2-10
Installing Cisco Intrusion Prevention System Appliances and Modules 6.2
OL-15638-01
Chapter 2 Installing IPS-4240 and IPS-4255
Installing IPS-4240-DC
For More Information
•DC power guidelines are listed in Regulatory Compliance and Safety Information for the Cisco
Intrusion Detection and Prevention System 4200 Series Appliance Sensor.
•For more information on working with electrical power and in an ESD environment, see Site and
Safety Guidelines, page 1-32.
•For the procedure for placing IPS-4250-DC in a rack, see Rack Mounting, page 2-6.
•For the instructions for setting up a terminal server, see Connecting an Appliance to a Terminal
Server, page 1-19.
•For the procedure for using the setup command to initialize IPS-4250-DC, see Basic Sensor Setup,
page 10-3.
•For the procedure for updating IPS-4250-DC with the most recent cisco IPS software, see Obtaining
Cisco IPS Software, page 12-1.
•If you have the IPS-4240 DC model, see Installing IPS-4240-DC, page 2-10.
•For the procedure for using HTTPS to log in to IDM, refer to Logging In to IDM.
•For the procedures for configuring intrusion prevention on your sensor, refer to the following
documents:
–
Installing and Using Cisco Intrusion Prevention System Device Manager 6.2
–
Installing and Using Cisco Intrusion Prevention System Manager Express 6.2
–
Configuring the Cisco Intrusion Prevention System Sensor Using the Command Line Interface
6.2
Installing IPS-4240-DC
The IPS-4240-DC-K9 (NEBS-compliant) model equipped with DC-input power supply must be
terminated with the DC input wiring on a DC source capable of supplying at least 15 amps. A 15-amp
circuit breaker is required at the 48 VDC facility power source. An easily accessible disconnect device
should be incorporated into the facility wiring.
Warning
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
To ensure that all power is OFF, locate the circuit breaker on the panel board that services the DC
circuit, switch the circuit breaker to the OFF position, and tape the switch handle of the circuit
breaker in the OFF position.
Note The DC return connection should remain isolated from the system frame and chassis (DC-I). This
equipment is suitable for connection to intra-building wiring only.
Warning
Only trained and qualified personnel should be allowed to install, replace, or service this equipment.
Statement 1030