Hint: Foropening a new WebSupervisoraccount kindly send e-mailto
admin.websupervisor@comap.cz yourName, Login name, E-mailaddress andTimezone. We will
create freeaccountforyou. Detailsat: http://www.comap.cz/products/detail/WebSupervisor .
Communication isnowreadyforuse.
Hint: To reduce the data trafficoverGPRSnetwork you can set in setpoint group„CommsSettings“
the parameter„AirGate IP“=80.95.108.26. Thiswill save significant data amount needed fortranslation
of Airgate serverIPaddress. In case of changing the serverIPaddress thissettingshasto be updated
orreturned to default„airgate.comap.cz“.
Hint: From it’snature the GPRSconnection can from time totime drop fora shorttimedue to a number
of reasonsaffectingthecellularnetwork. Howeverthe system isdesigned in the waythat controllerwill
automaticalyreconnectback.
Warning: AllmanipulationswithIL-NT-GPRSmodulehasto be donewith DC powersupplyswitched
off. Module can be onlypowered on while plugged in the controllerand togetherwith controller!
•GSM DiagCode – Diagnosticcode forIL-NT-GPRSmodem
Table ofDiagnosticCodes:
Code Description
0 OK. No error.
1 Not possible to hang up.
2 IL-NT-GPRSisswitched off
3 IL-NT-GPRSisswitched on
4 IL-NT-GPRS– errorininitialization
5 IL-NT-GPRS– not possibleto set the APN
6 IL-NT-GPRS– not possibleto connect toGPRSnetwork
7 IL-NT-GPRS– not possibleto retrieve IPaddress
8 IL-NT-GPRS– not accepted DNSIPaddress
9 Errorin modemdetection
10 Errorininitialization ofanalog modem
11 SIM cardislocked (PossiblyPIN code required, PIN needstobe deactivated)orunknown
statusofSIM locking
12 No GSM signal
13 Not possible to read the SIM card parameters
14 GSM modemdid not accepted particularinitialization command, possiblycausedby
locked SIM card
15 Unknownmodem
16 Bad answerto complement initialization string
17 Not possible to read GSM signalstrength
18 CDMAmodemnot detected
19 No CDMAnetwork
20 Unsuccesfulregistrationto CDMAnetwork
•AirGate Diag – DiagnosticCode forAirGate connection