Installation Instructions
CQAC Fan Forced Wall Heater
Reference
J061d
Remove from carton and check contents :- - grille, frame and fixing screws
- heater assembly fitted in CQAC-R recess box
- fixing screws (4)
HEATER LOCATION
The heater should be mounted vertically on the wall with the air outlet at the bottom. To ensure proper air
distribution a minimum spacing from heater to closest adjacent wall, floor or ceiling of 200mm must be
observed.
When RECESSED the flanges of the wall box MUST be on the finished surface of the wall .
RECESSED MOUNTING
1) Remove heater assembly (B) from CQAC-R Recess box (A) by removing 7 screws.
2) Create cut-out 491mm x 362mm in wall ensuring adequate fixing locations are available.
3) Remove appropriate knock out (K) and fix recess box. Pull through sufficient cable to make connections.
4) Make connections to terminal block and earth screw.
5) Install heater assembly into recess box and replace screws (7).
6) Fit grille (F) to heater securing with screws (4) supplied
7) Fit frame (P) to grille and secure with single screw in lower edge.
SURFACE MOUNTING
1) Securely fix recess box to wall via fixing holes in back.
2) Place surface box CQAC-S over recess box.
3) Use bottom knock-out only for surface fixing.
ELECTRICAL CONNECTIONS.
The Heater should be installed in accordance with the latest edition of the IEE Requirements for Electrical
Installation (BS 7671:2001) by a suitably qualified person. The unit should be connected to a suitable 230Vac
50Hz.power supply incorporating a means of isolation having a contact separation of at least 3mm in all poles.
Connect as follows:-
Green-yellow wire to terminal marked E , with earth symbol.
Blue wire to terminal marked N
Brown wire to terminal marked L
WARNING: THE HEATER MUST BE EARTHED.
362 mm
491 mm
200 mm
MIN