MODEL DST226C
SINGLE RANGE SUPERLOADCELLS
INSTRUCTION MANUAL F-102
6
Copyright 2023 - Revised, Comptrol All Rights Reserved
II-H FULL LOAD ADJUSTMENT
After the loadcell has been zeroed, a pull test can be
made to check the output voltage of the loadcell at full
load. (See calibration sheet for voltage output)
1. Run a non-stretchable rope over the center of the
tension roll simulating the web path. (NOTE: the rolls
should be free to turn)
2. With one end of the rope secured, hang a known
weight, equally over the roll so that the total tension is
equal to the maximum strip tension specified on the
calibration sheet, at the other end. (See Figure 9A)
For larger tension where dead weights would be too
large, a crane scale can be used to simulate maximum
strip tension (See Figure 9B)
3. With a voltmeter connected to the bottom Terminals 3
and 4 of the Terminal Board, maximum output voltage
will be observed.
4. Repeat Step3for the loadcell mounted on the opposite
end of the measuring roll.
5. Recheck to make certain that all leads are dressed
away from the LVDT crossbar assembly on both
loadcells and replace both conduit box covers.
Comptrol loadcells instrumentation provides the required
signal conditioning and a reliable high level output signal
for use as feedback control of a tension drive system.
The feedback signal is directly proportional to the strip
tension applied. If a Comptrol control is used, refer to the
control manual for further calibration.
Although the electrical output of Comptrol loadcells are
sufficient to drive most electrical indicators, substantial
signal conditioning is normally required for effective
tension instrumentation system control. Refer to the
documentation available from the instrumentation
supplier for more information.
II-J VISCOUS DAMPER ADJUSTMENT
The Viscous Damper allows for adjustment of the
loadcell output signal for signal fluctuations resulting
from such conditions as slight roll imbalance,
variations in the strip material, or the operation of the
machine.
The calibrated dial is graduated from "0" to "10". The
damping effect is minimum at "0" and maximum at"10".
Adjustment between these two points is stepless.
Because the need for damping becomes apparent
only
under dynamic conditions, damper
adjustment must be
made while the strip is moving
through the process at
normal speed.
NOTE:For bestperformancetheViscousDamper should
be set as close to zero as possible without the
mechanical stop contacting the load plate.
To Adjust the Viscous Damper:
1. Connect a chart recorder to the
Terminal 3 and 4 on the bottom of the
Terminal Board.
2. Record the loadcell output signal
while the line is running. The chart
will show the frequency and
amplitude oftheoscillation ofthe
topplate.
3. Using
a
3/16-inch hex key,
rotate
the adjustment dial
clockwiseor counterclockwise
alongthecalibrated scale,until thevariation of the
fluctuation of the output signals minimal.
NOTE: Rotating the dial beyond the "0" or "10"
markings on the scale has no effect on the Damper
Adjustment.
PART Ill - TROUBLE SHOOTING
When properly installed in accordance with the original
design specifications, Comptrol should require little or no
regular maintenance or service.
Certain conditions, however, can impair their inherently
accurate and reliable performance. Therefore, if trouble
should arise, the following conditions should be checked.
III-A MECHANICAL
1. Has the tension measuring system been changed?
a. An increase or decrease in web tension. (Refer to A
on the calibration sheet for specified web tension)
b. An increase or decrease in the wrap angle. (Refer
to B on the calibration sheet for the specified wrap
angle)
If any of the above parameters have been
changed, recalibration may be required. (Refer to
Recalibration Procedure, Page 8)