LOCATION
The heater must be installed at least 2.0m above floor
level. All round minimum clearance dimensions must be
observed.
For optimum effect the heater should be mounted as close
as possible to the top of the doorway. The maximum
recommended mounting height is 2.3m for 3kW and 2.8m
for 4.5, 6.0 and 9.0kW units.
The heater is designed to take input air from the
ceiling void it is therefore imperative that a suitably
sized inlet grille is provided within the ceiling or
enclosure.
The heater must not be covered or the airflow impeded
in any way.
If one inlet grille is at its minimum dimension the other
must have an unrestricted airflow
CONTROL
Remote Switch
Thermostat (CRST16 or CPRST)
The Remote Switch Unit allows ON/OFF, Fan only with 3kW and 6kW.
This will switch the heater off when set temperature is
reached. To allow the fan only to operate in summer the thermostat must be set high and the heat switches
must be in the off position.
If a thermostat is required remove link between Fuse and Lt and replace with connection to thermostat. A
thermostat with at least a 3A rating is required.
The control circuit is fitted with a 3A fuse should this blow check for reason and replace , if the problem
persists consult a suitably qualified person.
CONTENTS
- grille frame and 2 no roundhead woodscrews
Remove from carton and check contents ;
- heater unit
- 2 no support brackets, 4 no. machine screws and 4 no woodscrews
- ODH-RSW three switch control unit
- 25mm cord grip bush and locknut
ELECTRICAL CONNECTION
The heater should be installed in accordance with the latest edition of the IEE Requirements for Electrical
Installation (BS 7671:2008)
The unit should be permanently connected to a suitable 230Vac power supply incorporating a means of
isolation having a contact separation of at least 3mm in all poles.
remote switch unit in suitable location.
Select cabling with 4 cores and earth and of appropriate size for current and volt drop.
Pass cable/s through cord grip in back of unit. Leave sufficient length for connection but ensuring cables do
not foul blower unit. Make off connections to connector block and earth stud in accordance with circuit
diagram RDH-W-003 (copy on back page )
If remote switching is not required connect power supply to L and N and link Lt,Lsw,LI and LII with 1.5sqmm
cable.
Tighten up cord grip. Replace cover.
Remove heater cover, position heater in ceiling (See Fixing). Fix
Note: Ensure link between Fuse and Lt is secure otherwise heater will not operate
WARNING THE HEATER MUST BE EARTHED
IMPORTANT : always check to ensure the heating elements cannot be energised without the fan
running.
OVER TEMPERATURE CUT OUT
To RESET -
Should the heater exceed normal operating temperature the over temperature cut out on the heating
elements will operate switching off both elements and fans.
switch off power to the unit and allow to cool before switching on again. If the problem
persists consult a suitably qualified person.
min
20
min
100
min
30
SAFETY
The correct procedures for working at height must be adopted when installing this heater.
The heater must be installed by a suitably qualified person in accordance with current regulations.