UC-7112-LX Plus - User Guide 5
2 About the Module
UC-7112-LX Plus is multipurpose communication gateway. It can acts as:
Gateway for connecting 3rd party devices into WebSupervisor
Connection PV inverters to InteliSys NTC Hybrid controller
Connection MTU MIP engine to ComAp controller.
Using this module can be realized in three scenarios:
Create configuration by selecting predefined devices selected from list.
Using predefined configuration, available on ComAp website.
In case of specific requests or non-supported device, please contact ComAp support for help with
solution. ComAp support can prepare custom configuration file. This service may be charged.
2.1 LED indication
LED name Description Meaning
Ready Indicates the state
of device
Off - device is out of power or damaged
Solid light - Device is starting. If the LED is steadily lighting
after 5 minutes after turning on - please contact technical
support, the device is probably corrupted
Flashes - standard operation. Flashing speed is 0.5 Hz.
RX/TX - P1 Recieve/transmit at
P1 port.
Off - no communication at port P1
Flashes - communication on port P1 (RS232 or RS485)
RX/TX - P2 Recieve/transmit at
P2 port.
Off - no communication at port P2
Flashes - communication on port P2 (RS232 or RS485)
Ethernet LEDs Indicates state of
LAN
Green - 100Mbit LAN is connected
Orange - 10 Mbit LAN is connected
Flashing indicates LAN traffic.
2.2 Resetting the module
For resetting the UC-7112-LX Plus please unplug the power and plug in again.
Do not use the reset button! Reset button can remove the entire system inside and the module needs to be
sent back to ComAp for reprogramming.
2.3 Starting the module
After the power is turned on, the module will start the operating system. In this time the Ready LED is light on.
When the system is running the LED starts flashing and then the LAN ports are being initialized. During the LAN
initialization the device is not detectable via „ComAp Communication Gateway Configurator“.
The starting procedure may take up to 5 minutes.