CIAM BRILLIANT Series User manual

BRILLIANT SERIES
TN VENTILATED
User manual
CIAM spa
06081 Petrignano d’Assisi
PG – Italy
tel. 075 80161
Fax 075 8016215
http //www.ciamgroup.it
e-mail [email protected]

1. INTRODUCTION
1.1. PRESENTATION
Dear customer,
Ciam spa, glad to have among its customers, confident that you purchased the equipment fully meets your expectations. For this to happen it is
advisable to follow the advice and instructions contained in this user’s manual that you should always keep it safe for future reference.
1.2. USE OF EQUIPMENT
PERMITTED USED
his refrigeration unit is used exclusively for the exhibition and sale of confectionery products.
NOT PERMITTED USED
It 'absolutely forbidden to use the equipment for storage of pharmaceutical products.
1.3. NORME RISPETTATE
he device is designed in meeting the safety standards laid down by the applicable directives:
Direttiva Macchine N° 200 /42/CE : Regulations for the CE
Direttiva N° 200 /95/CE : lowt tension
Direttiva N° 2004/108/CE : electromagnetic compatibility
Norma CEI EN 0335-1 (CEI 1-150) : Safety of household and similar electrical
Norma CEI EN 0335-2-24 (CEI 1-5 ) : Particular requirements for refrigerators, freezers and ice makers
1.4. RESPONSABILITY
he manufacturer declines all responsibility for damage caused to persons, animals or the product itself due to:
• non-compliance with the rules in force;
• installation not in accordance with the provisions contained in the manual;
• failure to comply with maintenance recommended in the manual;
• extraordinary changes do not agree with the 'manufacturer;
• Operation of this equipment other than that provided.
1.5. WARNING
he manufacturer reserves the right, at any time and without obligation to promptly update the contents of the manual and / or modify the product in
case it contributes to the improvement of the quality of the same.
2. DISPLAY CASE DATA PLATE
2.1. DATA PLATE CONTENT
1. Commercial name of the unit
2. Identification number
3. Production date
4. Voltage
5. Phases
6. Frequency
7. Compressor type
8. Number of compressor
9. Refrigerant type
10. Refrigerant weight
11. Climatic rate (Cl.3 = +25°C/60% U.R.; Cl. 4 = +30°C/55% U.R.)
12. est pressure – system high pressure side
13. est pressure – system low pressure side
14. Nominal power/current absorbed during defrost
15. Max. power absorbed during defrost
16. Nominal power absorbed by heating elements (only if higher than 100W)
17. Lighting nominal power

2. TECHNICAL DATA
External dimension
( LxWxH ) (mm)
1
390
x
686x24
15
Type of dysplay shelves
Glass tempered
477x1250
mm
thickness 10 mm
Number of shelves
8
Capacità netta di ogni ripiano
(
Kg
)
15 kg
regulary distribuited
Prestazioni
Cliamtic class
(°C/%U.R.)
3
-
(+25° / 60%)
Class Temperature
H2 (-1 ÷+10)
Temperatura di esercizio
(°C)
+4÷+15
Electric supplied
(V/ph/Hz)
230 / 1 / 50
or 60
Type of refrigeration
ventilated
Type of defrost
Stop compressor
Refrigerant
R 404A
Illumination
T
ype
Led 4100°K 12V 9Watt/meter
N°
4
Condensing
unit
Type
Hermetic single-phase
N°
1
Po
wer
/c
urrent
absorbed
(W/A)
350 / 1.5 without U.C.)
Closing refrigerated compartment
Doors with double glass

3. INSTALLATION
3.1. MACHINE HANDLING
The movement, the means of transport to the final site, must be carried out following the instructions rovided in the A endix.
The cabinet can be shipped with or without wood packaging, in case wood crate will
be used, will have a pallet base for an easy fork
-
lift handling.
The pallet, however should be handle in the central position
During the shipment, it is necessary to avoid any crash or/and shake of the display cabinet in order to not damage its frame, especially its glasses.
Do not drag the display cabinet on the floor and do not push it on the upper glasses
.
3.2 STOCK OF THE DISPLAY CABINET
Whenever the cabinet has to be stoked, follow carefully what suggested before.
Environmental temperature during the cabinet stock can have following range - 5°C and + 55°C and humidity between 30% and 90%.
The display cabinet has always to be protected by sunrays and raining.
In case the display cabinet has to remain in stock quite long time before its use, keep it with its packaging in order to maintain its protection.
3.3. PACKAGING REMOVE
Before getting the display cabinet from the forwarding agent, check its conditions. In case it will be some damages, inform the driver and sign it on
shipping documents. Eventual damages relevant to the shi ment and/or to the wrong stock, have not to be ascribed to the manufacturer.
3.4. DISPLAY CABINET POSITION
The refrigerated display cabinet needs particular environmental conditions in order to offer the right performance, so that the area where it will be
used has to respect following indications
Floor has to be levelled perfectly, on the contrary keep the display cabinet on the horizontal position in order to guarantee
a perfect defrosting
water drain and avoid boring compressor noises.
The display cabinet has to not be under the sun
-
rays in order to have its better refrigeration performance, has to remain inside the local or to be
sheltered by window curtain. If what described above is not observed, it can determinate an increase of temperature of displayed product and
an increasing power consume.
The display cabinet has not to be under air currents due to open doors or windows, or under roof ventilators or under air co
ndition outlets.
In case will be not respected the above suggestions it can arise an increasing of temperature of the displayed product and/or an increasing ice
phenomena on the evaporator and internal fans, which compromise the correct cold air circulation and product consistence
The display cabinet has not to be placed close any heat source as heaters, ovens, etc
The display cabinet has to have a sufficient place in order to ensure a correct custom service, to make an easy maintenance o
per
ation, to
guarantee the right air flow necessary to make cold the condenser. Besides the warm air which flows out has to no have any obstacle or to
invest other equipments in order to not reduce the correct functions.

3.5. REMOTE CONDENSING UNIT PLACING
According to the model of ice cream display cabinet you have No. or No.2 internal, or remote, condensing units.
The remote condensing unit has to be checked by specialised technicians and according to the required refrigerating power and their position
respect the cabinet. The condensing unit has to be placed following these points:
The condensing unit has to be located at least 250 mm from any eventual wall.
( ic.
3
.
1
)
Air flow direction has to be from the eventual wall towards compressor.
The local, in case will be closed, has to be with enough air circulation.
By the condenser has to be guaranteed in any case as much as possible cold air.
In case will be necessary it has to be foreseen a forced air exchange by any fan according to the
air flow of condenser.
The condensing units of display cabinets have to be fixed properly.
The generated noise has not exceed the admitted noise levels relevant to the public places,
especially in case of domestic buildings.
It is always necessary a sufficient place along the four sides of the display cabinet in order to make
easy any type of check and maintenance operations.
When the condensing units are external will be necessary a frame holder that has to be fixed in a
proper way and eventually added with amortising elements. Besides this frame has to be closet with
no-water protection grid and sufficient opening holes for ventilation.
36 ELECTRICAL CONNECTION
Before proceeding with electrical connection, be sure that the available electric power and tension are what is required on technical label of the
cabinet.
The electric connection has to be made by qualified personnel and following manufacturer’s instructions taking into
consideration the relevant norms in force.
The display cabinet has already a general switch, however it is necessary an omni
polar switch, with a minimum distance among the contacts of 3mm.
It is obligatory that the display cabinet will be connected properly with an efficient
ground socket.
WARNING!
A wrong connection may occur always to persons, animals and things,
where the manufacturer cannot be considered as responsible.
WARNING!
The dis lay cabinet has no main switch breaking both the hases.
Before any maintenance o eration disconnect the electrical su ly of the
dis lay cabinet (see label on the rear of the dis lay cabinet). ( ic.3.3).
ic.3.1
ic.3.3

!
"
#
$
%
&
"
#
'

4. LOAD LIMITS AND NOTES TO THE CORRECT FUNCTIONING
4.1 SHELVES POSITION
WARNING! The glass shelves a e numbe ed and must be placed inside the ef ige ated c ite ion, only in this way you can ensu e
p ope cooling inside the ef ige ated compa tment.
POSITION OF THE SHELVES
1
2
3
4
5
6
7
8

NUMBERS OH THE SHELVES
4.2 LOAD LIMIT
Each glass shelf can be loaded with a maximum weight of 15kg, the weight should be distributed evenly over the surface of the floor.
Leave between a product and the other sufficient space for air circulation and also to facilitate the grip by the customer.
Also leave a space of at least cm between the upper limit of the displayed product and the shelf immediately above to allow a more
facilitates air circulation above the product itself.
WARNING! The ef ige ated cabinet is a fai dist ibution of the tempe atu e when it is fully loaded (within the limits set by the load
limits just mentioned).
In this case it will also be gua anteed a lowe ai exchange opening of the doo s, with the consequent dec ease in the pe centage
of comp esso ope ation, and then with all the benefits associated.
NUMBERS ENGRAVED ON
GLASS SHELF

5.
ROUTINE MAINTENANCE AND PERIODIC CHECKS
These kinds of operations are at client s expenses.
In case some malfunctioning of the unit are observed, please make sure this is not due to non-maintenance reasons, before you apply to qualified
assistance.
The accurate and periodic cleaning of the unit will reduce the risk of damages to the unit itself and to the products stored within.
See following tab for reference.
ATTENTION !
Before starting any maintenance and cleaning operation make sure you operate on the
main switch in order to deactivate tension (pic. 5)
(pic 5)
MAINTENANCE OPERATIONS AND THIR FREQUENCY. A SUMMARY TAB.
OPERATION DESCRIPTION FREQUENCY
Surfaces cleaning •Wash exclusively with warm water and neutral soup; rinse abundantly and wipe off with a soft
cloth.
•Do not use abrasive products
weekly
Plastic surfaces cleaning •Wash exclusively with warm water and neutral soup; rinse abundantly and wipe off with a soft
cloth.
•Do not use alcohol, acetone and any solvent that might spoil the look and structure of the
material.
weekly
Glass surfaces cleaning •Use only specific products for glass cleaning
•Using water alone might lead to calcareous deposits on the glass surfaces
daily
Wooden surfaces cleaning •Use exclusively a wet cloth. weekly
Additional defrost
•Under particular conditions of temperature and humidity, the frost that normally forms on the
evaporator and fans might increase in volume, so leading to a faulty functioning the unit.
•If these conditions should last, the assistance of a qualified technician shall be needed. Waiting
for this service, it is suggested to operate one or more defrost cycles (despite the damages this
might cause to the stored product)
Waiting for
qualified
assistance
Periodic defrost
•In order to obtain the best performance from the cooling system, we suggest to operate an
extended defrost cycle.
•Before you do that, please remove displayed products from inside the cabinet; always operate
an additional defrost cycle in order to remove from the evaporator the largest possible amount
of frost or ice. Turn the main switch off for 5 hours (min.)
•Before re-starting the unit, make sure that frost has totally melted and wipe carefully.
max. 15 DAYS
ATTENTION! DO NOT CLEA
N THE UNIT WITH WATER JETS
6. EXTRAORDINARY MAINTENANCE
This type of operation has to be made by qualified technician only.
ATTENTION!
Before operating any maintenance, make sure the tension is deactivated. (pic.11).
Lamps replacement: qualified technician needed.
Air condenser cleaning: qualified technician needed. When the fan is switched off you can clean the condenser
with a compressed air jet. Never use metallic brushes. Use protection gloves (pic.6).
(Pic.
6
.)

DixellDixell
Installing and Operating Instructions rel.1.0 –25/10/2000 - cod. 1592009530
1592009530 XW271K GB.doc
XW270K - XW271K
1/2
WWINGING
XW270K - XW271KXW270K - XW271K
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
•This manual is part of the product and should be kept near the instrument for
easy and quick reference.
•The instrument shall not be used for purposes different from those described
hereunder. It cannot be used as a safety device.
•Check the application limits before proceeding.
1.2 SAFETY PRECAUTIONS
•Check the supply voltage is correct before connecting the instrument.
•Do not expose to water or moisture: use the controller only within the
operating limits avoiding sudden temperature changes with high atmospheric
humidity to prevent formation of condensation
•Warning: disconnect all electrical connections before any kind of
maintenance.
•Fit the probe where it is not accessible by the End User. The instrument must
not be opened.
•In case of failure or faulty operation send the instrument back to the distributor
or to “Dixell s.r.l.” (see address) with a detailed description of the fault.
•Consider the maximum current which can be applied to each relay (see
Technical Data).
•Ensure that the wires for probes, loads and the power supply are separated
and far enough from each other, without crossing or intertwining.
•In case of applications in industrial environments, the use of mains filters (our
mod. FT1) in parallel with inductive loads could be useful.
2. GENERAL DESCRIPTION
Models XW270K and XW271K are microprocessor based controllers suitable for
applications on medium or low temperature refrigerating units. They must be
connected by means of a two-wire cable (∅1mm) at a distance of up to 30 meters
to the keyboards T820 or T821. They are provided with six relay outputs to control
compressor, defrost - which can be either electrical or hot gas - the evaporator
fans, the lights, the alarm and an auxiliary output. In XW271L the auxiliary output is
configured as anti-condensing heater.
They are also provided with three NTC probe inputs, one for temperature control,
one to control the defrost end temperature of the evaporator and the third, optional,
for the display. There are two digital inputs (free contact) for the door switch and
configurable by parameter.
The standard TTL output allows the user to connect, by means of a TTL/RS485
external module, a ModBUS-RTU compatible monitoring system and to programme
the parameter list with the “Hot Key”. An optional output for RS485 direct is
available.
3. CONTROLLING LOADS
3.1 THE COMPRESSOR
The regulation is performed according to the temperature measured by the
thermostat probe with a positive differential from the set point: if the temperature
increases and reaches set point plus differential the compressor is started and then
turned off when the temperature reaches the set point value again.
In case of fault in the thermostat probe the start and stop of the compressor are
timed through parameters “COn” and “COF”.
3.2 FAST FREEZING
When defrost is not in progress, it can be activated the keypad by holding the
èè
key pressed for about 3 seconds. The compressor operates in continuous mode for
the time set through the “CCt” parameter. The cycle can be terminated before the
end of the set time using the same activation key,
èè
for about 3 seconds.
3.3 DEFROST
Three defrost modes are available through the “tdF” parameter: defrost with
electrical heater, hot gas or thermostatic defrost. The defrost interval is control by
means of parameter “EdF”: (EdF=in) the defrost is made every “IdF” time, (EdF=Sd)
the interval “IdF” is calculate through Smart Defrost algorithm (only when the
compressor is ON and the evaporator temperature is bigger than “SdF” parameter).
At the end of defrost the drip time is controlled through the “Fdt” parameter.
3.4 CONTROL OF EVAPORATOR FANS
The fan control mode is selected by means of the “FnC” parameter:
C-n = running with the compressor, OFF during the defrost;
C-y = running with the compressor, ON during the defrost;
O-n = continuous mode, OFF during the defrost;
O-y = continuous mode, ON during the defrost;
An additional parameter “FSt” provides the setting of temperature, detected by the
evaporator probe, above which the fans are always OFF. This can be used to make
sure circulation of air only if his temperature is lower than set in “FSt”.
3.5 AUXILIARY OUTPUT
The auxiliary output is switch ON and OFF by means of the corresponding button
on the keyboard.
The auxiliary output of the XW271K model controls the anti-condensing heater and
it is automatically activated if the room temperature is lower than the “SAA”
parameter.
4. KEYBOARD
To display and modify target set point; in programming mode it
selects a parameter or confirm an operation.
By holding it pressed for 3s when max or min temperature is
displayed it will be erased.
To see the max. stored temperature; in programming mode it
browses the parameter codes or increases the displayed value. By
holding it pressed for 3s the fast freezing cycle is started.
To see the min stored temperature; in programming mode it browses
the parameter codes or decreases the displayed value.
By holding it pressed for 3s the defrost is started.
Switch ON and OFF the cold room light.
By holding it pressed for 3s Energy Saving function is started or
stopped.
Present in T820 Keyboard ( for connection to XW270K).
Switch ON and OFF the auxiliary output.
Present in T821 Keyboard ( for connection to XW271K).
Switch ON and OFF the anti-condensing heater output.
Switch ON and OFF the instrument.
KEY COMBINATIONS
+To lock and unlock the keyboard.
+To enter the programming mode.
+To exit the programming mode.
4.1 USE OF LEDS
Each LED function is described in the following table.
LED MODE Function
ON The compressor is running
FLASHING - Programming Phase (flashing with LED )
- Anti-short cycle delay enabled
ON The fan is running
FLASHING Programming Phase (flashing with LED )
ON The defrost is enabled
FLASHING Drip time in progress
ON The Fast Freezing cycle is enabled
ON - ALARM signal
- In “Pr2” indicates that the parameter is also
present in “Pr1”
ON (Present only in T821 keyboard)
The Anti-condensing heater relay (Aux) is ON.
Function of the LEDs placed on the left top side of buttons:
BUTTON MODE FUNCTION
SET FLASHING The Set point is displayed and it can be
modified
DEFROST ON The Manual Defrost is activated
ENERGY SAVING ON The Energy Saving is enabled
LIGHT ON The Light is ON
AUX ON The Auxiliary output is ON (T820)
HEATER ON The Anti-condensing heater is ON (T821)
ON/OFF ON The instrument is OFF
4.2 HOW TO SEE THE MIN TEMPERATURE
1. Press and release the
key.
2.
The “Lo” message will be displayed followed by the minimum
temperature recorded.
3. By pressing the
key or waiting for 5s the normal display will
be restored.
4.3 HOW TO SEE THE MAX TEMPERATURE
1. Press and release the
èè
key.
2.
The “Hi” message will be displayed followed by the maximum
temperature recorded.
3. By pressing the
èè
key or waiting for 5s the normal display will
be restored.
4.4 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED
To reset the stored temperature, when max or min temperature is displayed :
1. Press SET key until “rST” label starts blinking.
N.B. After the installation RESET the temperature stored .
4.5 HOW TO SEE AND MODIFY THE SET POINT
1. Push and immediately release the SET key: the display will
show the Set point value;
2. The SET LED start blinking;
3. To change the Set value push the
èè
or
arrows within 10s.
4. To memorise the new set point value push the SET key again
or wait 10s.
4.6 TO START A MANUAL DEFROST
1. Push the DEF key for more than 2 seconds and a manual
defrost will start.
4.7 TO ENTER IN PARAMETERS LIST “PR1”
To enter the parameter list “Pr1” (user accessible parameters) operate as follows:
1. Enter the Programming mode by pressing the Set
and DOWN key for few seconds ( and
start blinking).
2. The instrument will show the first parameter
present in “Pr1”
4.8 TO ENTER IN PARAMETERS LIST “PR2”
To access parameters in “Pr2”:
1. Enter the “Pr1” level.
2. Select “Pr2” parameter and press the “SET” key.
3. The “PAS” flashing message is displayed, shortly followed by “0 - -” with a
flashing zero.
4. Use
èè
or
to input the security code in the flashing digit; confirm the figure
by pressing “SET”. The security code is “321“.
5. If the security code is correct the access to “Pr2” is enabled by pressing “SET”
on the last digit.
Another possibility is the following: after switching ON the instrument the user can
push Set and DOWN keys within 30 seconds.
NOTE: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by
pressing “SET” +
. When a parameter is present in “Pr1” LED is on.
4.9 HOW TO CHANGE THE PARAMETER VALUE
1. Enter the Programming mode.
2. Select the required parameter with
èè
or
.
3. Press the “SET” key to display its value ( and LED starts blinking).
4. Use
èè
or
to change its value.
5. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 15s without pressing a key.
NOTE: the new programming is stored even when the procedure is exited by
waiting the time-out.
4.10 HOW TO LOCK THE KEYBOARD
1.
Keep the
èè
and
keys pressed together for more than 3 s
the
èè
and
keys.
2.
The “POF” message will be displayed and the keyboard is
locked. At this point it is only possible the viewing of the set
point or the MAX o Min temperature stored and to switch ON
and OFF the light, the auxiliary output and the instrument.
TO UNLOCK THE KEYBOARD
Keep the
èè
and
keys pressed together for more than 3s.
4.11 ON/OFF FUNCTION
By pushing the ON/OFF key, the instrument shows “OFF” for 5 sec.
and the ON/OFF LED is switched ON.
During the OFF status, all the relays are switched OFF and the
regulations are stopped; if a monitoring system is connected, it does
not record the instrument data and alarms.
N.B. During the OFF status the Light and AUX buttons are
active.
4.12 TO SEE THE PROBE VALUES
1. Enter in “Pr2” level.
2. Select “Prd” parameter with
èè
or
.
3. Press the “SET” key to display “Pb1” label alternate with Pb1 value.
4. Use
èè
and
keys to display the other probe values.
5. Press “SET” to move to the following parameter.
5. PARAMETER LIST
REGULATION
Hy Differential: (0,1÷25,5°C; 1÷45°F): Intervention differential for set point,
always positive. Compressor Cut IN is Set Point Plus Differential (Hy).
Compressor Cut OUT is when the temperature reaches the set point.
LS Minimum set point limit: (-50,0°C÷÷SET; -58°F÷SET) Sets the minimum
acceptable value for the set point.
US Maximum set point limit: (SET÷÷110°C; SET÷230°F) Set the maximum
acceptable value for set point.
OdS Outputs activation delay at start up: (0÷255 min) This function is enabled
at the initial start up of the instrument and inhibits any output activation for the
period of time set in the parameter. (AUX and Light can work)
AC Anti-short cycle delay: (0÷30 min) interval between the compressor stop
and the following restart.
CCt Thermostat override: (0min ÷23h 50min) allows to set the length of the
continuous cycle. Can be used, for instance, when the room is filled with new
products.
Con Compressor ON time with faulty probe: (0÷255 min) time during which the
compressor is active in case of faulty thermostat probe. With COn=0
compressor is always OFF.
COF Compressor OFF time with faulty probe: (0÷255 min) time during which the
compressor is off in case of faulty thermostat probe. With COF=0 compressor
is always active.
DISPLAY
CF Temperature measurement unit: °C = Celsius; °F = Fahrenheit . When the
measurement unit is changed the SET point and the values of the regulation
parameters have to be modified
rES Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display.
de = 0,1°C
in = 1 °C
Red Remote display : select which probe is displayed by the remote display
(T820 or T821)
P1 = Thermostat probe
P2 = Evaporator probe
P3 = auxiliary probe
1r2 = difference between P1 and P2 (P1-P2)
DEFROST
tdF Defrost type:
rE = electrical heater (Compressor OFF)
rT = thermostat defrost. During the defrost time “MdF”, the heater switches
On and OFF depending on the evaporator temperature and “dtE” value.
in = hot gas (Compressor and defrost relays ON)
EdF Defrost mode:
in = interval mode. The defrost starts when the time “Idf” is expired.
Sd = Smartfrost mode. The time IdF (interval between defrosts) is increased
only when the compressor is running (even non consecutively) and only if the
evaporator temperature is less than the value in "SdF” (set point for
SMARTFROST).
SdF Set point for SMARTFROST: (-30÷30 °C/ -22÷86 °F) evaporator
temperature which allows the IdF counting (interval between defrosts) in
SMARTFROST mode.
dtE Defrost termination temperature: (-50,0÷110,0°C; -58÷230°F) (Enabled
only when the evaporator probe is present) sets the temperature measured by
the evaporator probe which causes the end of defrost.
IdF Interval between defrosts: (1÷120h) Determines the time interval between
the beginning of two defrost cycles.
MdF (Maximum) duration of defrost: (0÷255 min) When P2P = n, no evaporator
probe, it sets the defrost duration, when P2P = y, defrost end based on
temperature, it sets the maximum length for defrost.
dFd Display during defrost:
rt = real temperature;
it = temperature reading at the defrost start;
Set = set point;
dEF = “dEF” label;
dEG = “dEG” label;
dAd Defrost display time out: (0÷255 min) Sets the maximum time between the
end of defrost and the restarting of the real room temperature display.
Fdt Drain down time: (0÷60 min.) time interval between reaching defrost
termination temperature and the restoring of the control’s normal operation.
This time allows the evaporator to eliminate water drops that might have
formed due to defrost.
dPO First defrost after start-up:
y= Immediately;
n= after the IdF time
dAF Defrost delay after fast freezing: (0min÷23h 50min) after a Fast Freezing
cycle, the first defrost will be delayed for this time.
FANS
FnC Fan operating mode:
C-n = running with the compressor, OFF during the defrost;
C-y = running with the compressor, ON during the defrost;
O-n = continuous mode, OFF during the defrost;
O-y = continuous mode, ON during the defrost;
Fnd Fan delay after defrost: (0÷255 min) The time interval between the defrost
end and evaporator fans start.
FSt Fan stop temperature: (-50÷110°C; -58÷230°F) setting of temperature,
detected by evaporator probe, above which the fan is always OFF.
ALARMS
ALC Temperature alarm configuration
rE = High and Low alarms related to Set Point
Ab = High and low alarms related to the absolute temperature.
ALU High temperature alarm setting:
ALC= rE, 0 ÷÷ 50°C or 90°F
ALC= Ab, ALL ÷110°C or 230°F
when this temperature is reached and after the ALd delay time the HA alarm
is enabled.
ALL Low temperature alarm setting:
ALC = rE , 0 ÷÷ 50 °C or 90°F
ALC = Ab , - 50°C or -58°F ÷÷ ALU
when this temperature is reached and after the ALd delay time, the LA alarm
is enabled,.
AFH Temperature alarm and fan differential: (0,1÷25,5°C; 1÷45°F) Intervention
differential for temperature alarm set point and fan regulation set point, always
positive.
ALd Temperature alarm delay: (0÷255 min) time interval between the detection
of an alarm condition and the corresponding alarm signalling.
dAO Delay of temperature alarm at start-up: (0min÷23h 50min) time interval
between the detection of the temperature alarm condition after the instrument
power on and the alarm signalling.
EdA Alarm delay at the end of defrost: (0÷255 min) Time interval between the
detection of the temperature alarm condition at the end of defrost and the
alarm signalling.
dot Delay of temperature alarm after closing the door : (0÷255 min) Time
delay to signal the temperature alarm condition after closing the door.
doA Open door alarm delay:(0÷255 min) delay between the detection of the
open door condition and its alarm signalling: the flashing message “dA” is
displayed.
tbA Buzzer and alarm relay silencing: by pushing one of the keypad buttons.
n= Only the Buzzer is silenced;
y= Buzzer and relay are silenced.
nPS Pressure switch number: (0 ÷15) Number of activation of the pressure
switch, during the “did” interval, before signalling the alarm event (I2F= PAL).
PROBE INPUTS
Ot Thermostat probe calibration: (-12.0÷÷12.0°C/ -21÷÷21°F) allows to adjust
possible offset of the thermostat probe.
OE Evaporator probe calibration: (-12.0÷÷12.0°C/ -21÷÷21°F) allows to adjust
possible offsets of the evaporator probe.
O3 Auxiliary probe calibration: (-12.0÷÷12.0°C/ -21÷÷21°F) allows to adjust
possible offsets of the evaporator probe.
P2P Evaporator probe presence:
n= not present: the defrost stops only by time; y= present: the defrost stops
by temperature and time.
P3P Auxiliary probe presence: n= not present; y= present.
HES Temperature increase during the Energy Saving cycle : (-30,0°C ÷
30,0°C / -22÷86°F) sets the increasing value of the set point during the
Energy Saving cycle.
DIGITAL INPUTS
odc Compressor and fan status when open door:
no = normal;
Fan = Fan OFF;
CPr = Compressor OFF;
F_C = Compressor and fan OFF.
I1P Door switch input polarity:
CL : the digital input is activated by closing the contact;
OP : the digital input is activated by opening the contact.
I2P Configurable digital input polarity:
CL : the digital input is activated by closing the contact;
OP : the digital input is activated by opening the contact
I2F Digital input operating mode: configure the digital input function:
EAL = generic alarm;
bAL = serious alarm mode;
PAL = Pressure switch;
dFr = Start defrost;
AUS = Relay AUX actuation;
Es = Energy Saving;
onF = remote On/OFF.
did Time interval/delay for digital input alarm:(0÷255 min.) Time interval to
calculate the number of the pressure switch activation when I2F=PAL. If
I2F=EAL or bAL (external alarms), “did” parameter defines the time delay
between the detection and the successive signalling of the alarm.
SAA Set Point for anti-condensing heater: (-50,0÷110,0°C; -58÷230°F) defines
the room temperature setpoint to switch on the anti-condensing heater.
OTHER
Adr RS485 serial address (1÷247):Identifies the instrument address when
connected to a ModBUS compatible monitoring system.
Rel Release software: (read only) Software version of the microprocessor.
Ptb Parameter table: (read only) it shows the original code of the
dIXEL
parameter map.
Prd Probes display: (read only) display the temperature values of the evaporator
probe Pb2 and the auxiliary probe Pb3.
Pr2 Access to the protected parameter list (read only).
6. DIGITAL INPUTS
The Wing series can support up to 2 free contact digital inputs. One is always
configured as door switch, the second is programmable in seven different
configurations by the “I2F” parameter.

DixellDixell
Installing and Operating Instructions rel.1.0 –25/10/2000 - cod. 1592009530
1592009530 XW271K GB.doc
XW270K - XW271K
2/2
6.1 DOOR SWITCH INPUT
It signals the door status and the corresponding relay output status through the
“odc” parameter:
no = normal (any change);
Fan = Fan OFF;
CPr = Compressor OFF;
F_C = Compressor and fan OFF.
Since the door is opened, after the delay time set through parameter “dOA”, the
alarm output is enabled and the display shows the message “dA”. The alarm stops
as soon as the external digital input is disabled again. During this time and then for
the delay “dot” after closing the door, the high and low temperature alarms are
disabled.
6.2 CONFIGURABLE INPUT - GENERIC ALARM (EAL)
As soon as the digital input is activated the unit will wait for “did” time delay before
signalling the “EAL” alarm message. The outputs status don’t change. The alarm
stops just after the digital input is de-activated.
6.3 CONFIGURABLE INPUT - SERIOUS ALARM MODE (BAL)
When the digital input is activated, the unit will wait for “did” delay before signalling
the “BAL” alarm message. The relay outputs are switched OFF. The alarm will stop
as soon as the digital input is de-activated.
6.4 CONFIGURABLE INPUT - PRESSURE SWITCH (PAL)
If during the interval time set by “did” parameter, the pressure switch has reached
the number of activation of the “nPS” parameter, the “PAL” pressure alarm
message will be displayed. The compressor and the regulation are stopped. When
the digital input is ON the compressor is always OFF.
6.5 CONFIGURABLE INPUT - START DEFROST (DFR)
It executes a defrost if there are the right conditions. After the defrost is finished, the
normal regulation will restart only if the digital input is disabled otherwise the
instrument will wait until the “Mdf” safety time is expired.
6.6 CONFIGURABLE INPUT - RELAY AUX ACTUATION (AUS)
This function allows to turn ON and OFF the auxiliary relay by using the digital input
as external switch.
6.7 CONFIGURABLE INPUT - ENERGY SAVING (ES)
The Energy Saving function allows to change the set point value as the result of the
SET+ HES (parameter) sum. This function is enabled until the digital input is
activated.
6.8 CONFIGURABLE INPUT - REMOTE ON/OFF (ONF)
This function allows to switch ON and OFF the instrument.
6.9 DIGITAL INPUTS POLARITY
The digital inputs polarity depends on “I1P” and “I2P” parameters.
CL : the digital input is activated by closing the contact.
OP : the digital input is activated by opening the contact
7. INSTALLATION AND MOUNTING
T820 and T821 keyboards shall be mounted on vertical panel, in a 150x31 mm
hole, and fixed using two screws ∅3 x 2mm. To obtain an IP65 protection grade
use the front panel rubber gasket (mod. RG-L). Power modules XW270K and
XW271K shall be mounted in a panel with two or more screws and they must be
connected to the keyboards by means of a two-wire cable (∅1mm). The
temperature range allowed for correct operation is 0 - 60 °C. Avoid places subject
to strong vibrations, corrosive gases, excessive dirt or humidity. The same
recommendations apply to probes. Let the air circulate by the cooling holes.
7.1 T820 AND T821 CUT OUT
165
150
31
+0.5
-0
+0 .5
-0
+1
-1
Ø3 x2
7.2 MOUNTING WITH KEYBOARD COVER OPENING DOWNWARD
CLICK!
1
2
2
3
3
1
1
7.3 MOUNTING WITH KEYBOARD COVER OPENING UPWARD
CLICK!
1
2
2
2
3
3
1
1
8. ELECTRICAL CONNECTIONS
XW270K and XW271K are provided with screw terminal block to connect cables
with a cross section up to 2,5 mm2for the RS485(optional) and the keyboard.
Connecting other inputs, power supply and relays, XW270K and XW271K are
provided with Faston connection (6,3mm). Heat-resistant cables have to be used.
Before connecting cables make sure the power supply complies with the
instrument’s requirements. Separate the probe cables from the power supply
cables, from the outputs and the power connections. Do not exceed the maximum
current allowed on each relay, in case of heavier loads use a suitable external relay.
N.B. Maximum current allowed for all the loads is 20A.
8.1 PROBE CONNECTIONS
The probes shall be mounted with the bulb upwards to prevent damages due to
casual liquid infiltration. It is recommended to place the thermostat probe away from
air streams to correctly measure the average room temperature. Place the defrost
termination probe among the evaporator fins in the coldest place, where most ice is
formed, far from heaters or from the warmest place during defrost, to prevent
premature defrost termination.
9. TTL/RS485 SERIAL LINE
The TTL connector allows, by means of the external module TTL/RS485 (XJ485), to
connect the unit to a network line ModBUS-RTU compatible as the
dIXEL
monitoring system XJ500 (Version 3.0).
The same TTL connector is used to upload and download the parameter list of the
“HOT KEY“. The instruments can be ordered wit the serial output RS485(Optional).
10. USE OF THE PROGRAMMING “HOT KEY “
The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2
internal memory to the “Hot Key” and vice-versa.
10.1 DOWNLOAD (FROM THE “HOT KEY” TO THE INSTRUMENT)
1. Turn OFF the instrument by means of the ON/OFF key, remove the TTL
serial cable if present, insert the “Hot Key” and then turn the Wing ON.
2. Automatically the parameter list of the “Hot Key” is downloaded into the
Wing memory, the “DoL” message is blinking. After 10 seconds the
instrument will restart working with the new parameters.
3. Turn OFF the instrument remove the “Hot Key”, plug in the TTL serial
cable, then turn it ON again.
At the end of the data transfer phase the instrument displays the following
messages:
“end “ for right programming.
The instrument starts regularly with the new programming.
“err” for failed programming.
In this case turn the unit off and then on if you want to restart the download
again or remove the “Hot key” to abort the operation.
10.2 UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”)
1. Turn OFF the instrument by means of the ON/OFF key and remove the TTL
serial cable if present; then turn it ON again.
2. When the Wing unit is ON, insert the “Hot key” and push
è
key; the
"uPL" message appears.
3. Push “SET” key to start the UPLOAD; the “uPL” message is blinking.
4. Turn OFF the instrument remove the “Hot Key”, plug in the TTL serial
cable, then turn it ON again.
At the end of the data transfer phase the instrument displays the following
messages:
“end “ for right programming.
“err” for failed programming. In this case push “SET” key if you want to
restart the programming again or remove the not programmed “Hot key”.
11. ALARM SIGNALS
Message Cause Outputs
“P1” Thermostat probe failure Alarm output ON; Compressor output
according to parameters “COn” and “COF”
“P2” Evaporator probe failure Alarm output ON; Other outputs unchanged
“P3” Auxiliary probe failure Alarm output ON; Other outputs unchanged
“HA” Maximum temperature
alarm
Alarm output ON; Other outputs unchanged
“LA” Minimum temperature
alarm
Alarm output ON; Other outputs unchanged
“EE” Data or memory failure Alarm output ON; Other outputs unchanged
“dA” Door switch alarm Alarm output ON; Other outputs unchanged
“EAL” External alarm Alarm output ON; Other outputs unchanged
“BAL” Serious external alarm Alarm output ON; Other outputs OFF
“PAL” Pressure switch alarm Alarm output ON; Other outputs OFF
The alarm message is displayed until the alarm condition is recovery.
All the alarm messages are showed alternating with the room temperature except
for the “P1” which is flashing.
To reset the “EE” alarm and restart the normal functioning press any key, the “rSt”
message is displayed for about 3s.
11.1 SILENCING BUZZER / ALARM RELAY OUTPUT
If “tbA = y”, once the alarm signal is detected the buzzer and the relay are is
silenced by pressing any key.
If “tbA =n”, only the buzzer is silenced while the alarm relay is on until the alarm
condition recovers.
Buzzer is mounted in the T820 and T821 keyboards and it is an option.
11.2 “EE” ALARM
The
dIXEL
instruments are provided with an internal check for the data integrity.
Alarm “EE” flashes when a failure in the memory data occurs. In such cases the
alarm output is enabled.
11.3 ALARM RECOVERY
Probe alarms : “P1” (probe1 faulty), “P2” and “P3”; they automatically stop 10s after
the probe restarts normal operation. Check connections before replacing the probe.
Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat
temperature returns to normal values or when the defrost starts.
Door switch alarm “dA” stop as soon as the door is closed.
External alarms “EAL”, “BAL” stop as soon as the external digital input is disabled
“PAL” alarm is recovered by switching OFF the instrument.
12. TECHNICAL DATA
T820 and T821 keyboards
Housing: self extinguishing ABS.
Case: facia 38x185 mm; depth 23mm
Mounting :
panel mounting in a 150x31 mm panel cut-out with two screws. ∅3 x 2mm.
Distance between the holes 165mm
Protection: IP20.
Frontal protection: IP65 with frontal gasket mod RG-L. (optional)
Connections: Screw terminal block ≤2,5 mm2heat-resistant wiring and 6,3mm
Power supply: from XW270K or XW271K power module
Display: 3 digits, red LED, 14,2 mm high.
Optional output: buzzer
Power modules XW270K and XW271K
Case:
“OS”: open board 132x 94 mm; height: 40mm.
“OA”: open board with aluminium protection 176x 123mm; height: 52mm.
“GS”: case 155x114; height 70mm. Self extinguishing ABS. IP55
“PS”: case 147x110; height 47mm. Self extinguishing ABS. IP55. UL approved
Connections: Screw terminal block ≤2,5 mm2heat-resistant wiring and 6,3mm
Faston
Power supply: 230Vac or. 110Vac ±10%
Power absorption: 10VA max.
Inputs: 3 NTC probes
Digital inputs: 2 free voltage
Relay outputs: Total current on loads MAX. 20A
compressor: relay SPST 20(8) A, 250Vac
light: relay SPST 16(3) A, 250Vac
fans: relay SPST 8(3) A, 250Vac
defrost: relay SPST 8(3) A, 250Vac
alarm: SPST relay 8(3) A, 250Vac
auxiliary (XW270K): SPST relay 16(3) A, 250Vac
heater (XW271K): SPST relay 16(3) A, 250Vac
Serial output : TTL standard. RS485 optional
Communication protocol: Modbus - RTU
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B.
Pollution grade: normal
Software class: A.
Operating temperature: 0÷60 °C.
Storage temperature: -25÷60 °C.
Relative humidity: 20÷85% (no condensing)
Measuring and regulation range: NTC probe: -40÷110°C (-58÷230°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0,5 °C ±1 digit
13. CONNECTIONS
13.1 XW270K / XW271K
(*) In XW271L, AUX is an anticondensing heater
Connector
number
Description Connector
number
Description
HOT KEY Hot key for programming 11 - 12 Alarm relay
RS485
(Optional)
RS485 direct output 13 - 14 Compressor relay
KEY (+) + :connection for keyboard 15 Phase
KEY (-) - : connection for keyboard 16 Neutral
1 – 2 Display probe 17 - 18 Light relay
3 - 4 Defrost probe 19 - 20 Defrost relay
5 - 6 Room probe 21 - 22 Fan relay
7 - 8 Configurable digital input 18 -19 Auxiliary relay
9 - 10 Door switch
14. DEFAULT SETTING VALUES
Label Name Range Default Level
REGULATION °C/°F XW270K XW271K
Set Set point LS÷US -5/23 Pr1 Pr1
Hy Differential 0,1÷25,5 °C
1÷45°F
2/4 Pr1 Pr1
LS Minimum set point -50,0°C÷SET
-58°F÷SET
-30/-22 Pr2 Pr2
US Maximum set point SET ÷ 110°C
SET ÷ 230°F
20/68 Pr2 Pr2
OdS Outputs activation delay
at start up
0÷255 min. 1 Pr2 Pr2
AC Anti-short cycle delay 0÷30 min. 1 Pr1 Pr1
CCt Compressor ON time
during fast freezing
0 ÷ 23h 50 min. 0 Pr2 Pr2
COn Compressor ON time
with faulty probe
0÷255 min. 15 Pr2 Pr2
COF Compressor OFF time
with faulty probe
0÷255 min. 30 Pr2 Pr2
DISPLAY
CF Temperature
measurement unit
°C ÷ °F °C/°F Pr2 Pr2
rES Resolution
(integer/decimal point)
in ÷ de de Pr1 Pr1
Lod Local display P1 ÷ 1r2 P1 Pr2 Pr2
Red Remote display P1 ÷ 1r2 Pr2 Pr2
DEFROST
tdF Defrost type rE, rT, in rE Pr1 Pr1
EdF Defrost mode In, Sd In Pr2 Pr2
SdF Set point for SMART
DEFROST
-30 ÷ +30°C
-22÷+86°F
0 Pr2 Pr2
dtE Defrost termination
temperature
(1°Evaporator)
-50,0÷110°C
-58÷230°F
8/46 Pr1 Pr1
IdF Interval between defrost
cycles
1÷120h 6 Pr1 Pr1
MdF (Maximum) length for 1°
defrost
0÷255 min. 30 Pr1 Pr1
dFd Displaying during
defrost
rt, it, SEt, dEF,
dEG
it Pr2 Pr2
dAd MAX display delay after
defrost
0÷255 min. 30 Pr2 Pr2
Fdt Draining time 0÷60 min. 0 Pr2 Pr2
dPO First defrost after start
up
n ÷ y n Pr2 Pr2
dAF Defrost delay after fast
freezing
0 ÷ 23h 50 min. 2 Pr2 Pr2
FANS
FnC Fans operating mode C-n, C-y, O-n, O-y O-n Pr2 Pr2
Fnd Fans delay after defrost 0÷255 min. 10 Pr2 Pr2
Label Name Range Default Level
FSt Fans stop temperature -50,0÷110°C
-58÷230°F
2/35 Pr2 Pr2
ALARMS
ALC Temperature alarms
configuration
rE÷Ab rE Pr2 Pr2
ALU MAXIMUM temperature
alarm
-50,0÷110°C
-58÷230°F
10/20 Pr1 Pr1
ALL minimum temperature
alarm
-50,0÷110°C
-58÷230°F
10/20 Pr1 Pr1
AFH Temperature alarm and
fan differential
0,1÷25,5 °C
1÷45°F
2/4
ALd Temperature alarm
delay
0÷255 min. 15 Pr2 Pr2
dAO Delay of temperature
alarm at start up
0 ÷ 23h 50 min. 1,3 Pr2 Pr2
EdA Alarm delay at the end
of defrost
0÷255 min. 30 Pr2 Pr2
dot Delay of temperature
alarm after closing the
door
0÷255 min. 15 Pr2 Pr2
dOA Open door alarm delay 0÷255 min. 15 Pr2 Pr2
tBA Alarm relay silencing y ÷ n y Pr2 Pr2
nPS Pressure switch
activation number
0÷15 0 Pr2 Pr2
ANALOGUE INPUTS
Ot Thermostat probe
calibration
-12,0÷12,0°C
-21÷21°F
0 Pr1 Pr1
OE Evaporator probe
calibration
-12,0÷12,0°C
-21÷21°F
0 Pr2 Pr2
O3 Auxiliary probe
calibration
-12,0÷12,0°C
-21÷21°F
0 Pr2 Pr2
P2P Evaporator probe
presence
n ÷ y y Pr2 Pr2
P3P Auxiliary probe
presence
n ÷ y n Pr2 Pr2
HES Temperature increase
during the Energy
Saving cycle
-30÷30°C
-22÷86°F
0 Pr2 Pr2
DIGITAL INPUTS
Odc Open door control no, Fan, CPr, F_C Fan Pr2 Pr2
I1P Door switch polarity CL÷OP CL Pr2 Pr2
I2P Configurable digital
input polarity
CL÷OP CL Pr2 Pr2
i2F Digital input
configuration
EAL, bAL, PAL,
dFr, AUS, ES, OnF
EAL Pr2 Pr2
dId Digital input alarm delay 0÷255 min. 5 Pr2 Pr2
SAA Set point for anti-
condensing heater
-50,0÷110°C
-58÷230°F
-20.0/4 - - - Pr2
OTHER
Adr Serial address 0÷247 1 Pr1 Pr1
rEL Software release - - - 1.0 Pr2 Pr2
Ptb Map code - - - - - - Pr2 Pr2
Prd Probes display Pb1÷Pb3 - - - Pr2 Pr2
Pr2 Access parameter list - - - - - - Pr2 Pr2
- - -
Dixell s.r.l. Via dell’Industria, 27 - 32010 Z.I Pieve d’Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13



Leg.Man.Uso Man.ENG-CIAM-13/2012-R02
AGD
AEL
AP
CA
CAR
CE
CN
CO
D
DEV
DR
EM
EV
F
FD
FLU
FR
HL
I
IEC
IGD
II
IL
IMC
INV
IR
IRP
IV
KM
LF
LI
LIA
LIG
LIP
MDIG
MM
MUC
PA
PD
PO
QE
QF
R
RADD
RE
REL
REP
RES1
RES2
RES3
RES4
RES5
RES6
RES7
RES8
RES9
RES10
RES11
RES12
RES13
RES14
RES15
RES16
RES17
RES18
RES19
RES20
RES21
RES22
RES23
RES24
RES25
RES26
RES27
DIGITAL FLAVOURS DISPLAY FEEDER
ELECTRONIC BALLAST
SERVICE VALVE
SUPPLY CABLE
AIR CONDENSER
ELECTRONIC CONTROL
MULTIPOLAR CONNECTOR
COMPRESSOR
DIOD
SHUNT
REMOTE DISPLAY
PHOTOCELL EMITTER
EVAPORATOR
FUSE
FILTER DRIER
WATER FLOW SWITCH
COMPRESSOR THERMAL PROTECTION
COMPRESSOR ALARM LIGHT
GENERIC SWITCH
WATER EVAPORATION BIN SWITCH
DIGITAL FLAVOURS DISPLAY
LIGHTING SWITCH
SIGHT GLASS
WARM SHELF SWITCH
INVERTER
REFRIGERATION SWITCH
LIGHT REFRIGERATION SWITCH
INTERNAL FAN SWITCH
CONTACTOR
FRONT LIGHTING
INTERNAL UPPER LIGHTING
FRONT LIGHTING
FLAVOURS DISPLAY LIGHTING
REAR LIGHTING
DIGITAL MODULE FOR FLAVOURS DISPLAY
SPINNING SHELVES ELECTRIC MOTOR
CONDENSING UNIT ELECTRIC CONNECTIONS
HIGH PRESSURE CONTROL
HIGH-LOW PRESSURE CONTROL
WATER PUMP
EXTERNAL ELECTRIC PANEL
MAGNETIC-THERMIC SWITCH
LIGHTING BALLAST
RECTIFIER
GENERIC RELAY
ELECTRONIC BALLAST
ELECTRONIC CONTROL TEMPERATURE REPEATER
COLD AIR DISCHARGE HEATING ELEMENT
FRONT PROFILE HEATING ELEMENT
RIGHT/LEFT GLASS HEATING ELEMENT
FRONT GLASS HEATING ELEMENT
DEFROST HEATING ELEMENT
WATER EVAPORATION HATING ELEMENT
TOP LIGHTING FIXTURE HEATING ELEMENT
LATERAL GLASS SUPPORT HEATING ELEMENT
FRONT BAND HEATING ELEMENT
COUPLING BAND HEATING ELEMENT
SERVICE TOP HEATING ELEMENT
UPPER BAND/DOOR FRAME HEATING ELEMENT
HOT DRY/BAIN MARIE DISPLAY HEATING ELEMENT
ANTI-FOG SUCTION AIR BAND HEATING ELEMENT
WARM SHELF HEATING ELEMENT
SIDE BANDS/ FRONT GLASS HINGE HEATING ELEMENT
DEHUMIDIFICATION HEATING ELEMENT
DEFROSTING WATER DRAIN HEATING ELEMENT
RING FRAME HEATING ELEMENT
SIDE BAND HEATING ELEMENT
SUCTION AIR GLASS HEATING ELEMENT
OUTLET AIR HEATING ELEMENT
REAR GLASS HEATING ELEMENT
INTERNAL GLASS HEATING ELEMENT
FRONT GLASS UPPER FRAME HEATING ELEMENT
FRONT GLASS LATERAL/LOWER FRAME HEATING
ELEMENT
FRONT GLASS LATERAL FRAME HEATING ELEMENT
RES28
RES29
RES30
RES31
RES32
RES33
RES34
RES35
RES36
RES37
RES38
REV
REVC
RI
RIC
RICV
RIS
RL
RLA
RO
SAA
SC
SD
SDC
SE
SEC
SFV
SIDG
SL
SLA
SPC
SPMC
SPR
SPS
SS
ST
STR
SU
T
TI
TC
TE
TER
TF
TMC
TP
TRA
TRC
TREV
TS
TVC
V
VC
VEC
VES
VI
VPA
VR
VRA
VRE
VS
VSA
VSAB
VSIC
VSL
VSS
VT
VV
X1
X2
X3
FRONT GLASS LOWER FRAME HEATING ELEMENT
FRONT GLASSES COUPLING PROFILE HEATING ELEMENT
DOORS FRAME MIDDLE POST HEATING ELEMENT
GLASSES PERIMETRAL FRAME HEATING ELEMENT
HEATED DOORS HEATING ELEMENTS
WATER DRAIN HEATING ELEMENT
DOORS FRAME HEATING ELEMENT
COMPRESSOR CRANKCASE HEATING ELEMENT
FRONT GLASS FRAME HEATING ELEMENT
CABINET FRAME HEATING ELEMENT
HOT COMPARTMENT HEATING ELEMENT
CONDENSER FAN SPEED CONTROL
CONDENSER FAN RELAY
REFRIGERANT TAP
COMPRESSOR DELAYER
PHOTOCELL RECEIVER
RESERVE , ANTI-FOG HEATER ELEMENT
LIQUID RECEIVER
WATER LEVEL ELECTRONIC CONTROL
OIL HEATER ELEMENT
ABSENCE OF WATER LIGHT
CONDENSER PROBE
TERMINAL BOX
COMPRESSOR TERMINAL BOX
PROXIMITY SENSOR
MAIN SWITCH
TANK BOTTOM HEATING COIL
FLAVOURS DISPLAY DIGITAL SYSTEM
LIQUID SEPARATOR
WATER LEVER PROBE
COMPRESSOR LIGHT
WARM SHELF LIGHT
ELECTRIC SUPPLY LIGHT
DEFROSTING LIGHT
DEFROSTING PROBE
TEMPERATURE PROBE
LIGHTING STARTER
HUMIDITY PROBE
TEMPERATURE CONTROL
WINTER THERMOSTAT
CAPILLARY TUBE
TIMER
THERMOMETER
FUSIBLE PLUG
WARM SHELF THERMOSTAT
LIGHTING FIXTURES REGRIGERATOR THERMOSTAT
TRANSFORMER
ELECTRONIC CONTROL TRANSFORMER
WATER EVAPORATION HEATER ELEMENT THERMOSTAT
SECURITY THERMOSTAT
CONDENSER FAN THERMOSTAT
COMPRESSOR FAN / GENERAL USE
CONDENSER FAN
WATER EVAPORATION BIN
EXPANSION VALVE
INTERNAL FAN
CONDENSING PRESSURE CONTROL WATER VALVE
CHECK VALVE
SUCTION PRESSURE REGULATION VALVE
EVAPOTATING PRESSURE REGUTATION VALVE
GENERAL USE SOLENOID VALVE
SOLENOID WATER VALVE
BY-PASS SOLENOID WATER VALVE
REVERSING CYCLE SOLENOID VALVE
LIQUID SOLENOID VALVE
DEFROSTING SOLENOID VALVE
POWER REGULATOR
GLASS FAN
CABINET CONNECTIONS
EXTERNAL ELECTRIC PANEL CONNECTIONS
CONDENSING UNIT CONNECTIONS
Table of contents
Popular Commercial Food Equipment manuals by other brands

Electrolux Professional
Electrolux Professional thermaline MAYA DOBO Series Installation and operating manual

Adventys
Adventys MO2I user guide

Lotus
Lotus LIBR.ISTR.BM110E Installation and operating instructions

Vollrath
Vollrath FC-4SH Operator's manual

Meris
Meris THAYA operating manual

BRIKA
BRIKA BSP-12 product manual