & Commissioning Instructions (EN1Z-
1039GE51).
Use shielded, twisted pair cable J-Y-(St)-Y 2 x 2 x 0,8.
Shielding
Shielding is especially recommended when the M-Bus cable
is installed in areas with expected or actual electromagnetic
noise. Avoiding such areas is to be preferred.
Use shielded, twisted pair cable J-Y-(St)-Y 2 x 2 x 0,8 and
connect the shield to a noise-free earth ground – only once
per M-Bus connection.

EAGLEHAWK NX CONTROLLER – PRODUCT DATA
EN0Z-1039GE51 R0319
5
M-Bus Repeaters
The M-Bus can be extended to 1,000 meters, depending on
the communication rate, and provided that the electrical limi-
tations are observed. For details refer to the EAGLEHAWK
NX Controller – Installation & Commissioning Instructions
(EN1Z-1039GE51).
For bus length extension, M-Bus repeaters can be used, but
have not been tested by Honeywell. Hence, it is the
responsibility of the installing / commissioning personnel to
ensure proper functioning.
M-Bus Master Specifications
For a detailed description of the M-Bus functionality, please
refer to the M-Bus Online Help.
Physical Layer
RS232 to PW3/PW20/PW60
Physical connector: RS232 / RJ45 socket (see Fig. 5)
Cable order number: XW586
Communication rates: 300, 2,400, and 9,600 bps are
supported, individually per M-Bus
slave.
Max. no. of devices: 60 (excluding the EAGLEHAWK NX
controller)
Cable and wiring specifications: See EAGLEHAWK NX –
Installation & Commissioning Instructions (EN1Z-1039GE51).
Address Range
M-Bus slaves can have a primary address between 1 and
250.
Measurement Cycle
Individually per M-Bus slave, the measurement cycle can be
configured from 1 to 604,800 sec (i.e., 1 second to 7 days).
Modbus Connection
The EAGLEHAWK NX controller can function as a Modbus
Master/Slave.
For Modbus RTU, the RS485 wiring rules must be followed.
Wiring Topology
Only daisy-chain wiring topology is allowed.
MODBUS
MASTER
MODBUS
SLAVE
MODBUS
SLAVE
MODBUS
SLAVE
MODBUS
SLAVE
Fig. 7. Allowed Modbus wiring topology
Other wiring topologies (e.g., star wiring, or mixed star wiring
and daisy chain wiring) are prohibited; this is to avoid com-
munication problems of the physical layer.
MODBUS
MASTER
MODBUS
SLAVE
MODBUS
SLAVE
MODBUS
SLAVE
MODBUS
SLAVE
MODBUS
SLAVE
MODBUS
SLAVE
Fig. 8. Prohibited Modbus wiring topology (example)
Cables
See section "EIA 485 Cable Specifications" in EAGLEHAWK
NX Controller – Installation & Commissioning Instructions
(EN1Z-1039GE51).
Use shielded, twisted pair cable J-Y-(St)-Y 2 x 2 x 0,8.
You must use three wires:
One wire for D1 = Modbus +
One wire for D0 = Modbus –
One wire for the signal common
When using one pair for D1 and D0 and one wire of another
pair for the signal common, CAT5 cable may also be used.
For connection details, see EAGLEHAWK NX Controller –
Installation & Commissioning Instructions (EN1Z-1039GE51).
Shielding
Shielding is especially recommended when the Modbus cable
is installed in areas with expected or actual electromagnetic
noise. Avoiding such areas is to be preferred.
Use shielded, twisted pair cable J-Y-(St)-Y 2 x 2 x 0,8 and
connect the shield to a noise-free earth ground – only once
per Modbus connection.
RS485 Repeaters
RS485 repeaters are possible, but have not been tested by
Honeywell. Hence, it is the responsibility of the installing /
commissioning personnel to ensure proper functioning.
NOTE: Each Modbus segment requires its own line
polarization and line termination.
Modbus Specifications
For Modbus RTU and TCP specifications, please refer to the
COACH AX document entitled Niagara AX-3.x Modbus
Guide.

EAGLEHAWK NX CONTROLLER – PRODUCT DATA
EN0Z-1039GE51 R0319 6
WARNING
NETWORK SECURITY
Honeywell hereby expressly states that the EAGLEHAWK NX
is not inherently protected against cyber attacks from the
Internet and that it is therefore intended solely for use in
private, protected networks.
Unprotected Internet connections can expose the controller to
cyber attacks from third parties who can then damage it and
connected facility components or cause them to malfunction,
or who can misuse it for illegal purposes for which the
operator may then be held liable.
When directly connected to the Internet, the EAGLEHAWK
NX automatically becomes a potential target for cyber attacks.
Corresponding protective measures are therefore essential if
safe and reliable operation is to be ensured.
If it is not necessary for the EAGLEHAWK NX to be
accessible from the Internet, the EAGLEHAWK NX should be
isolated from the Internet via a suitable firewall.
If it is necessary for the EAGLEHAWK NX to be accessible
from the Internet (e.g., in order to perform remote main-
tenance), the use of a coded VPN connection is
indispensable. Suitable VPN routers are available from
numerous third-party manufacturers in a wide variety of
designs, for operation at 230 V or 24 V.
CONTROLLER SPECIFICATIONS
General
Table 1. Controller specifications
Ambient temperature 0 … 40 °C (wall-mounting)
0 … 50 °C (cabinet/door mounting)
Storage temperature -20 … +70 °C
Humidity 5 … 95% r.h. non-condensing
Dimensions See Fig. 10 and Fig. 11.
Degree of protection
IP20 (mounted on walls, with two
accessory MVC-80-AC1 covers)
IP30 (mounted in cabinet doors,
with accessory MVC-80-AC2)
Fire class V0
Shock protection Class II
Pollution degree 2
Installation Class 3
Rated impulse
voltage
330 V for SELV, 2500 V for relay
outputs
Overvoltage category II
Automatic action Type 1.C
Software class Class A
Ball-pressure test
temperature
housing parts >75°C
terminals >125°C
Electrical Data
Table 2. Electrical data
Power supply 19 … 29 VAC, 50/60 Hz, or
20 … 30 VDC
Power
consumption
typically DC: 7 W; max. 9 W
typically AC: 10 VA; max. 12 VA
Heat dissipation Max. 9 W at DC power supply
max. 9 W at AC power supply
Current
consumption
typically DC: 300 mA; max. 375 mA
typically AC: 400 mA; max. 500 mA
Due to the risk of short-circuiting (see Fig. 9), it is strongly
recommended that the EAGLEHAWK NX controller be
supplied with power from a dedicated transformer. However, if
the EAGLEHAWK NX controller is to be supplied by the same
transformer powering other controllers or devices (e.g., the
PW M-Bus Adapter), care must be taken to ensure that
correct polarity is observed.
24 V~
24 V~0
LINE
L
N
CPU 1 CPU 2
NOISE-FREE EARTH GROUND
(ONLY ONE PER SYSTEM)
N, L
EARTH GROUND
USB 2.0
Device Interface
!
REVERSED
POLARITY!
PC 1 PC 2
2 21 1
24V~ 24V~
24V~0 24V~0
SHORT-CIRCUITING!
Fig. 9. Incorrect polarity → SHORT-CIRCUITING!
Mechanical Data
Housing Dimensions (L x B x T): 215.5 x 110 x 61 mm
Housing Material: ABS blend; flame retardant V0
Weight: 400 g (without packaging)
Protection Class: IP 20

EAGLEHAWK NX CONTROLLER – PRODUCT DATA
EN0Z-1039GE51 R0319
7
CPU
Processor
NXP i.MX 6SoloX 32-bit dual core processor with 1 GHz
Arm® Cortex®-A9 core and 227 MHz Arm Cortex-M4 core
Operating System
QNX
Memory
1 GB DDR3-RAM
512 KB MRAM
4 GB Flash Memory
Real-Time Clock
accuracy: ± 2 minutes per year (at, typically, 25 °C)
buffered typically for 72 h by gold capacitor
Standards, Approvals, etc.
Device meets EN 60730-1, EN 60730-2-9, UL60730, and
UL916.
The device complies with Ethernet Protocol versions
IEEEC 802.3.
The device supports BACnet IP and BACnet MS/TP
communications as per ANSI / ASHRAE 135-2012.
Mounting
The EAGLEHAWK NX controller is suitable for mounting as
follows:
► in cabinets;
► in fuse boxes conforming with standard DIN43880, and
having a slot height of max. 45 mm;
► on walls (using accessory MVC-80-AC1 covers);
► in cabinet front doors (using accessory MVC-80-AC2).

EAGLEHAWK NX CONTROLLER – PRODUCT DATA
EN0Z-1039GE51 R1018
8
Extra Parts
Table 3. Extra parts
order no. description
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9
XS830
Set of ten terminals. Each package consists of two groups of
nine internally connected push-in terminals, for distributing
signals / power.
A1 B1 A2 B2 A3 B3 A4 B4 G1 G2A5 B5 A6 B6 A7 B7 A8 B8
XS831
Set of ten terminals. Each package consists of two groups of
four pairs of push-in terminals (each with a 499 Ω resistor), for
converting 0…20 mA signals into 0…10 VDC signals, and one
push-in ground terminal per group.
TPU-11-01 Removable terminal plugs, push-in type; complete set of 3
plugs (for terminals 1, 2, 24-32); for the CLNXxxx00xxx.
TPU-45-01
Removable terminal plugs, push-in type; complete set of 9
plugs (for terminals 1 - 47); for the CLNXxxx14xxx and
CLNXxxx26xxx.
MVC-80-AC1 Terminal cover (color: RAL9011); package of ten.
MVC-80-AC2 Front door mounting accessory (color: RAL9011); package of
ten.
MVC-40-AC3 Strain relief; package of ten.

EAGLEHAWK NX CONTROLLER – PRODUCT DATA
EN0Z-1039GE51 R0319
9
MODELS
Table 4. Overview of models (hardware)
feature description
max.
cable
length
order no.
without HMI with HMI
CLNXEH00ND100A, CLNXEHSERIES00ND
CLNXEHS00ND100A
CLNXEH14ND100A, CLNXEHSERIES14ND
CLNXEHS14ND100A
CLNXEH26ND100A, CLNXEHSERIES26ND
CLNXEHS26ND100A
CLNXEH00D100A, CLNXEHSERIES00D
CLNXEHS00D100A
CLNXEH14D100A, CLNXEHSERIES14D
CLNXEHS14D100A
CLNXEH26D100A, CLNXEHSERIES26D
CLNXEHS26D100A
UI NTC10kΩ / NTC20kΩ / 0…10V / slow BI, 0.4 Hz 400 m 0 0 4 4 8 8 0 0 4 4 8 8
NTC10kΩ / NTC20kΩ / 0…10V fix pull-up / slow BI, 0.4 Hz 400 m 0 0 0 0 2 2 0 0 0 0 2 2
BI open = 24 V / closed 2.0 mA / totalizer 15 Hz 400 m 0 0 4 4 4 4 0 0 4 4 4 4
AO 0..11 V (max. 1 mA) 400 m 0 0 2 2 4 4 0 0 2 2 4 4
BO
Relay N.O. contact: 3 A, 250 VAC, 30 VDC 400 m 0 0 3 3 4 4 0 0 3 3 4 4
Relay N.O. contact (high in-rush): 10 A, 250 VAC, 30 VDC 400 m 0 0 1 1 1 1 0 0 1 1 1 1
Relay N.O. contact with one common: 3 A, 250 VAC,
30 VDC 400 m 0 0 0 0 3 3 0 0 0 0 3 3
total I/Os -- 0 0 14 14 26 26 0 0 14 14 26 26
bus
interfaces
RS485-1, isolated, BACnet MS/TP, Panel Bus, or Modbus
RTU Master or Slave communication 1)1200 m 1 2)11
2)11
2)1 1 2)1 1 2)11
2)1
RS485-2, non-isolated, BACnet MS/TP, Panel Bus, or
Modbus RTU Master or Slave communication (NOTE: It is
imperative that the RS485-2 be powered by a power supply
having the proper polarity. Failure to do so will make data
transmission impossible.)
1)1200 m 1 2)11
2)11
2)1 1 2)1 1 2)11
2)1
Ethernet Interfaces (e-mail communication, browser
access, BACnet IP communication, Niagara Network,
Modbus TCP)
100 m 2 2 2 2 2 2 2 2 2 2 2 2
USB 2.0 Device Interface (as Network Interface) 3 m 1 1 1 1 1 1 1 1 1 1 1 1
USB 2.0 Host Interface (max. 200 mA) 3 m 1 1 1 1 1 1 1 1 1 1 1 1
RS232 M-Bus communication via 15-meter-long PW3 /
PW20 / PW60 converters 1)1000 m 1 1 1 1 1 1 1 1 1 1 1 1
LEDs
power LED (green) -- 1 1 1 1 1 1 1 1 1 1 1 1
status LED (red; indicates an active alarm; is controlled by
Niagara Alarm System; is configurable) -- 1 1 1 1 1 1 1 1 1 1 1 1
LED L1 (yellow; lit = Daemon starting; flashing = station
starting; if L2 is also flashing, then the station has started) -- 1 1 1 1 1 1 1 1 1 1 1 1
LED L2 (yellow; lit = platform has started / is reachable;
flashing = station has started / is reachable) -- 1 1 1 1 1 1 1 1 1 1 1 1
bus status LEDs (for isolated RS485-1 interface) -- 2 2 2 2 2 2 2 2 2 2 2 2
1) Depending upon bit rate. However, in the case of configuration of RS485-2 for Panel Bus, the communication rate is set to
115.2 kbps, and the max. cable length is hence 800 m.
2) In the case of these devices, for Panel Bus functionality, an additional license must be purchased (see Table 5).

EAGLEHAWK NX CONTROLLER – PRODUCT DATA
EN0Z-1039GE51 R0319 10
Software Licenses and Upgrades
Table 5. Software Licenses and Upgrades
model License content / upgrade license
CLNXEH00ND100A
100 integration points + 255 Panel Bus / onboard I/O points + 1st year of Software Maintenance
Agreement
CLNXEH14ND100A
CLNXEH26ND100A
CLNXEHS00ND100A
100 integration points / onboard I/O points
CLNXEHS14ND100A
CLNXEHS26ND100A
CLNXEHSERIES00ND N/A
CLNXEHSERIES14ND N/A
CLNXEHSERIES26ND N/A
CLNXEH00D100A
100 integration points + 255 Panel Bus / onboard I/O points + 1st year of Software Maintenance
Agreement
CLNXEH14D100A
CLNXEH26D100A
CLNXEHS00D100A
100 integration points / onboard I/O points
CLNXEHS14D100A
CLNXEHS26D100A
CLNXEHSERIES00D N/A
CLNXEHSERIES14D N/A
CLNXEHSERIES26D N/A
CLNXEHPB100UP +102 Panel Bus / onboard I/O points upgrade
CLNXEHPB255UP +255 Panel Bus / onboard I/O points upgrade
CLNXEHRBAC250UP +250 Honeywell BACnet points (for BACnet room devices, e.g., MERLIN / CPO-R) upgrade
CLNXEHRLON250UP +250 Honeywell points (for LONWORKS room devices, e.g., SERVAL / Excel 10) upgrade
CLNXEH-DEVICE-UP-1 +50 open points upgrade
CLNXEH-DEVICE-UP10 +500 open points upgrade
CLNXEH-DEVICE-UP25 +1250 open points upgrade
CLNXEH-DEVICE-UP50 +2500 open points upgrade
NOTE: For more details on the licenses, please refer to the Release Bulletin.

EAGLEHAWK NX CONTROLLER – PRODUCT DATA
Manufactured for and on behalf of the Connected Building Division of Honeywell Products and Solutions SARL, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative:
CentraLine
Honeywell GmbH
Böblinger Strasse 17
71101 Schönaich, Germany
Phone +49 (0) 7031 637 845
Fax +49 (0) 7031 637 740
www.centraline.com
Subject to change without notice
EN0Z-1039GE51 R0319
DIMENSIONS
110
215.5
5245
24V-0
24V~
1 2
49.5
57.5
J1 J8
24 25 26 27 28 29 30 31 32
GND1
485-1+
485-1-
n.a.
n.a.
GND2
485-2+
485-2-
n.a.
RS232
RS485-1
END
BIAS
MID
BI1
BI2
BI3
BI4
GND
UI1
UI2
UI3
UI4
UI5
UI6
UI7
33 34 35 36 37 38 39 40 41 42 43 44 45 46
UI8
47
UI9
UI10
21
DO1
DO2
DO3
IN
IN4
DO4
DO5
IN5
IN6
DO6
DO7
IN7
IN8
DO8
5678910 1112131415161718
GND
AO1
AO2
AO3
19 20 21 22
AO4
23
Fig. 10. EAGLEHAWK NX controller (w/o HMI but with RJ45 socket for connection of portable HMI, and with full
complement of onboard I/Os), dimensions (in mm)
147
57.5
215.5
J1 J8
52
Fig. 11. EAGLEHAWK NX controller with covers, dimensions (in mm)
NOTE: Use of the covers (MVC-80-AC1) will obstruct access to the Ethernet, USB 2.0, and RS232 interfaces.
Other manuals for EAGLEHAWK NX
1
Table of contents
Other CentraLine Controllers manuals
Popular Controllers manuals by other brands

Sunlight Supply
Sunlight Supply TITAN Controls Saturn 4 instruction manual

Becker
Becker Centronic EasyControl EC513 Assembly and operating instructions

IMO Precision Controls
IMO Precision Controls i3 Tutorial

CASTLE
CASTLE Sidewinder 4 quick start guide

Epever
Epever DuoRacer Series user manual

Daiya Electronic
Daiya Electronic RTU5011 user manual