CIAT V300 Use and maintenance manual

Control manual
Zone timer
V300
01 - 2015
NA 14.13 A


EN
EN - 1 N 14.13 A
CONTENTS PAGE
1 CENTRALISED MANAGEMENT BY ZONE TIMER FOR COMFORT UNIT 2
1.1 Operating principle: 2
2 SCHEMATIC DIAGRAM 2
3 ZONE TIMER USER TERMINAL 3
4 DETAILS OF ZONE TIMER SCREEN 3
5 V300 ZONE TIMER PARAMETERS AND DIAGNOSTICS 4
6 PARAMETER TABLE 5
7 DIAGNOSTIC TABLE 7
8 OPERATING DATA 7
9 BUS WIRING/TOPOLOGY 7
9.1 Precautions: 7
10 GENERAL TREE STRUCTURE FOR THE DIFFERENT MENUS 10
11 MAIN MENUS 11
11.1 Screens 11
11.2 Settings: 13
12 ZONE TIMER CONTROLLER & TERMINAL DIMENSIONS 18
13 TECHNICAL SPECIFICATIONS 19
Original text: French Version

EN - 2 N 14.13 A
1 CENTRALISED MANAGEMENT BY ZONE TIMER FOR COMFORT UNIT
The comfort units (ductable, air handling units or cassettes), which are all independent, are equipped with a V300 control. Each
comfort unit has its own comfort temperature sensor.
A centralised timer comprising a zone controller and a wired LCD terminal in an electrical cabinet outside the zone enable remote
centralised management of this loop. A terminal is connected to this controller for adjusting and operating the system. The timer is
integrated in this controller to ensure time management of the 4 operating modes: Comfort/Economy/Frost protection/Off.
.The terminal is used:
→Tosettheintegrateddaily/weeklytimer
→Todistributeallthecomfortunitsacross6self-containedzones
→Todetermine,foreachzone,thehourlymanagementofthe4modes(Comfort/Economy/Frostprotection/Off)
→Toset,foreachzone:
•TheheatingandcoolingComfortsetpoints
•TheheatingandcoolingEconomysetpoints
•Tooverridethetimeslotsperzone,orfortheentirebuilding.
. The controller therefore enables management of the entire building for:
→Thelocallyauthorisedsetpointshiftrange
→Adjustmentofthecomfortrestarttimeonthelocalwall-mountedterminal
→Possiblecentralchangeover
→Advanceheatingrestartbasedontheoutdoortemperature(dependingonoptions)
1.1 Operating principle:
- Each V300 is controlled by the timer for Comfort/Economy/Frost protection or Off mode depending on the defined time
schedule.
-TheV300sconnectedtothetimercanbespreadacrossamaximumof6independentzones
-Inlocalmode,theuserhascompletecontrolovertherunningofthecomfortunitviathewall-mountedcontrolterminal.
A) V300 in Comfort mode according to the timer program
.Theusercanswitchoffthecomfortusingthelocalterminal:Offkeycorrespondingtoafrostprotectionmode(configurable*)
.ThecomfortunitwillrestartinComfortmodethenexttimeitreceivestheComfortcommandsignalfromthetimerorifthelocal
terminalisactivated.
B) V300 in Economy, Frost protection or Off mode according to the time schedule (night, weekend operation, etc.)
.The user can stop the comfort unit using the local terminal
.The comfort unit stops either when the wall-mounted terminal is activated or automatically if local action is set to a timer
(configurationofstandbybuttononthelocalterminal*)
*TheseconfigurationsareaccessedusingtheCIATterminalwithdisplay.Procedureaspertableonp5
2 SCHEMATIC DIAGRAM
V300
controller
Electrical cabinet
Zone timer
V300 terminal V300 terminal V300 terminal
Sensor
Sensor
Sensor
Sensor
V300 integrated
"Individual"
controller
V300 integrated
"Slave"controller
V300 integrated
"Master" controller
V300 integrated
"Individual"controller
Office 1 Office 2 Office 3
Toanotheroffice/IndividualorMaster
V300 controller (30 max.)
Maximum:30offices(correspondingtoMasterand/orindividualunits)
(1)Zonetimeruserterminalfordaily/weeklytimeschedulingover6zones
(2)C/O:Changeoversensorfor2-tubereversibleHeating/Coolingapplicationinthecaseofacentralchangeover
(3)SensoronthereturnofSlaveunits:twocontroloptionspossibleviaparameters:
→Sensordisabled:theslavecontrolsusingthetemperatureinformationmeasuredbytheMaster
→Sensoractivated:theslavecontrolsusingitsownreturntemperatureinformation(inthecaseoflargeopenplanoffices)

EN
EN - 3 N 14.13 A
(4)ContactinputstooverridetheinstallationinComfort/Economy/FrostprotectionorOffmode(priority)
(5)Authorisingoperationoftheelectricheatersonthecomfortunits(forbypass,etc.)
(6)230Voutputforautomaticoperationcontrol(On/off)ofancillaryequipment(AHU,extractors,etc.)
(7)Outdoortemperaturesensoroption(activationlimitforelectricheatersoncomfortunitsand/oradvanceheatingrestart).
(8)RS485communicationbus:2shieldedtwistedpairsforconnection
→Terminal–Controller
→MasterandSlavecontrollers
→Zonetimer–MasterorIndividualcontroller
1) Display:
The permanent display shows:
- The current time and day
-Thegeneralstateofthebuilding(AutoorOverrideinprogress)
-Thestateofthecentralchangeover(ifoptionincluded)
- The number of zones declared in the building
2)Navigationkeys: / These are used to enter settings (parameters, diagnostics, settings, etc.)
3)Validationkey , this is used to conform the settings entered
4) MENUkey.Thisisused:
- To select the All Zones, Zones x, Schedule settings menus, etc.
- To exit the selected menus.
Zonenumber(1to6)
(Zoneno.1.6correspondstothe"auxiliary"zone)
→Fixeddisplay=zonecontrolledbytimeschedule
→Flashingdisplay=manualoverrideorviacontactD2inprogress
Auto: at least one of the zones is
controlledbythetimeschedule*
At least one of the zones has
overriddenthetimeschedule
Time
7daysoftheweek
(Wednesday in this example)
: Indicates Comfort mode
: Indicates Economy mode
: Indicates Frost protection mode
: Indicates Off mode
:Ifthechangeoveriscentral,indicatesthattheinstallationisin
Cooling mode
or
adjustment of Cooling setpoints (Comfort and Economy)
:Ifthechangeoveriscentral,indicatesthattheinstallationisin
Heatingmode
or
adjustmentofHeatingsetpoints(ComfortandEconomy)
*Note:Thetimerhasadefaulttimescheduleforeachdeclaredzone:seepp11&16
3 ZONE TIMER USER TERMINAL
4 DETAILS OF ZONE TIMER SCREEN

EN - 4 N 14.13 A
Functions:
▪Daily/weeklytimeracross6independentzones(forsettingseepages11&16)
▪Forcinganoperatingmodefortheentireinstallationviapotential-free(dry)contactinD2
-Inthiscase,theentireinstallationwillbeforcedtooperateinthemodedefinedbytheconfigurationofinputD2(seeP65)
-Thelogoforthedefinedoverridemode+thezonesflash+the logo appears
▪Operatingauthorisationforthecomfortunitelectricheaters:viacontactoninputD1
(Bypass, heating authorisation by Joule effect, etc.)
▪Centralchangeover(dependingonOptions)andconfiguration(seeP60/P47)
- Via contact on input "S2-┴" (terminal 33-34)
Open=coolingoperatingorClosed=heatingoperation
- Via CO sensor to be wired to input "S2-┴" (terminal 33-34)
▪Outdoortemperaturesensor(dependingonoptions)
- To be wired to sensor S1-┴(terminal 31-32)
-Enables:1)activationlimitforelectricheatersonthecomfortunits
2)theinstallationtobestartedinadvanceforheating
▪230V–10Amax.contactoutputslavedtoatimeschedule(auxiliarycontrol):
The230VEHoutputisthenconsideredasaseparatezoneandcanbeswitchedON/OFFbythetimescheduleforthiszone(e.g.
start-upofauxiliaryequipment:extractor,fan,etc.).Thiszoneappearsas"Zone16"onthedisplay.
▪Displaykeyslocked(securingaccesstooperatetheinstallation,etc.)
5 V300 ZONE TIMER PARAMETERS AND DIAGNOSTICS
▪Twolevelsareavailable:
-Level1:settings
-Level2:systemstart-up
Level2"Systemstart-up"mustbeusedwithcare:thesesettingsconfiguretheinstallation,thereforemodificationsmustonly
bemadewithfullknowledgeofthesituation.Ciatacceptsnoresponsibilityforoperatingmalfunctionsontheinstallation
resulting from incorrect configuration
▪Level 1 "Settings" access:
- From the main screen
- Press and hold the and keyssimultaneouslyfor5seconds
- Select the configuration with the and keys
- Consult the parameter with the
key
- Confirm a parameter modification:
-Exitparametermode:MENU
▪Access level 2 "System start-up":
-Fromlevel1
- Press and hold the and keyssimultaneouslyfor5seconds
- Consult the parameter with the
key
- Confirm a parameter modification:
-Exitparametermode:MENU
▪Access to diagnostics:
- From the main screen
-PressandholdtheMENUand keyssimultaneouslyfor5seconds
- Select the diagnostic with the and keys
- Consult the diagnostic with the
key
-Exitdiagnosticmode:MENU
▪Locking the display keys:
- Press and hold the andMENUkeyssimultaneouslyfor5seconds
-Timedisappearsbriefly/thekeypadislocked
-Sameprocedureasforunlocking

EN
EN-5 N14.13A
6 PARAMETER TABLE
Settings Name Explanation Setting
range
Default
value
Access
Setting Commissioning
P06 Comfort setpoint setting range Rules for maximum +/- shift of the setpoint for room units
0.0...9.0
resolution
defined by
P07
4.0 x x
P07 No comfort setpoint
adjustment
Defines the display resolution for the comfort setpoint
shift on the room units 0.5 : 1.0 1.0 x x
P08 Operating mode activated by
sleep key on user terminal
0 = Comfort →Off
1 = Comfort →Frost protection
2 = Comfort →Economy
3 = Comfort →Eco →Frost protection →Off →
Comfort
0...3 1 x x
P09 Temperature displayed on
terminal
Actual temperature display on the indoor environment
device LCD:
1 = Setpoint
2 = Measurement
1 : 2 2 x x
P10 Setpoint offset value display
Display of actual temperature offset value:
1 = Not displayed (bar chart)
2 = Display offset + bar chart
3 = Display setpoint + bar chart
1 : 2 : 3 1 x x
P11 Temperature sensor selection
(if recycled air application)
Control sensor selection
0 = Return sensor priority
1 = Master room sensor priority
0 : 1 1 x
P18 Number of fan speeds 0 = 3 speeds in all modes
1 = 3 speeds in comfort mode/2 speeds in reduced mode 0 : 1 0 x x
P19 Deadband ventilation
0 = Ventilation off in all modes
1 = Periodic restarts in comfort mode/off in economy and
frost protection mode
2 = Periodic restarts in all modes
3 = Permanent ventilation in comfort mode/off in
economy and frost protection mode
4 = Permanent ventilation in comfort mode/periodic
restarts in economy and frost protection modes
5 = Permanent ventilation in cooling comfort mode/off in
heating comfort, economy and frost protection mode
6 = Permanent ventilation in cooling comfort mode/
periodic restarts in heating comfort, economy and
frost protection modes
7 = Permanent ventilation in cooling comfort mode/
periodic restarts in heating comfort/off mode
0...7 0 x
P20 Electric heater operation
0 = Electric heater disabled
1 = Electric heater in main heating mode only
2 = Auxiliary electric heater only
3 = Electric heater in main heating + auxiliary mode
0 : 1 : 2 : 3 3 x x
P47 Local input function S2 on
V300s
1 = Local changeover (sensor or contact)
2 = Hot water present
3 = Cold water present
4 = Heating/cooling authorisation
5 = Electric heater authorisation
1...5 1 x
(accessible if P60 = 0)
P48 Local changeover high
threshold
Two-tube changeover high threshold for detection
of hot water (in relative value compared to room or return
temperature)
0...20 7 x
(accessible if P47 = 1)
P49 Local changeover low
threshold
Two-tube changeover low threshold for detection of
cold water (relative value compared to room or return
temperature)
-20...0 -4 x (accessible if P47 = 1)

EN-6 N14.13A
Settings Name Explanation Setting
range
Default
value
Access
Setting Commissioning
P54 Time delay for override to a
higher mode
Length of the override when the user selects a mode
higher than the zone timer mode. May be set to remain
on at all times, to turn on for a specific period, or be
disabled.
For overrides to a lower mode, the override is never
delayed
0 = Override prohibited
1...12 = Length of override in hours
13 = Unlimited override
0...13 4 x x
P55 Back to factory settings
0 = Normal operation
1 = Storing parameters as factory values
2 = TMZ returns to factory values the next time the
param menu is exited (P60 to P73 + setpoints + time
schedule).
3 = Entire building returns to factory values (same as
P55 = 2 + transfer of all parameters from the 1st
System start-up column)
0...3 0 x
P60 Input S2 function
0 = Not used (in this case: set P47)
1 Central changeover
2 = Heating/cooling authorisation for 4-tube or 2-tube
cooling + 2-wire applications
0 : 1 : 2 0 x
P61 Central changeover high
threshold
High threshold for detection of hot water 15...40 27 x
(accessible if P60 = 1)
P62 Central changeover low
threshold
Low threshold for detection of cold water 5...25 17 x
(accessible if P60 = 1)
P63 Action direction of input D1
(electric heater authorisation)
0 = Normally open
(open = authorised, closed prohibited)
1 = Normally closed
(closed = authorised, open = prohibited)
0 : 1 0 x
P64 Action direction of input D2 0 = Normally open
1 = Normally closed 0 : 1 0 x
P65 Input D2 function
0 = Forced Off
1 = Forced frost protection
2 = Forced Economy
3 = Forced Comfort
0...3 1 x
P66 Number of CU zones Number of zones 1...6 6 x
P67 Automatic operation control
zone (ZONE 1 6)
0 = No automatic operation control
1 = Automatic operation control on EH output (EH closed
in comfort mode, open for other modes)
0 : 1 0 x
P68 Forced automatic operation
control
Determines the behaviour of the EH output if input D2 is
activated
0 = EH output not affected by forcing (retains state
corresponding to the time schedule)
1 = Affected by forcing of input D2
0 : 1 1 x
P69 Advance comfort restarts
0 = No advance
1...10: Value representing inertia of the building
(1 = Building with low inertia, 10 = building with high
inertia)
0...10
increments
of 1
5 x
P70 Building equilibrium
temperature
Outdoor temperature from which comfort restarts must
be advanced -35...+20 12 x
P71 Base temperature
Lowest outdoor temperature for calculating the limitation
of the electric heater power and the length of comfort
restarts.
-35...+5 -10 x
P72 Excess capacity difference
Temperature difference (°C) between the real energy
limitation curve and the theoretical energy limitation
curve
0...5
increments
of 0.5
1.0 x
P73 Installation reset
0 = Normal operation
1 = Transfer all parameters sent during first powering up 0 : 1 0 x

EN
EN - 7 N 14.13 A
7 DIAGNOSTIC TABLE
Settings Name Explanation Setting range
d10 Outdoor temperature Temperature supplied by the sensor connected to analogue input S1 Read-only
d11 Central changeover
0 = No central changeover
1 = Hot water
2 = Cold water
3 = Water neither hot nor cold
Read-only
d12 Heat/cold authorisation
0 = No pilot line (heating and cooling authorised)
1 = Heating authorisation only
2 = Cooling authorisation only
Read-only
d13 Electric heater authorisation 0 = Electric heater disabled Read-only
d14 Software version Read-only
8 OPERATING DATA
ThefollowingvaluesaresentbythezonetimertoeachV300controllerwhenthesystemisfirstpoweredupandeachtimethe
valuechanges:
- Comfort setpoints
- Economy setpoints
- Operating mode
- % limitation of the electric heaters (depending on the option)
-Changeoverstate
Sent periodically:
- Operating mode
- % limitation of the electric heaters (depending on the option)
-Changeoverstate
9 BUS WIRING/TOPOLOGY
9.1 Precautions:
Intheinterestofsafetyandtoeffectivelycombatinterference,thewiringinaninstallationwithdigitalconnectionsmustmeeta
numberofbasicrulesthataimtoestablishacommonbondingnetwork,meshedandconnectedtoearth.
A) Zone controller/Zone terminal
-RS485bus,4wires+shielding
-Polaritytobeobserved(withdenominationA=+andB=-)onthesametwistedpair
-Shieldingtobefittedalongtheentirelengthandconnectedatthecontrollerandterminalend(via┴terminals)
-Maximumdistance=30m
-FilotexFMA-2Ptypebuscable,Belden2pairsref.9842/9842NH24AWGorequivalent(2shieldedtwistedpairs)
-Seediagram7415353
L
230/1/50
N
21 2220 23
20 21
LN
01 02 03 04 05
V300
22 23
5V A B
31 32 33 34
S1
27 28 29 30
D1
24 25 26
A
B
V300
D2 S2
06 07
EH
10A
TMZ
A
D
K
N 1
2
Q
KE KD
BSE BSA With changeover
sensor
BOILER
ROOM
MECHANICAL
ROOM
SELF-
CONTAINED
UNIT
To V300
Brown
Blue
Blue
Brown
CONTROLLER POWER SUPPLY
POWER IN
230 V

EN - 8 N 14.13 A
B) Zone controller to "Individual" or "Master" controllers
-RS485bus,2wires+shielding
-Polaritytobeobserved(withdenominationA=+andB=-)onthesametwistedpair
-Shieldingcontinuitytobeensuredalongtheentirelength(via┴terminalsofthecontrollers)
- Max. total length of the bus: 200 m (see below)
-NumberofMasterorIndividualV300controllers:30max.
-FilotexFMA-2Ptypebuscable,Belden2pairsref.9842/9842NH24AWGorequivalent(2shieldedpairs)
- Topology:
•Zonetimermustbeplacedattheheadofbus
•Ideal:Serialbus/totalbuslength=200mmax.
or•Acceptable:MaindorsalL=200mmax.withmax.5mlongbranchtoconnecteachmasterorindividualunit.
•Starorloopprohibited
- Junction box for branches
•Thecableconnectiontothejunctionconnector(perpair)mustmatchthepolarity
•Theshieldingmusthavecontinuityinthejunctionbox
•Itisprohibitedtouseboxescarrying230Vorstrongcurrent
•Seeschematicdiagramonp10
-Topreventcablereflectioncausedbylongdistances,werecommendinstallinga120Ω+/-5%¼wradialresistoronthelast
controller (the furthest from the zone timer) on terminals A-B
- Ideal topology:
T
A+ 24
B- 25
T
V300
A+ 24
B- 25
A+
24
B-
25
r
26
V300
A+
24
B-
25
r
26
V300
200 m maxi
Shielding
Zone
timer
- Acceptable topology:
T
V300
A+ 24
B- 25
T
A+ 24
B- 25
A+
24
B-
25
r
26
V300
A+
24
B-
25
r
26
V300
200 m maxi
5 m
Shielding
Zone
timer

EN
EN - 9 N 14.13 A
- Wiring details:
Note:Asseveralwiresareconnectedtothesameterminal,checkthattheyarecorrectlytwistedbeforeinsertingtheminthe
corresponding terminal.
C) Wiring modifications (e.g. repartitioning offices)
-Thebuscablecanbe"cut"andthenewunit,whichhasbecometheMasterorIndividualunit,branchsupplied(observethe
shieldingpolaritiesandcontinuity):thenewbranchcreatedmustnotexceed5m.
-Buscabletobeconnectedtothe"Slave"input,24-A/25-Bterminalsonthenewunit
FIRST START-UP
1/ Preset the zones on the comfort units: see below
2/ Declare the number of zones on the timer: see below
3/Checkthed08oneachComfortunit(d08=1communicationOK:usedtocheckthatalltheunitsarecorrectlyconnectedto
thezonetimerandthattheyarereceivingthesettingsentered.
4/Setthegeneraltimer:Hours-minutes-dayoftheweek:seep20(§4SettingtheTimer)
5/Setthetimeslotsforeachzoneifnecessary:seebelowandp15(§1TimeSetting)
Declaring the zones (6 maximum)
A) On each V300 controller for the Master or Individual comfort units:
-SettheP01"Zonenumber"correspondingtothedesiredzone(manualN12-53)
-AlltheunitsonwhichP01=1willbeassignedtozone1,etc.
B) On the zone timer:
-SetthecorrespondingP66"Numberofzones"(see"Systemstart-up"level/default:6zones)
-P67allowsanadditionalzone,calledzone"1-6"tobedeclaredfortheon/offautomaticoperationcontrolofauxiliaryequipment
suchasanextractororchiller(via230VEHrelayoutput)
Operating mode order of priority
The operating mode adopted by the zone depends on the following priorities (in decreasing order of importance):
- Mode forced by input D2
-Modemanuallyoverriddenfromthezonetimer
- Mode defined by the time schedule
Central changeover
Thedefaultchangeover(factoryconfiguration)is:Localonthecomfortunitsandthezonetimer.
Foracentralchangeover
-Verifythepresenceofthechangeoversensoronthezonetimerontheterminal┴-S2/33-34
-ParameterP60mustbesetto1
21 2220 23
21 2220 23
20 21
LN
01 02 03 04 05
V300
22 23
5V A B
3127 28 29 30
D1
24 25 26
A
B
V300
D2
06 07
EH
10A
TMZ
20 21
LN 3A
F1
01 02 03 04 05
V300
22 23
5V A B
31
27 28 29 30
D1
24 25 26
A
BD2
06 07 08
EH
10A
21 2220 23
20 21
LN 3A
F1
01 02 03 04 05
V300
22 23
5V A B
3127 28 29 30
D1
24 25 26
A
B D2
06 07 08
EH
10A
21 2220 23
20 21
LN 3A
F1
01 02 03 04 05
V300
22 23
5V A B
31
27 28 29 30
D1
24 25 26
A
BD2
06 07 08
EH
10A
20 21
LN 3A
F1
01 02 03 04 05
V300
22 23
5V A B
31
27 28 29 30
D1
24 25 26
A
B D2
06 07 08
EH
10A
A
A
D
D
A
D
A
D
D
15mmax.
(slaves)
Slave
Master
30m max.
(individualormaster)
Individual
POWER IN
230 V
POWER IN
230 V
POWER IN
230 V
POWER IN
230 V
POWER IN
230 V
MASTER
TERMINAL SLAVE
SLAVE
MASTER
TERMINAL
MASTER
TERMINAL
MASTER
TERMINAL
Individual
Zone timer
Total length of TMZ on last master or
individualV300TMZ:200mmax.
TERMINAL
SLAVE
SLAVE

EN - 10 N 14.13 A
10 GENERAL TREE STRUCTURE FOR THE DIFFERENT MENUS
In general, the MENUkey canbe usedto navigatethrough thevarious menusand sub-menusshown belowfrom themain
screen. It can also be used to exit a menu without confirming.
The keyisusedtoentertheselectedmenuortoconfirmdatainordertoreturntothepreviousmenu.
The 》and 《keysareusedtoenterthesettingsfromamenu.
Main screen
(all zones)
MENU
MENU
MENU
MENU
MENU
Set timer
Zone16(ifpresent)
Zone xx
All zones Buildingoverride
MENU
MENU
MENU
MENU
MENU
MENU
MENU
MENU
Time schedule
Building setpoints
Zoneoverride
Zone timer prog
Zone setpoints
Zoneoverride
Zone timer prog
MENU
》or《
》or《
》or《
》or《
》or《
MENU
MENU
MENU
MENU
MENU
MENU
MENU
》or《
》or《
》or《
》or《
》or《
》or《
》or《
》or《
》or《
Time schedule
- A default time schedule exists for each zone created inthetimer(validforthexzonesdeclared)
- This time schedule corresponds to classic "Office" use
→"Comfort"modefrom07:00to18:00overthefirst5daysoftheweek
→"Economy"modefrom18:00to07:00
→"Frostprotection"modeattheweekendfrom18:00to07:00(correspondingtothelast2days).
Monday to Friday Days 1 to 5 7 : 00 Comfort
Monday to Thursday Days 1 to 4 18 : 00 Economy
Friday Day 5 18 : 00 Frost protection
→Thesetimeslotsaredeclaredbydefaultatzonelevel
→ThereisnotimeslotdefinedatBuildinglevel(allzones)
→Ifatimeslotiscreatedatbuildinglevel,itwilloverrideallthezonetimeslots
→Seep16(§1timesetting)forthetimeslotoptionsandsettingprocedure

EN
EN - 11 N 14.13 A
11 MAIN MENUS
Details of different menus:
▪Onthemainscreen,theMENUkeyisusedtosuccessivelyselectandviewthestateofallzones,eachdeclaredzone,thenzone
16ifithasbeendeclared(theZONEindicatorflashes).TheMENUkeycanthenbeusedtoaccessthe"settimer"menu,before
returning to the main screen.
▪Thekeyisusedtoentertheselectedzonesub-menu.TheMENUkeyisusedtonavigatewithinthissub-menu,andtoreturn
to the zone's main screen.
If none of these menus is confirmed using the keywithin10seconds,thedisplayautomaticallyreturnstothemainscreen.
▪Itisalsopossibletoaccesstheparameteranddiagnosticmenusfromthemainscreen,inthesamewayasonaV300room
terminal.
→Fromthemainscreen:Accessbysuccessivelypressingthe"MENU"key
→4mainmenus:Mainscreen/AllZones/Zone1,Zone2,Zonex…/Zone1-6(ifpresent)/SetTimerscrollsuccessively.
→ThegeneralBuildingoverrideisperformedinthe"AllZones"screen
→TheOverride/Timeschedule/Setpointssub-menusareaccessiblefromthefollowingmenus:Allzones(generalbuilding
override)/Zonesx/Zone16(ifpresent)
Main screen
In this example:
•"1234"=thereare4zonesinthebuilding
•Ifthezonesarelitsteady=onthetimeschedule
•Ifthezonesareflashing=manualoverrideinprogress
•AUTO=Thebuilding isonthedefinedtimeschedule*
•Itis18:25onthe3rddayoftheperiod(Wednesday)
*Logo: AUTO/ / Zones lit steady or flashing:
•ZoneNo.steady=Operationasperthetimeschedule
•ZoneNo.flashing=ZoneoverriddenmanuallyorbycontactD2
•AUTOsymbolappearsifatleastonezoneisinAutomode.
• symbolappearsifatleastonezoneisoverridden.
Foranexistingzone1-6:
•AllzonesflashingwithAUTO:zone16inAutomode
• symbolwithallzonesfixed:Zone16overridden
"All Zones" screen
All ZONES
•1stpressonMENUkey
•"Zone"flashesandallthezonenos.aredisplayed
"Zone 1" screen
Zones X
•2ndpressonMENUkey
•"Zone"flashesandtheselectedZone1isdisplayed
•Itscurrentmodeappears: if comfort
•AUTO: if the zone is on the time schedule
•PressMENUsuccessivelytoscrollthroughthedeclaredzones:Zone2,3,
4andZone16(ifpresent)
11.1 Screens

EN - 12 N 14.13 A
"Zone 1 6" screen
ZONE 1-6 (if present)
•Thiszonecorrespondstothepresenceofauxiliaryequipment
•"Zone"flashes/theselectedZone16isdisplayed
"Set timer" screen
Set timer
•PresstheMENUkey
•Hours,minutesanddayoftheweekflash
→Ifnoneofthesemenusisconfirmed,themainscreenwillautomaticallybedisplayedafter10seconds
→TheMenukeyisusedtoreturntothemainscreen

EN
EN - 13 N 14.13 A
1) "All Zones" general setting (Building)
→Fromthislevel,allthedeclaredzoneswilladoptthetime,overrideandsetpointsettings;thesettingsenteredatzonelevel
willbeoverridden
" All zones" screen
•Fromthe"AllZones"screen(viaMenu)
•:UsedtoentertheGeneralAllZonesmenu
→Usedtodirectlyaccessthe"Override" menu
→Thelogosforthedifferentmodesflash
•MENU:usedtoscrollthroughthemenus
→Time Schedule All Zones
→AllZonessetpoints
•:Usedtoentertheselectedsub-menu
"Override" screen
All Zones override (or Building)
•thelogosforthedifferentmodesflash
•Allzoneslitsteady=settingvalidforAllzones
•:usedtoentertheOverridesub-menu
•and areusedtoselectthedesiredmodefortheoverride
alternating display of symbols , , , and
AUTO
•:Usedtoconfirmtheselectedmodewithautomaticreturntotheoverride
menu.
•MENU:usedtoexittheoverridesub-menuwithoutconfirmingthe
modification,tocontinuenavigatingandreturntothemainscreen
Main screen with "All Zones overridden"
•Logos and indicatingtheStopinprogressoverridefortheentire
building
•All the Zones flash
•Tocanceltheoverrideandreturntothetimeschedule
•Sameprocedurebyselecting"AUTO"forthemodes
Note:forageneralBuildingOverridevia contact D2:
→The"Override"sub-menuisnolongeraccessible
→ThelogoforthemodedefinedbyP65flashes
(Frost protection by default)
→Theentireinstallationisthenoverriddeninthis
operating mode
→Thezonenos.flashandthe logo is displayed
→ Time schedule (All Zones)
Before adjusting this schedule, please see below the product's default time schedule.
DefaulttimescheduleforEACHZONE:
Monday to Friday Days1to5:
▪▪▪▪▪□□ 7 : 00 Comfort
Monday to Thursday Days 1 to 4
▪▪▪▪□□□ 18 : 00 Economy
Friday Day5
□□□□▪□□ 18 : 00 Frost protection
11.2 Settings:

EN - 14 N 14.13 A
•3 different time slots
•Correspondingtoclassic"Office"typeoccupancy
→Default:ThereisnotimeslotsetforthegeneralBuildingtime:
•Atinitialstart-up,thetimeslotdisplayatthislevelis:
This allows:
•Eachzonetobeindividuallyandindependentlymodifiedifnecessary
•Modification/creationofatimeslotatBuildinglevelwilloverrideanytimeslotssetforanyofthezones
As a precaution, the MENUkeycanbeusedtocancelthemodificationinprogressandexitthetimeslotmodification
sequence
→Thetimeslotsareorganisedinascendingtimeorder(daynottakenintoaccount)
→TheMENUkeyisused:
→Toaddatimeslot:
•PressandholdMENUtoinsertanemptyslot
•Itcanbeenteredinanyorder
•Itwillbeautomaticallyreorganisedinascendingtimeorder
→Duringsetting,brieflypressingMENUcancelsthecurrentsettingandreturnstothedisplayoftheselectedtimeslot
→Tocancelapreviouslysavedtimeslot:for more than 2 seconds
→Thedefaulttimescheduledisplayisasfollows:
•Three different slots corresponding to:
•Start-upat07:00inComfortmodeover5days(MondaytoFridaymorning)
•Stopat18:00inEconomymodeover4days(MondaytoThursdayevening)
•Stopat18:00inFrostprotectionmodeonFridayevening
•Thelastscreenindicatestheendofthetimeschedule
Slotno.107:00/D1to5
Comfort
Slot no. 2 18:00/D1to4
Economy
Slotno.318:00/D5
Frost protection
End of time slots

EN
EN-15 N 14.13 A
•Scrollingthrough time slots using the and keys,forviewingonly
•Fromaflashingdisplayofatimeslot:
→Thekeyisusedtoenterandmodifythetimeslot,ifnecessary
•Tablefordefiningyournewtimeslot:
Usedtodefineyourrequirementbeforeprogrammingasdesired:
Zone no.: _______
Day of the week
concerned Corresponding Days Times Operating mode
to □□□□□□□ :□ □ □ □
to □□□□□□□ :□ □ □ □
to □□□□□□□ :□ □ □ □
to □□□□□□□ :□ □ □ □
to □□□□□□□ :□ □ □ □
to □□□□□□□ :□ □ □ □
to □□□□□□□ :□ □ □ □
to □□□□□□□ :□ □ □ □
to □□□□□□□ :□ □ □ □
to □□□□□□□ :□ □ □ □
Note: a maximum of 10 switches are possible for 1 complete time slot
Example: adding a time slot to the basic schedule:
For example:
•Timeslotfrom12:00to14:00inEcomodefromMondaytoFriday
→additionoftwotimeslots
• Programming sub-menu of the zone(s) concerned
•Firsttimeslot/screenflashing
•MENU: pressed and held
•Atimeslotisinserted,thedisplayshows:"00: 00"
•:Usedtoenterthetimeslot
• and areusedtoreviewthehours/minutes/desiredmodeand
weekdayswithconfirmationusing
Fortheweekdays, =confirmday =canceldayandmovetonext
12:00 time slot
Ecoover5d
With: 12:00/ /5days
•MENU: pressed and held
•Atimeslotisinserted,thedisplayshows:"00: 00"
•:Usedtoenterthetimeslot
• and areusedtoreviewthehours/minutes/desired mode and
daysoftheweekwithconfirmationusing
With: 14:00/ /5days

EN-16 N 14.13 A
→Thenewtimescheduleisnowdisplayedasfollows:
•Five different slots corresponding to:
→A time slot can be deleted as follows:
•Gotothetimeslottobedeleted
•for two seconds
•Thedisplaynowshows:"-- : -- " (either briefly with display of the next time slot or permanent if end of time slot)
•Theslotisdeleted
•MENU to exit
New slot
12:00
New slot
14:00
End of time slot
"All zones" setpoint adjustment (Building)
"Setpoint adjustment" screen
-ThisiswheretheHeatingComfort/CoolingComfort//HeatingEco/Cooling
Eco setpoints are set
•TheComfort andHeating logos and the current setpoint flash
•Allzoneslitsteady=settingvalidforAllzones
• and can be used to scroll through the 4 setpoints
•:UsedtosettheHEATING comfort setpoint
•OnlytheHeatingComfortsetpoint"19°C"flashes
• and canbeusedtoadjustthesetpointin0.5°Kincrements
•
:Usedtoconfirmthesetting(writingthenewsetpointinallV300sinthe
building)
"Cooling Comfort Setpoint Setting" screen
•TheComfort and Cooling logos and the current setpoint flash
•Allzoneslitsteady=settingvalidforAllzones
•:UsedtosettheCOOLING comfort setpoint:
•OnlytheCoolingComfortsetpoint"26°C"flashes
• and canbeusedtoadjustthesetpointin0.5°Kincrements
•:Usedtoconfirmthesetting(writingthenewsetpointinallV300sinthe
building)
•Applythesameprocedurefortheothersetpoints:
HeatingEco , and Cooling Eco ,
•: The last confirmation allows a return to the main screen

EN
EN - 17 N 14.13 A
2) Zones x menus:
ThismenuallowsindividualadjustmentofeachZonefor:
→Itstimeslot
→Itsmanualoverride
→Itssetpoints
Ifsettingshavepreviouslybeenenteredatthe"AllZones"level,theywillbeoverriddenforthiszone
→Theoperationsforenteringthesesettingsareidenticaltothe"AllZones"menu(seeabove)forthepreviouslyselected
zone
Main screen with Zone 1 overridden
•ExampleofamainscreeninwhichZone1hasbeenoverridden
•"1"flashestoindicatethatanoverrideisinprogressforthiszone+ logo
•AUTOisstillpresent:theotherzonesarestillonthetimeschedule
3) Zones 1 6 menu: (if present)
Thismenuallowsindividualadjustmentofthiszone,whichisdedicatedtocontrollingauxiliaryequipmentasfollows:
→On–Offasperatimeschedulewith:On= andOff=
→On-Offmanualoverride
→Consequently,onlythetwoOverrideandTimeSchedulesub-menusexistforthiszone
→Settingidenticaltotheotherzones
4) Setting the timer:
"Set timer" screen •Fromthemainscreen,withsuccessivepressesonMENU
•AlltheselogosFlash
•:UsedtosettheTime
• and are used to set the hours (the latter flashes and the other
symbols are lit steady)
•:Usedtoconfirmthetime/the minutes flash
• and are used to set the minutes (the latter flashes and the other
symbols are lit steady) ?
•:Usedtoconfirmtheminutes;the days of the week flash
• and are used to set the day
•:Usedtoconfirmthedayandautomaticallyreturntothemainscreen

EN - 18 N 14.13 A
12 ZONE TIMER CONTROLLER & TERMINAL DIMENSIONS
Controller:
Location for configuration
label (affixed by CIAT)
Detachable screw
terminals
Mounting on sym. rail
width35-depth7.5
Identification label
Comprising:
- CIAT item code
- Production batch/Serial no.
-Softwareversionnumber
i
V300
TMZ
REF : 7335309
FAB : 1425/0002
LOG : V1.06
Marking details:
FAB:1425/0001/=FabricationYear2014/weekno.25/2ndproductmanufacturedintheweek
Connection to screw terminals
Other manuals for V300
1
Table of contents