ComAp IL-NT-GPRS User manual

IL-NT-GPRS QuickGuide Page 1of4
IL-NT-GPRSQuickGuide / ©ComAp – May2012 / IL-NT-QuickGuide 5-2012.pdf
ISO9001Certified
C
o
m
A
p
s
.
r
.
o
.
Q
u
a
l
i
t
y
M
a
n
a
g
e
m
e
n
t
ComAp,spol.s r.o.
Kundratka2359/17
180 00 Prague 8
CzechRepublic
Tel.:+420 246 012111
Fax: +420 246 316 647
E-mail: info@comap.cz
Internet: http://www.comap.cz
Shortguidehowtostartusing IL-NT-GPRSmodule
CAUTION!:
Anymanipulation with plug-in moduleshallbe done with disconnected powersupplyto both controllerand
module. Powersupplyshallbe switched on alsoissame time to both moduleandcontroller. Failto follow
theseinstructions(powersupplyactiveonlyin controlleroronlyinmodule)can lead tomodule orcontroller
failure!
1. You will need one ofsupported ComAp controllers (IL-NT/IC-NT/ID-Lite), IL-NT-GPRS, antenna,
SIM card with GPRSservice and optionallyIL-NT-RS232 orIL-NT-S-USB module. Firmware
supporting IL-NT-GPRSmoduleisIL-NT2.0 orIL-NT-WSUPorselected customerbranches
(contact support@comap.cz fordetails). It isavailablehere: http://www.comap.cz/products/detail/IL-
NT-GPRS/support/software/
2. ContactSIM card operatorforgetting GPRSAPN(APN =Access Point Name)name, username
and password. Some operator’sAPNsarelisted here: http://www.quickim.com/support/gprs-
settings.html#Australia orhere:
http://www.flexispy.com/Mobile%20APN%20Setting%20to%20use%20GPRS.htm
Example: APN Name =internet.t-mobile.cz, UserName =[blank], Password=[blank].
3. Make sure SIMcard doesnot requirePIN code. Ifitdoes, itispossibleto disableit inanycommon
networkunlocked mobiletelephone.
4. Powerup the ComAp controller.
5. EntercorrectAPN Name, APN UserName andAPN UserPass incontroller’ssetpoint group Comms
Settings.Set COM1Mode =DIRECT. Commssettingsaseverysepoint group are accessible by
PAGEbuttonfromanymeasurement screen on controller.Setpointscan be set oncontroller’sfront
panelkeyboard orbyLiteEdit4.5 and higher.
6. Switchoff ComAp controller.
7. PlacetheSIM cardinto sloton IL-NT-GPRScard, plugin the IL-NT-GPRScard into communication
slot on backside ofComAp controller.
8. Connect theantenna todesignated SMAconnector.
9. Connect powersupplyto IL-NT-GPRSmodule.It supports8-36VDC voltage.
10.Powerup the system(Controllerandmodule together).

IL-NT-GPRS QuickGuide Page 2of4
IL-NT-GPRSQuickGuide / ©ComAp – May2012 / IL-NT-QuickGuide 5-2012.pdf
ISO9001Certified
C
o
m
A
p
s
.
r
.
o
.
Q
u
a
l
i
t
y
M
a
n
a
g
e
m
e
n
t
ComAp,spol.s r.o.
Kundratka2359/17
180 00 Prague 8
CzechRepublic
Tel.:+420 246 012111
Fax: +420 246 316 647
E-mail: info@comap.cz
Internet: http://www.comap.cz
11.Waitforapprox2 -4 minutesforfirst connection ofthe systemto AirGate. AirGatewill generate
automaticallytheAirGate ID value. Then navigate to last ofmeasurement screenswhereyou will
find signalstrength barandAirGate ID identifier.
Once thisAirGate ID isdisplayed, connection via AirGate wassuccesfull. Thisvalue willbeneeded
forLiteEditorWebSupervisorconnection. Kindlymake a note forfuture reference.
AirGate Connection dialog in LiteEdit:
Add new gen-set dialog inWebSupervisor:
Shouldyouencounteranytroubleswith connection, checkthe faultcodeson the same screen and
find detaileddescription inDiagnosticcodeslistedlower.
12.Open LiteEditPC softwareorenteryourWebSupervisoraccount at http://websupervisor.comap.cz.

IL-NT-GPRS QuickGuide Page 3of4
IL-NT-GPRSQuickGuide / ©ComAp – May2012 / IL-NT-QuickGuide 5-2012.pdf
ISO9001Certified
C
o
m
A
p
s
.
r
.
o
.
Q
u
a
l
i
t
y
M
a
n
a
g
e
m
e
n
t
ComAp,spol.s r.o.
Kundratka2359/17
180 00 Prague 8
CzechRepublic
Tel.:+420 246 012111
Fax: +420 246 316 647
E-mail: info@comap.cz
Internet: http://www.comap.cz
Hint: Foropening a new WebSupervisoraccount kindly send e-mailto
admin.websupervisor@comap.cz yourName, Login name, E-mailaddress andTimezone. We will
create freeaccountforyou. Detailsat: http://www.comap.cz/products/detail/WebSupervisor .
Communication isnowreadyforuse.
Hint: To reduce the data trafficoverGPRSnetwork you can set in setpoint group„CommsSettings“
the parameter„AirGate IP“=80.95.108.26. Thiswill save significant data amount needed fortranslation
of Airgate serverIPaddress. In case of changing the serverIPaddress thissettingshasto be updated
orreturned to default„airgate.comap.cz“.
Hint: From it’snature the GPRSconnection can from time totime drop fora shorttimedue to a number
of reasonsaffectingthecellularnetwork. Howeverthe system isdesigned in the waythat controllerwill
automaticalyreconnectback.
Warning: AllmanipulationswithIL-NT-GPRSmodulehasto be donewith DC powersupplyswitched
off. Module can be onlypowered on while plugged in the controllerand togetherwith controller!
•GSM DiagCode – Diagnosticcode forIL-NT-GPRSmodem
Table ofDiagnosticCodes:
Code Description
0 OK. No error.
1 Not possible to hang up.
2 IL-NT-GPRSisswitched off
3 IL-NT-GPRSisswitched on
4 IL-NT-GPRS– errorininitialization
5 IL-NT-GPRS– not possibleto set the APN
6 IL-NT-GPRS– not possibleto connect toGPRSnetwork
7 IL-NT-GPRS– not possibleto retrieve IPaddress
8 IL-NT-GPRS– not accepted DNSIPaddress
9 Errorin modemdetection
10 Errorininitialization ofanalog modem
11 SIM cardislocked (PossiblyPIN code required, PIN needstobe deactivated)orunknown
statusofSIM locking
12 No GSM signal
13 Not possible to read the SIM card parameters
14 GSM modemdid not accepted particularinitialization command, possiblycausedby
locked SIM card
15 Unknownmodem
16 Bad answerto complement initialization string
17 Not possible to read GSM signalstrength
18 CDMAmodemnot detected
19 No CDMAnetwork
20 Unsuccesfulregistrationto CDMAnetwork
•AirGate Diag – DiagnosticCode forAirGate connection

IL-NT-GPRS QuickGuide Page 4of4
IL-NT-GPRSQuickGuide / ©ComAp – May2012 / IL-NT-QuickGuide 5-2012.pdf
ISO9001Certified
C
o
m
A
p
s
.
r
.
o
.
Q
u
a
l
i
t
y
M
a
n
a
g
e
m
e
n
t
ComAp,spol.s r.o.
Kundratka2359/17
180 00 Prague 8
CzechRepublic
Tel.:+420 246 012111
Fax: +420 246 316 647
E-mail: info@comap.cz
Internet: http://www.comap.cz
Table ofDiagnosticCodes:
Code Description
0
Waiting forconnection to AirGate Server
1
Controllerregistered, waiting forauthorization
2 Not possible to register, controllerblacklisted
3 Not possible to register, serverhasno more capacity
4 Not possible to register, otherreason
5 Controllerregistered and authorized
Note:
ComAp believesthat allinformation provided hereiniscorrect and reliable and reservestheright toupdate
at anytime. ComAp doesnot assume anyresponsibilityforitsuseunless otherwise expresslyundertaken.
Some ofInteliLite functionsare subject ofchangesdependon SWversion. The data in thismanualonly
describesthe product and are not warrantyofperformance orcharacteristic.
Table of contents
Other ComAp Control Unit manuals