Cerberus Pyrotronics
8 Fernwood Road
Florham Park, New Jersey 07932
Installation and Programming Instructions
MODEL MSI-MB6
Manual Station
P/N 315-093613-1
Figure 1
MSI-MB6 Cover
Note:
The connection from the FPI-32 to the
MS-MI is not polarity sensitive. However,
connection from the Control Panel to
the MSI-MB6 is polarity sensitive.
3. Following the instructions given in the FPI-32
Programmer/Tester Manual (P/N 315-
090077), program the MSI-MB6 to the
desired address.
4.
Record the device address on the label located
on the MSI-MB6 housing. (See Figure 1.)
5. Distribute the manual station boxes
throughout the protected area so that they
are unobstructed, readily accessible, and
located in the normal exit path.
6. Place the manual station according to the
regulations of the authorities having
jurisdiction.
INTRODUCTION
The Cerberus Pyrotronics Manual Station
Model MSI-MB6 is an addressable device
containing advanced control panel communi-
cation technology. This technology, which
provides bidirectional communication with the
control panel, produces an Intelligent Initiating
Device. The MSI-MB6 is a single action sta-
tion; when used with the MS-DA plate, the
MSI-MB6 is a double action station.
OPERATION
The MSI-MB6 Manual Station operates with either
the MXL Control Panel or the XL3 Control Panel.
When an alarm condition occurs, pull down on
the PULL lever of the manual station. This
pushes the switch down to ALARM position.
The pull-down cover remains down and locked
until the station is reset.
The MSI-MB6 with the MS-DA plate has an
additional lever labeled LIFT PULL LEVER
which must be lifted up before access is
provided to the station PULL.
INSTALLATION
1. Locate the opening on the MSI-MB6 cover
that allows access to the programming
points on the MSI-MB6 printed circuit
board. (Refer to Figure 1.)
2. The manual station is programmed by
using the Cerberus Pyrotronics Model
FPI-32 Programmer/Tester. Connect the
MSI-MB6 to the FPI-32 by using the cable
provided with the Programmer/Tester.