
ALARM
RESET
©2011 The Chamberlain Group, Inc.
01-35589 All Rights Reserved
WIRING
FINE TUNE THE FORCE
PROGRAMMING
INITIAL LIMITS AND FORCE ADJUSTMENT
OBSTRUCTION TEST
When limits are set properly the operator will automatically exit limit setting mode.
51Press and release the SET OPEN and SET CLOSE buttons simultaneously to enter limit setting mode.
2Press and hold one of the MOVE GATE buttons to move the gate to the
open or close limit.
3Press and release the SET CLOSE or SET OPEN button
depending on which limit is being set.
4Press and hold one of the MOVE GATE button to move the
gate to the other limit.
5Press and release the SET CLOSE or SET OPEN button depending on which
limit is being set.
61Open and close the gate with the test buttons.
2If the gate stops or reverses before reaching the fully open or
closed position, increase the force by turning the force control
slightly clockwise.
7
81Press and release the LEARN
button (operator will beep
and green XMITTER LED will
light).
2Press the remote control button for the
desired function. The
operator will automatically
exit learn mode (operator
will beep and green
XMITTER LED will go out)
if programming is
successful.
6Cycle the gate open and close. This automatically sets the force.
The FORCE DIAL on the control board is used for fine tuning the force. The force setting should be high enough that
the gate will not reverse by itself nor cause nuisance interruptions, but low enough to prevent serious injury to a
person. The force setting is the same for both the open and close gate directions.
3Perform the “Obstruction Test” after every force setting adjustment (see below).
1Open and close the gate with the test buttons, ensuring that the gate is stopping at the proper open and close limit
positions.
2Place a solid object between the open gate and a rigid structure. Ensure that the gate, the solid object, and the rigid
structure can withstand the forces generated during this obstruction test.
3Run the gate in the close direction. The gate should stop and reverse upon contact with the solid object. If the gate
does not reverse off the solid object, reduce the force setting by turning the force control slightly counter-clockwise.
The gate should have enough force to reach both the open and close limits, but MUST reverse after contact with a
solid object.
4Repeat the test for the open direction.
To protect against fire and electrocution:
• DISCONNECT power and battery BEFORE
installing or servicing operator.
For continued protection against fire:
• Replace ONLY with fuse of same type and
rating.
WIRE THE ENTRAPMENT PROTECTION DEVICES
Connect the entrapment protection device to the EYES EDGE terminal on the control
board.
• Close Photoelectric Sensor Entrapment Protection: Connect wires from the
photoelectric sensors to the Inputs on the CLOSE EYES/INTERRUPT terminal.
• Close Edge Entrapment Protection: Connect wires from the entrapment protection
device to the Inputs on the CLOSE EDGE terminal.
• Open Entrapment Protection: Connect wires from the entrapment protection device
to the Inputs on the OPEN EYES/EDGE terminal.
POWER WIRING
This operator can be wired for either 120 Vac or 240 Vac or a
solar panel (not provided). These instructions show a 120 Vac
application. For information regarding a 240 Vac or solar
application refer to the installation manual.
1
2EARTH GROUND ROD
1Install the earth ground rod within 3 feet
of the operator.
2Run wire from the earth ground rod to the
operator.
Check national and local
codes for proper depth
3
4CONNECT BATTERIES
Red Wire
Black Wire
Jumper
1Connect the battery wires to the
J15 plug on the control board.
2Turn ON AC power to the
operator.
3Turn ON the AC power switch on
the operator.
1Turn off the AC power from the main
power source circuit breaker.
2Run the AC power wires to the
operator.
3Connect the green wire to the earth
ground rod and AC ground using a
wire nut. NOTE: The earth ground
rod can be grounded to the chassis.
4Connect the white wire to NEUTRAL
using a wire nut.
5Connect the black wire to HOT using
a wire nut.
Junction Box
SET OPEN SET CLOSE
OFF
PRESS &
RELEASE
TO BEGIN
LIMIT
ALARM
RESET
MOVE
GATE
5
INPUT POWER
STATUS:
PRESS &
RELEASE
TO BEGIN
SETUP
LIMIT
ALARM
RESET
60
180 MIN MAX
BATT LOW
NETWORK
OPEN CLOSE STOP
XMITTER
NETWORK
AC Power Switch