
3
C. ADDITIONAL INSTALLATION
D. STARTUP PROCEDURES
E. WHEN YOU CLEAN YOUR FILTER
1. Pressure gauge
a. Hole in cover is already pre-tapped. Apply PTFE (Teon®) tape to pressure gauge threads and
screw gauge into threads on cover.
2. CMP recommends 1 gallon per minute (gpm) per square foot of lter for proper ltration.
a. 50 sq ft lter = 50 gpm
b. Pair lter with appropriately sized pump for optimal lter performance.
c. Too much ow rate through cartridge lter may decrease desired performance
of lter system. Exceeding recommended ow rate may damage the lter element and/or water
features in line with lter.
3. Apply O-ring lube to Oring on cover.
4. Tighten down cover until locking tab is secure.
5. Do not over-tighten.
6. Check for leaks in system before operating.
7. WARNING Maximum recommended pressure is 50 psi.
1. Monitor pressure dierence from when the lter was originally installed.
a. If pressure rises 10 psi or greater, check lter element and clean or replace if necessary.
b. If ow drops below desired rate, check lter element and clean or replace if necessary.
c. WARNING Do not allow pressure to exceed 50 psi
2. MY ORIGINAL STARTING PRESSURE IS ____________ PSI. I SHOULD CLEAN MY FILTER AT _________ PSI
3. Flow rate and pressure may not always indicate when lter needs to be cleaned.
4. Check your lter if you notice any other performance variation besides psi change.
1. WARNING Make sure both suction and discharge valves are in the open position.
2. Open manual air relief valve (3 turns counter clockwise)
a. Air will vent out of the discharge outlet to the pool and through the manual relief valve.
b. Once all air is out of the system, close manual relief air valve. Pressure gauge should read “0” psi.
3. Record starting pressure of the system. This may help provide an indicator of when the lter needs
to be cleaned.
NOTICE