Chess mymesh User manual

Safety
- Installationshouldbeperformedbyqualiedpersonnelonly.
- The electrical installation must be in conformance with the national legislation and relevant
standards.
- DonotusetheEthernetgatewayifitisdamaged.
- TheEthernetgatewaymustbeinstalledonadrylocation.
Mymesh Ethernet Gateway
Mymesh Building Light Control
The Mymesh Ethernet gateway is a product in the Chess Wise program for building light con-
trol.TheEthernetgatewayautomaticallyformsawireless-sensor-and-controlnetworkwith
thesurroundingBLCproductsandconnectsthisnetworkwithabackoce.
Application
RefertotheEthernetgatewayproductsheet(seeChessWise.eu)fortheenvironmental
conditions.
Location
SelectalocationfortheEthernetgatewayinthedirectneighborhoodofotherBLCproducts.
Avoidclosedmetalcases.
Conguration
FactorydefaultsettingsoftheEthernetgatewayareshownbelow.Inmostcasesthesesettings
aresuitableandnocongurationisneeded.Atthehostsideaproxyserverwillroutethe
connectiontotherequiredEdgeserver.
IP addressing : DHCP
Firmware update url :u1.edge.chess-wise.eu
Firmware update port number : 80
Host url :gw.edge.chess-wise.eu
Host port number : 8080
by Chess
Installation instruction

Conguration
Followtheinstructionsbelowonlyincasethedefaultsettingsneedtobechanged.AnMS
Windows computer is used for the description, but a similar approach can be used for
otheroperatingsystems.ContactChessWiseforfurthersupportifneeded.
1. Disconnectallnetworkconnectionsofthecomputer(removeUTPcablesanddisable
WiFiconnections)
2. ConnectthecomputerandtheEthernetgatewaybymeansofanUTPcable(usea
crosscableifneeded).
3. ConnectthemainspowertotheEthernetgateway.The(right)powerLEDwillblink.
4. OpeninControlpaneltheNetworkandSharingCenter
5. OpentheLocal Area
Connection of the
Ethernet gateway
connection
6. OpenProperties

7. SelectInternet Protocol
Version 4 (TCP/IPv4) and
properties
8. Rememberthecurrentnetwork
settings for restoring later on!!
9. SelecttheoptionforaxedIPaddress
and add the following:
• IPaddress:192.168.0.2
• Subnetmask:255.255.255.0
10. Conrmthechangesandcloseall
congurationscreens.
11. Openawebbrowserwithurl192.168.0.1
(whilethe(left)networkLEDisoand
the(right)power/statusLEDison).
12. Restartthegatewayifneeded(the
gateway will only wait for a connection
withawebbrowserfor30sec).
13. Followingpagewillappear:

14. SelecttheIPconnectionmode:DHPC or static.
In most cases DCHPisused.Onlywhen
no dynamic IP addressing is used static should
becongured.Forstaticrefertostep19.
15. ChecktheFirmware hostname
(u1.edge.chess-wise.eu)andportnumber(80).
Onlychangethesesettingsafterconsultation
withChess.
16. ChecktheBackocehostnameto(gw.edge.
chess-wise.eu)andportnumber(8080).Only
change these settings after consultation
withChess.
17. Leavekeep aliveactive.
18. StorethechangeswithSave.Proceedatstep
27.
19. Followingpagewillappearafterselectionof
static.
Firmware version V1.0.028
Build at Api 18 2019 10:06:23
Device id F855F9A082AACE15
MAC-Address 00:20:92:FF25:1C
Firmware version V1.0.028
Build at Api 18 2019 10:06:23
Device id F855F9A082AACE15
MAC-Address 00:20:92:FF25:1C
20. Enterthelocal IP address and subnet mask of
theEthernetgateway.
21. EntertherouterIPaddressatGateway.
22. EntertheaddressofaDNSserveratDNS.This
canbealocalDNSserver,anISP’sDNSserver
orapublicDNSserver
(e.g.8.8.8.8,GooglepublicDNSserver).
23. ChecktheFirmware hostname
(u1.edge.chess-wise.eu)andportnumber(80).
Onlychangethesesettingsafterconsultation
withChess.
24. ChecktheBackocehostnameto(gw.edge.
chess-wise.eu)andportnumber(8080).Only
change these settings after consultation
withChess.
25. Leavekeep aliveactive.
26. StorethechangeswithSave.
27. RemovetheUTPcablebetweentheEthernet
gatewayandcomputer.
28. Restoretheoriginalnetworksettingsofthe
computer.Seestep4to8.

Installation
1.. MounttheEthernetgatewayattheselectedlocationandconnecttheUTP
andpowercable.
2. OpentheiPadcommissionappandsearchfortheEthernetgatewayinthe
devicelist.
3. CommissiontheEthernetgatewayinaroomofthebuilding.Resetthe
Ethernet gateway in the commission app to restart connection setup if
needed.
4. Afterrestart,the(left)hostconnectionLEDshouldbeoandthe(right)
power/statusLEDshouldbeonfor30seconds.Duringthisintervalthe
gatewayisaccessibleforcongurationwithalocalcomputer.
5. NextthegatewaywillcheckfornewIPrmwareattheChessrmware
server.Whenthisisthecase,thegatewaywillautomaticallydownloadand
installit.Thiswilltakeanumberofseconds.Duringsoftwareupdatethe
(left)hostconnectionLEDwillbeonandthe(right)powerLEDwillblink
quickly.
6. Afterwardsthegatewaywilltrytosetupaconnectionwiththehost
computer.The(left)hostconnectionLEDwillbeonandthe(right)power/
statusLEDwillblinkslowly.Assoonasthehostconnectionisestablished
thepower/statusLEDwillbeon.
7. The(center)MymeshLEDwillbeonwhenasurroundingMymeshnetwork
isdetected.
8. RefertothesectionstatusLEDsfordetailedconnectionstatusindications.
Problems
Suggestion for trouble shooting:
Host connection not established
ChecktheUTPcable
ChecktheEthernetgatewaycongurationsettings
Checkaccessibilityofhostcomputer
Checkrewallsettings
Hostconnectionbroken Checkrewalltimeoutsettings.Shouldbemorethan5min.
Mymesh connection not
established
Check(using the iPad commissionapp) that the Ethernet
gatewayhasbeencommissionedinaroomofthebuilding.

Status LEDs
ThreegreenLEDsatthefrontindicatetheEthernetgatewaystatus.
Power/status(seetablebelow)
Mymeshnetworkdetection
Hostconnection(seetablebelow)
ThetablebelowdetailstheLEDindicationsduringconnectionsetup.
Gateway status
OO
O Quick blink
O Slow blink
Quick blink Quick blink
On
Slow blink
OnO
On On
Powero.Checkpowercable
NoEthernetdetected.ChecktheUTP
cable
Awaitingcongurationupdate(30sec).
Duringthistimethecongurationpage
canbeopenedwithabrowser.
NoDHCPornoDNSqueryresult.On
sitenetworkorgatewaystaticIP
congurationissue.
DHCPconict.Removeandinsert
networkcableorpowercycleEthernet
gateway.
Awaitingrmwareupdateconnection
orinstallingnewIPrmware.
Quick blink
Awaiting Edge server connection
On
Connected to Edge server
Usage
TheEthernetgatewaywillconnecttheBLCnetworktotherelatedEdgeserver.
Compliance
This product complies with the European directives and relevant standards for
lowvoltage,EMC,RED,REACHandRoHS.TheEthernetgatewaycontainsa2.4
Ghzradio.Theappliedfrequencyoftheradioiswithintheband2.401–2.483GHz
andthemaximumtransmitpoweris+4dBm.
Hereby, Chess Wise declares that the radio equipment type Ethernet gateway is
incompliancewithDirective2014/53/EU.ThefulltextoftheEUdeclarationof
conformityisavailableatchess-wise.eu/downloads.

Repair
Donotopenthisproduct.IncaseoffailuretheEthernetgatewaymustbe
replaced.
Recycling
Do not dispose this product as household waste, but bring it to an appropriate
collectionpointforrecycling.
Other manuals for mymesh
2
Table of contents
Other Chess Gateway manuals
Popular Gateway manuals by other brands

AT&T
AT&T U-verse TV installation guide

Sierra Wireless
Sierra Wireless airlink es440 Hardware user's guide

Lucent Technologies
Lucent Technologies AnyMedia 4300 Specifications

Inteno
Inteno X5669 installation guide

Allied Telesis
Allied Telesis AT-iMG606BD Specifications

FXS
FXS 2FXS Administrator user manual