Cisco NCS 540 Series Manual

Cisco NCS 540 Router Hardware Installation Guide
First Published: 2018-03-28
Americas Headquarters
Cisco Systems, Inc.
170 West Tasman Drive
San Jose, CA 95134-1706
USA
http://www.cisco.com
Tel: 408 526-4000
800 553-NETS (6387)
Fax: 408 527-0883

THE SPECIFICATIONS AND INFORMATION REGARDING THE PRODUCTS IN THIS MANUAL ARE SUBJECT TO CHANGE WITHOUT NOTICE. ALL STATEMENTS,
INFORMATION, AND RECOMMENDATIONS IN THIS MANUAL ARE BELIEVED TO BE ACCURATE BUT ARE PRESENTED WITHOUT WARRANTY OF ANY KIND,
EXPRESS OR IMPLIED. USERS MUST TAKE FULL RESPONSIBILITY FOR THEIR APPLICATION OF ANY PRODUCTS.
THE SOFTWARE LICENSE AND LIMITED WARRANTY FOR THE ACCOMPANYING PRODUCT ARE SET FORTH IN THE INFORMATION PACKET THAT SHIPPED WITH
THE PRODUCT AND ARE INCORPORATED HEREIN BY THIS REFERENCE. IF YOU ARE UNABLE TO LOCATE THE SOFTWARE LICENSE OR LIMITED WARRANTY,
CONTACT YOUR CISCO REPRESENTATIVE FOR A COPY.
The Cisco implementation of TCP header compression is an adaptation of a program developed by the University of California, Berkeley (UCB) as part of UCB's public domain version of
the UNIX operating system. All rights reserved. Copyright ©1981, Regents of the University of California.
NOTWITHSTANDING ANY OTHER WARRANTY HEREIN, ALL DOCUMENT FILES AND SOFTWARE OF THESE SUPPLIERS ARE PROVIDED “AS IS" WITH ALL FAULTS.
CISCO AND THE ABOVE-NAMED SUPPLIERS DISCLAIM ALL WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING, WITHOUT LIMITATION, THOSE OF
MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT OR ARISING FROM A COURSE OF DEALING, USAGE, OR TRADE PRACTICE.
IN NO EVENT SHALL CISCO OR ITS SUPPLIERS BE LIABLE FOR ANY INDIRECT, SPECIAL, CONSEQUENTIAL, OR INCIDENTAL DAMAGES, INCLUDING, WITHOUT
LIMITATION, LOST PROFITS OR LOSS OR DAMAGE TO DATA ARISING OUT OF THE USE OR INABILITY TO USE THIS MANUAL, EVEN IF CISCO OR ITS SUPPLIERS
HAVE BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES.
Any Internet Protocol (IP) addresses and phone numbers used in this document are not intended to be actual addresses and phone numbers. Any examples, command display output, network
topology diagrams, and other figures included in the document are shown for illustrative purposes only. Any use of actual IP addresses or phone numbers in illustrative content is unintentional
and coincidental.
Cisco and the Cisco logo are trademarks or registered trademarks of Cisco and/or its affiliates in the U.S. and other countries. To view a list of Cisco trademarks, go to this URL: www.cisco.com
go trademarks. Third-party trademarks mentioned are the property of their respective owners. The use of the word partner does not imply a partnership relationship between Cisco and any
other company. (1721R)
©2018 Cisco Systems, Inc. All rights reserved.

CONTENTS
Safety Warnings 1
CHAPTER 1
Standard Warning Statements 1
Safety Guidelines for Personal Safety and Equipment Protection 2
Safety Precautions for Module Installation and Removal 2
Safety with Electricity 3
Power Supply Considerations 5
Power Connection Guidelines 5
Guidelines for DC-Powered Systems 5
Guidelines for AC-Powered Systems 6
Prevent Power Loss 6
Preventing ESD Damage 6
Cisco NCS 540 Router Overview 9
CHAPTER 2
Features 9
Interface Naming 10
Network Timing Interfaces 11
External Alarm Inputs 11
Console 11
USB Console 12
Online Insertion and Removal 12
Power Supply (N540-PWR400-A and N540-PWR400-D) 12
Fan Assembly (N540-FAN) 12
Prepare for Installation 13
CHAPTER 3
General Precautions 13
Site Planning Checklist 14
Cisco NCS 540 Router Hardware Installation Guide
iii

Site Power Guidelines 14
Electrical Circuit Requirements 15
Site Cabling Guidelines 15
Asynchronous Terminal Connections 15
Interference Considerations 16
Electromagnetic Interference 16
Radio Frequency Interference 16
Lightning and AC Power Fault Interference 16
Tools and Equipment 16
Prepare Your Location 17
Prepare Yourself 18
Prepare Rack for Router Installation 18
Unpack the Cisco NCS 540 Router 19
Install the Device 21
CHAPTER 4
Rack-Mount 21
Ground the Device 23
Install the AC Power Cables 24
Activate an AC Power Supply Module 24
Install the DC Power Cables 25
Activate a DC Power Supply Module 26
Port Connection Guidelines 26
Connect to the Console Port 27
Connect to the Management Ethernet Port 29
Install and Remove Transceiver Modules 30
Install and Remove SFP Modules 30
Bale Clasp SFP or SFP+ Module 31
Install a Bale Clasp SFP or SFP+ Module 31
Remove a Bale Clasp SFP or SFP+ Module 32
Install and Remove QSFP+/QSFP28 Transceiver Modules 34
Overview 34
Required Tools and Equipment 34
Install the 100-Gigabit Transceiver Module 34
Attach the Optical Network Cable 36
Cisco NCS 540 Router Hardware Installation Guide
iv
Contents

Remove the 100-Gigabit QSFP28 Transceiver Module 37
Connect Interface Ports 38
Connect a Fiber-Optic Port to the Network 38
Disconnect Optical Ports from the Network 38
Maintain Transceivers and Optical Cables 39
Configure the Device 41
CHAPTER 5
Create the Initial Router Configuration 41
Verify Device Installation 43
Replace Fan Module and Power Supply 45
CHAPTER 6
Replace Fan Module 45
Replace Power Supply 46
Remove the DC Power Supply Module 47
Install the DC Power Supply Module 47
Remove the AC Power Supply Module 48
Install the AC Power Supply Module 49
LEDs 51
APPENDIX A
Router LEDs 51
Fan Assembly LEDs 52
Power Supply LEDs 53
Cisco NCS 540 Router Hardware Installation Guide
v
Contents

Cisco NCS 540 Router Hardware Installation Guide
vi
Contents

CHAPTER 1
Safety Warnings
This handout topic lists the safety warnings necessary for handling this product. Before you install or service
the chassis, review these safety warnings to avoid injuring yourself or damaging the equipment.
For a complete list of translated safety warnings, see the Regulatory Compliance and Safety Information —
Cisco NCS 500 Series Routers document.
The safety warnings are grouped under the following sections:
•Standard Warning Statements, on page 1
•Safety Guidelines for Personal Safety and Equipment Protection, on page 2
•Safety Precautions for Module Installation and Removal, on page 2
•Safety with Electricity, on page 3
•Power Supply Considerations, on page 5
•Preventing ESD Damage, on page 6
Standard Warning Statements
This unit is intended for installation in restricted access areas. A restricted access area can be accessed only
by using a special tool, lock and key, or other means of security. Statement 1017
Warning
Ultimate disposal of this product must be handled according to all national laws and regulations. Statement
1040
Warning
To prevent the system from overheating, do not operate it in an area that exceeds the maximum recommended
ambient temperature of 158°F (70°C). Statement 1047
Warning
Mount the device on a rack that is permanently affixed to the building. Statement 1049
Warning
Cisco NCS 540 Router Hardware Installation Guide
1

This device is a Class A Device and is registered for EMC requirements for industrial use. You must be aware.
If sold or purchased by mistake, do replace with a residential-use type. Statement 294
Warning
Only trained and qualified personnel should be allowed to install, replace, or service this equipment. Statement
1030
Warning
SafetyGuidelines forPersonal SafetyandEquipmentProtection
The following guidelines ensure your safety and protect the equipment. This list does not include all the
potentially hazardous situations. Therefore, you must be alert.
• Before moving the system, always disconnect all power cords and interface cables.
• Never assume that power is disconnected from a circuit; always check.
• Before and after installation, keep the chassis area clean and dust free.
• Keep tools and assembly components away from walk areas where you or others could trip over them.
• Do not work alone if potentially hazardous conditions exist.
• Do not perform any action that creates a potential hazard to people or makes the equipment unsafe.
• Do not wear loose clothing that may get caught in the chassis.
• When working under conditions that may be hazardous to your eyes, wear safety glasses.
Safety Precautions for Module Installation and Removal
Be sure to observe the following safety precautions when you work on the chassis.
Class 1 laser product. Statement 1008
Warning
Do not stare into the beam or view it directly with optical instruments. Statement 1011
Warning
Invisible laser radiations present. Statement 1016
Warning
Cisco NCS 540 Router Hardware Installation Guide
2
Safety Warnings
Safety Guidelines for Personal Safety and Equipment Protection

Safety with Electricity
Before working on a chassis or with power supplies, unplug the power cord on AC units. Disconnect the
power at the circuit breaker on DC units. Statement 12
Warning
Before working on equipment that is connected to power lines, remove jewelry (including rings, necklaces,
and watches). Metal objects heat up when connected to power and ground and can cause serious burns or
weld the metal object to the terminals. Statement 43
Warning
Avoid using or servicing any equipment that has outdoor connections during an electrical storm. There may
be a risk of electric shock from lightning. Statement 1088
Warning
Read the installation instructions before connecting the system to the power source. Statement 1004
Warning
When you connect or disconnect the power and relay connector with power applied, an electrical arc can
occur. This action can cause an explosion in hazardous area installations. Be sure that power is removed from
the switch and alarm circuit. Be sure that power cannot be accidentally turned on or verify that the area is
nonhazardous before proceeding. Failure to securely tighten the power and relay connector captive screws
can result in an electrical arc if the connector is accidentally removed. Statement 1058
Warning
The plug-socket combination must be accessible always, because it serves as the main disconnecting device.
Statement 1019
Warning
This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the absence
of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or an electrician
if you are uncertain that suitable grounding is available. Statement 1024
Warning
This unit may have more than one power supply connection. All connections must be removed to de-energize
the unit. Statement 1028
Warning
Cisco NCS 540 Router Hardware Installation Guide
3
Safety Warnings
Safety with Electricity

This product requires short-circuit (overturned) protection, to be provided as part of the building installation.
Install only in accordance with national and local wiring regulations. Statement 1045
Warning
When installing or replacing the unit, ensure the ground connection first and disconnected last. Statement
1046
Warning
When you connect or disconnect the power and/or alarm connector with power applied, an electrical arc can
occur. This could cause an explosion in hazardous area installations. Be sure that all power is removed from
the switch and any other circuits. Be sure that power cannot be accidentally turned on or verify that the area
is nonhazardous before proceeding. Statement 1058
Warning
This equipment is intended to be grounded to comply with emission and immunity requirements. Ensure that
the switch functional ground lug is connected to earth ground during normal use. Statement 1064
Warning
Installation of the equipment must comply with local and national electrical codes. Statement 1074
Warning
When working on equipment that is powered by electricity, follow these guidelines:
• Locate the room’s emergency power-off switch. If an electrical accident occurs, you know where to
quickly turn off the power.
• Before starting work on the system, turn off the DC main circuit breaker and disconnect the power
terminal block cable.
• Disconnect all power when:
• Working on or near power supplies
• Installing or removing a device chassis or network processor module
• Performing most hardware upgrades
• Never install equipment that appears damaged.
•Carefully examine your work area for possible hazards, such as moist floors, ungrounded power extension
cables, and missing safety grounds.
• Never assume that power is disconnected from a circuit; always check.
• Never perform any action that creates a potential hazard to people or makes the equipment unsafe.
• If an electrical accident occurs and you are uninjured:
• Use caution to avoid injuring yourself.
• Turn off power to the device.
Cisco NCS 540 Router Hardware Installation Guide
4
Safety Warnings
Safety with Electricity

•If possible, send another person to get medical aid. Otherwise, determine the condition of the victim,
and then call for help.
• Determine whether the person needs rescue pulsing or external cardiac compressions; then take
appropriate action.
Use the following guidelines when working with any equipment that is disconnected from a power source,
but connected to telephone wiring or network cabling:
• When installing or modifying telephone lines, use caution.
• Never install telephone jacks in wet locations unless the jack is designed to handle such locations.
• Never install telephone wiring during a lightning storm.
Power Supply Considerations
Check the power at your site to ensure that you are receiving clean power (free of spikes and noise). If
necessary, install a power conditioner.
Power Connection Guidelines
This section provides guidelines for connecting the device power supplies to the site power source.
Never defeat the ground conductor or operate the equipment in the absence of a suitably installed ground
conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain that
suitable grounding is available. Statement 1024
Warning
The plug-socket combination must be accessible always because it serves as the main disconnecting device.
Statement 1019
Warning
This product requires short-circuit (overcurrent) protection, to be provided as part of the building installation.
Install only in accordance with national and local wiring regulations. Statement 1045
Warning
Guidelines for DC-Powered Systems
Basic guidelines for DC-powered systems include the following:
• Each chassis power supply has its own dedicated input power source. The source must comply with the
safety extra-low voltage (SELV) requirements in the UL 60950, CSA 60950, EN 60950, and IEC 60950
standards.
•Protect the circuit by a dedicated two-pole circuit breaker. Ensure that the circuit breaker is sized according
to the power supply input rating and local or national code requirements.
• The circuit breaker is considered as the disconnect device and is easily accessible.
Cisco NCS 540 Router Hardware Installation Guide
5
Safety Warnings
Power Supply Considerations

• The system ground is the power supply and chassis ground.
• Use the grounding lug to attach a wrist strap for ESD protection during servicing.
• Do not connect the DC return wire to the system frame or to the system-grounding equipment.
• Ensure that the DC return is grounded at the source side.
Guidelines for AC-Powered Systems
Basic guidelines for AC-powered systems include the following:
• Each chassis power supply has its own dedicated branch circuit.
• Ensure that the circuit breaker is sized according to the power supply input rating and local or national
code requirements.
• The AC power receptacles that are used to plug in the chassis must be the grounding type. The grounding
conductors that connect to the receptacles must connect to protective earth ground at the service equipment.
Prevent Power Loss
Use the following guidelines to prevent power loss to the device:
• To prevent input power loss, ensure that the maximum load on each circuit supplying the power is within
the current ratings of the wiring and breakers.
• In some systems, you can use an UPS to protect against power failures at your site. Avoid UPS types
that use ferroresonant technology. These UPS types can become unstable with systems such as the device,
which can have substantial current-draw fluctuations due to bursty data traffic patterns.
Determining power requirements is useful for planning the power distribution system to support the device.
Preventing ESD Damage
Ground this equipment. Use a green and yellow 6-AWG ground wire to connect the host to earth ground
during normal use. Statement 383
Warning
Electrostatic discharge (ESD) can damage equipment and impair electrical circuitry. ESD may occur when
electronic printed circuit cards are improperly handled and can cause complete or intermittent failures. When
removing and replacing modules, always follow these ESD prevention procedures:
• Ensure that the device chassis is electrically connected to earth ground.
• Wear an ESD-preventive wrist strap, ensuring that it makes good skin contact. To channel unwanted
ESD voltages safely to ground, connect the clip to an unpainted surface of the chassis frame. To guard
against ESD damage and shocks, the wrist strap and cord must operate effectively.
• If no wrist strap is available, ground yourself by touching a metal part of the chassis.
• When installing a component, use any available ejector levers or captive installation screws to properly
seat the bus connectors in the backplane or midplane. These devices prevent accidental removal, provide
proper grounding for the system, and help to ensure that bus connectors are properly seated.
• When removing a component, use available ejector levers or captive installation screws, if any, to release
the bus connectors from the backplane or midplane.
Cisco NCS 540 Router Hardware Installation Guide
6
Safety Warnings
Guidelines for AC-Powered Systems

• Handle components by only their handles or edges; do not touch the printed circuit boards or connectors.
• Place a removed component board side up on an antistatic surface or in a static-shielding container. If
you plan to return the component to the factory, immediately place it in a static-shielding container.
• Avoid contact between the printed circuit boards and clothing. The wrist strap only protects components
from ESD voltages on the body; ESD voltages on clothing can still cause damage.
• Never attempt to remove the printed circuit board from the metal carrier.
For the safety of your equipment, periodically check the resistance value of the antistatic wrist strap. Maintain
the value between 1 and 10 Mohm.
Cisco NCS 540 Router Hardware Installation Guide
7
Safety Warnings
Preventing ESD Damage

Cisco NCS 540 Router Hardware Installation Guide
8
Safety Warnings
Preventing ESD Damage

CHAPTER 2
Cisco NCS 540 Router Overview
The Cisco NCS 540 1RU router complements Cisco’s offerings for IP RAN solutions for the GSM, UMTS,
LTE, and CDMA.
For more information on its features and benefits, see the Cisco Network Convergence System 540 Router
Data Sheet.
•Features, on page 9
•Interface Naming, on page 10
•Network Timing Interfaces, on page 11
•External Alarm Inputs, on page 11
•Console, on page 11
•Online Insertion and Removal, on page 12
•Power Supply (N540-PWR400-A and N540-PWR400-D), on page 12
•Fan Assembly (N540-FAN), on page 12
Features
The Cisco NCS 540 1RU Router has the following hardware features:
• 24 x 10G SFP+ Ports
• Support DWDM & ZR Optics
• 8 x 25G SFP+ Ports
• 2 x 100G QSFP28 Ports
Figure 1: Cisco NCS 540 Device
Cisco NCS 540 Router Hardware Installation Guide
9

All ports are color coded in the chassis for ease of access; for example, the 10G SFP+ Ports are in pink, the
25G SFP+ Ports are in yellow, and the 100G QSFP28 Ports are in green.
Note
Interface Naming
The following table shows the interface naming of the Cisco N540-24Z8Q2C-M ports:
Table 1: Port Numbering
40G/100G ports
(QSFP28)
1G/10G/25G Dual rate ports (SFP28)1G/10G Dual rate ports (SFP+)
1/0302826242220181614121086420/0
1/10/312927252321191715131197531
• Port 0 – 23: Dual rate ports, which can act as 1G or 10G also includes Copper and DWDM.
• Port Numbering: Gig/Te 0/0/0/<0-23>
• Port 24-31: Dual rate ports, which can act as 1G or 10G or 25G.
• Port Numbering: Gig/Te/Twe 0/0/0/<24-31>
• For the ports 24-31, a quad configuration is required to bring-up the ports as 1G/10G
• By default, all ports will come up as 25G
• Use the command hw-module quad 0 location 0/0/CPU0 mode to change to 10G
• Copper optics is not supported in these 8 ports, 24-31
• Do not combine 1G or 10G with 25G in a quad, quad 1: 24-27 and quad 2: 28-31
• Port 32-33: 40G or 100G ports.
• Port Numbering: Hu 0/0/1/<0-1>
Dual-Rate functionality is supported only with the Supported SFP.
Note
Table 2: Maximum Number of Inerfaces
Port NumberMaximum
Interface
Category
0/0 - 2324100ME
copper
Cisco NCS 540 Router Hardware Installation Guide
10
Cisco NCS 540 Router Overview
Interface Naming

Port NumberMaximum
Interface
Category
0/0 - 31321GE
0/0 - 31, 1/0 - 1*32 / 40*1
10GE
0/24 - 31, 1/0 -
1*
8 / 16*25GE
1/0 - 1240GE
1/0 - 12100GE
1*4x10GE or 4x25GE option
Network Timing Interfaces
• BITS input or output—The BITS interfaces support clock recovery from either a T1 at 1.544 MHz or an
E1 at 2.048 MHz, configurable by software. BITS interface is provided through a standard RJ-48 connector
on the front panel.
• 1PPS input or output and ToD input or output—This shielded RJ-45 interface is used for input or output
of time-of-day (ToD) and 1PPS pulses. ToD format includes both NTP and IEEE 1588-2008 time formats.
The same RS422 pins for 1PPS and TOD are shared between input and output directions. The direction for
each can be independently configurable through software.
Use an SMB connector on the front panel for the following:
• GPS 10 Mhz input and output—10 MHz input for GPS Synchronization.
• GPS 1 PPS input and output—1 PPS input for GPS Synchronization.
External Alarm Inputs
The router supports four dry contact alarm inputs through an RJ-45 jack at the rear panel.
• Normally Open—indicates that no current flows through the alarm circuit and the alarm is generated
when the current is flowing.
Each alarm input can be provisioned as critical, major, or minor.
Console
The RS232 console port provides transmission (Tx), reception (Rx), and ground (Gnd).
Cisco NCS 540 Router Hardware Installation Guide
11
Cisco NCS 540 Router Overview
Network Timing Interfaces

USB Console
A single USB 2.0 Type-A receptacle on the front panel of the router provides console access to ROMMON,
Cisco IOS-XE and diagnostics. While it uses the Type-A connector, it operates as a USB peripheral only for
connection to an external host computer. This interface requires the use of a Type-A to Type-A connector
instead of a standard USB cable.
Use of the USB console is mutually exclusive of the RS232 console port. This interface requires the use of a
Type-A to Type-A USB cable.
Note
Online Insertion and Removal
The router supports the following OIR operations:
• When an SFP is removed, there is no effect on traffic flowing on other ports.
• When an SFP is installed, the system initializes that port for operation that is based on the current
configuration. If the inserted SFP is incompatible with the current configuration for that port, the port
does not become operational until the configuration is updated.
• Both power supplies are installed and active, the load may be shared between them or a single PSU could
support the whole load. When a power supply is not working or the input cable is removed, the remaining
power supply takes the entire load without disruption.
Power Supply (N540-PWR400-A and N540-PWR400-D)
The Cisco NCS 540 router supports two AC or DC power supplies, which power the router. The second power
supply ensures redundancy in the system. Both power supplies support hot swapping capabilities.
Fan Assembly (N540-FAN)
Cisco NCS 540 Router comes with 4 individual fan modules. Fans are located at the rear panel and support
hot swapping. Fan flow is supported only on the forward direction from front to back.
The system can function with a single fan failure but if more than one fan is faulty then the system shuts down.
Note
Cisco NCS 540 Router Hardware Installation Guide
12
Cisco NCS 540 Router Overview
USB Console

CHAPTER 3
Prepare for Installation
Before you install the Cisco NCS 540, you must prepare your site for the installation.
Preparing your site involves these tasks:
•General Precautions, on page 13
•Site Planning Checklist, on page 14
•Site Power Guidelines, on page 14
•Site Cabling Guidelines, on page 15
•Tools and Equipment, on page 16
•Prepare Your Location , on page 17
•Prepare Yourself , on page 18
•Prepare Rack for Router Installation, on page 18
•Unpack the Cisco NCS 540 Router, on page 19
General Precautions
Observe the following general precautions when using and working with your chassis:
• Keep your system components away from radiators and heat sources, and do not block cooling vents.
• Do not spill food or liquids on your system components, and never operate the product in a wet
environment.
• Do not push any objects into the openings of your system components. Doing so can cause fire or electric
shock by shorting out interior components.
• Position system cables and power supply cable carefully. Route system cables and the power supply
cable and plug so that they are not stepped on or tripped over. Ensure that nothing is rests on your system
component cables or power cable.
• Do not modify power cables or plugs. Consult a licensed electrician or your power company for site
modifications. Always follow your local and national wiring rules.
• If you turn off your system to avoid damage of system components, wait at least 30 seconds before
turning it on again.
Cisco NCS 540 Router Hardware Installation Guide
13

Site Planning Checklist
Use the following checklist to carry out all site planning tasks:
• The site meets environmental requirements.
• The site’s air conditioning system can compensate for the heat dissipation of the chassis.
• The floor space that the chassis occupies can support the weight of the system.
• Electrical service to the site complies with the safety with electricity requirements.
• The electrical circuit servicing the chassis complies with the power supply requirements.
• Console port wiring and cabling limitations have been considered in accordance to TIA/EIA-232F.
• The chassis Ethernet cabling distances are within prescribed limits.
• The equipment rack where the chassis is to be installed complies with prescribed requirements.
• When selecting rack location, safety, ease of maintenance, and proper airflow requirements have been
considered.
Site Power Guidelines
The chassis has specific power and electrical wiring requirements. Adhering to these requirements ensures
reliable operation of the system. Follow these precautions and recommendations when planning your site
power for the chassis:
• The redundant power option provides a second, identical power supply to ensure uninterrupted power
supply.
• Connect each power supply to a separate input power source. Otherwise, it results in total power failure
to the system due to a fault in the external wiring or a tripped circuit breaker.
• To prevent loss of input power, ensure that the maximum load on each circuit is within the current ratings
of the wiring and the breakers.
• Check the power at your site before installation, and periodically after installation, to ensure that you are
receiving clean power. If necessary, install a power conditioner.
• Provide proper grounding to avoid personal injury and damage to the equipment due to power surges or
lightning striking power lines. The chassis ground must be attached to a central office or other interior
ground system.
This product requires short-circuit (overcurrent) protection to be provided as part of the building installation.
Install only in accordance with national and local wiring regulations.
Caution
Cisco NCS 540 Router Hardware Installation Guide
14
Prepare for Installation
Site Planning Checklist
Other manuals for NCS 540 Series
3
Table of contents
Other Cisco Network Router manuals

Cisco
Cisco IAD2801 Series User manual

Cisco
Cisco 1801 User manual

Cisco
Cisco NCS 6000 Series User manual

Cisco
Cisco SG 300-10P User manual

Cisco
Cisco 7609-S User manual

Cisco
Cisco C11 1 8P Series Manual

Cisco
Cisco IR1101 Manual

Cisco
Cisco IR1101 Manual

Cisco
Cisco 8600 Manual

Cisco
Cisco Catalyst 2820 How to use

Cisco
Cisco NCS 5700 Series Manual

Cisco
Cisco 7201 User manual

Cisco
Cisco 12406 series Guide

Cisco
Cisco ASR 9000 Series User manual

Cisco
Cisco ASR1002 - ASR 1002 Router User manual

Cisco
Cisco 8800 Series Manual

Cisco
Cisco 897VAW User manual

Cisco
Cisco ASR 1000 Series User manual

Cisco
Cisco ASR-920-12SZ-IM Manual

Cisco
Cisco WRT54G User manual