Conotec i300 User manual

Thank you for using our CONOTEC’s products.
Please, be sure to read "Handling Precautions" before use, and use this product correctly.
After reading this user manual, keep it in a place where you can see at any time.
It will be much more convenient when you use this product after reading this user manual.
Manual Version: V1.0

This instrument is suitable for the following environments:
Ambient Temperature: 0℃~60℃
Ambient Humidity: Less than 80% RH
Rated Power: 110VAC~220VAC ± 10% 50/60Hz
Major Products and Developments
-Digital Temperature/Humidity Controller
-Digital Timer, Current/Voltage Meter
-Other Product Developments
※ CONOTEC’s services are also the best.
Through our dealer where you purchased this product, you can report on the failure or
discomfort in use.
To improve the performance of the products, the specifications of this product are
subject to change without prior notice.
Please well understand the specified contents in the precaution interval when handling
this product, and be sure to comply with them.

Switch and Display
Menu Road Map
Basic Menu
Detailed Temperature Setting
Communication Control Output
Others
Contents
Handling Precautions
Components
Product appearance and panel processing dimension
Terminal wiring methods and input/out specifications
Special Feature
Quality Warranty

Handling Precautions
Thank you for purchasing our CONOTEC’s products.
In order to use this product, please be aware of the details below.
Safety Precautions
Warnings
1. This product has not been manufactured as a safety device; therefore, in the
case that this product is going to be used for controls, such as devices from
which you feel concerned about personal injury, serious damage to the
peripheral devices and enormous property damage, please use it with double
safety devices attached.
2. Please do not connect, inspect or repair it when power is on.
3. The panel must be attached to use. It can be the cause of electric shock.
4. When connecting power, please be sure to identify the terminal number and
connect them.
5. Please never disassemble, process, improve or repair this device.
Caution
1. Prior to installation of this instrument, please well understand the safety
regulations, warnings and how to use and use this device only within its
specified relevant specifications or capacity.
2. Do not install or wire it on the motors and solenoids, etc. which are extremely
inductive loaded
3. When extending sensors, please use the same lines and do not make them
longer than necessary.
4. Do not use any parts which cause arc when directly opened or closed at the
same power or its nearby.
5. Please keep the power line away from the high-tension power cable, and do
not install it in a place where water, oil or dust is severe.
6. Please do not install it in the place of being exposed to direct sunlight or rain.
7. Please do not install it in the place of strong magnetism, noise, severe
vibration and shock.
8. Please keep it away from the place where strong alkaline and strong acidic
materials directly come out.
9. Do not spray water directly onto the device for the purpose of cleaning during
the installation in the kitchen
10. Do not install it in a location where the temperature /humidity exceed the
rated ones.
11. Please use it with the sensor wire not being broken or scratched.
12. Use an independent pipe and keep the sensor wire away from the signal line,
power and load wires
13. Please note that the follow-up services are not available when arbitrarily
disassembling or modifying this product.
14. A display on the terminal connection diagram is a safety phrase of caution or
warning.

15. Do not use near devices causing strong high-frequency noise
(high-frequency welders, high-frequency sewing machines, high-frequency
radios, large SCR controller).
16. When using methods other than specified by the manufacturer, injury or
property damage may occur.
17. Please keep out of children’s reach, since it is not a toy.
18. Please install it by the related professional or qualified person.
19. When wiring the product, terminals and screws should be tightened with
sufficient torque. Contact failure may cause a fire.
20. Do not use a load that surpassed the rated value of switching capacity of
relay contact point. This may cause insulation failure, contact weld, and
poor contact.
21. We disclaim all the responsibility for damages caused by the negligence
of the consumer or by not complying with a warning or caution statements
specified above.
Danger
Caution, danger of electric shock
1. Electric shock – Please do not touch the AC terminals while the power is
on. You may get an electric shock.
2. When checking the input power, please be sure to shut off the input power.

Components
Product
Bracket Sensor

Product appearance and panel dimension
Product dimension
Unit Error
Panel processing dimension

Terminal wiring methods and input/out specifications
Input Voltage
Output Voltage: The same as input voltage
Output contact capacity: Relay contact output (5A 250VAC)
Input Port: 3 Ports no power contact
Output Port: 7 Ports
Sensor
Temperature Range
Input Port Port Output Port
Port
Sensor
Temp.
Comm. Port
Comm.

Special Feature
and Touch Function
With TET-LCD and touch, much information and colors can be
displayed and easy operation and recognition support a user-oriented
interface.
※ The product uses a capacitive touch method and thus requires
precautions as the key may cause malfunction if touched with wet
hands or used with thick gloves.
Central Monitoring Control Function
The product is embedded with the RS485 communication function to
be connected to a computer. It uses the Modbus protocol to be used
with the MMI (Man Machine Interface) system.
Alarm history store
Up to 20 alarm histories can be stored, which helps to analyze the
cause of problems and maintenance.
Compact and Slim
The integrated display and control ensure sufficient space.
Preheating and freeze protection
The function to prevent a breakdown of water pipes and equipment
due to water frozen in the cold weather.
Pump operation is configured according to user convenience for
effective control and management
Pump manual/auto operation mode function

Switch and Display
Power: A button to start or stop a system.
Cancel: A button to move to the previous menu at the time of setting or to return to the
basic screen
Pump: A button for automatic operation of the pump operation mode / and to switch to the
manual operation
Top: A button to move to the menu in the setting or a button that increases the setpoint
upon changing
Bottom: A button to move to the menu in the setting or a button that decreases the setpoint
upon changing
Check: A button to enter the setting menu or to select setpoint.
Displays the current temperature (PV) or sensor errors
Displays the set temperature (SV)
Displays the current time
Displays the operation mode of the current pump
SV output status icon
Pump output status icon
Comp. output status icon
Heater output status icon
Alarm output status icon
Repair and maintenance alarm icon
Buzzer operation status icon
The output status icon is displayed only, and in delay time when not in operation.
When the icon starts moving, the output will be ON.

System
press
for 5
seconds
For more details on blackout restoration / delay time, refer to pages 14-15.
Output status / The current time (the telephone number to the
installer) / View alarm history
press
for 5
seconds
press
for 5
seconds
press
for 5
seconds Warning
history
delete
Pressing the button once without entering various menus in the main screen shows the
operation status, time, the contact number to the installer and alarm histories.
Menu Load Map

Pump Operation Mode Change
The system should be stopped to change the mode of pump operation.
Mute Mode
How to change the setpoint
When the alarm buzzer goes off, the buzzer sound can be turned off by
activating the mute mode.
press for
5 seconds
Move the cursor (a finger) by using the up/down key in the menu.
Place the cursor on the item for settings and press the set key. This will
change the value you wish to change to a black square and you can change
the value by using up/down key.
Pressing the set key again completes the change.
When the system is in operation, the operation mode of the pump or the
setpoint cannot be changed.
(However, the basic temperature setpoint can be changed.)
To change, press the power for 5 seconds to stop the system.
press for
5 seconds

Basic temperature settings
Detailed Menu Settings
See Page 15
See Page 15
press for
5 seconds
See Page 16

See Page 19
See Page 19
See Page 19
See Page 19
See Page 18
See Page 19

Basic Menu
Basic Temperature Settings
Setting
Temperature
Deviation
Setting Temperature
Factor
Reset Setting range Unit
Setup the basic temperature for operation
Temperature Deviation
A regular interval is required between ON and OFF in the ON/OFF control
(set up ON/OFF width)
Frequent ON and OFF will shorten the lifespan of the relay or the output
contact or cause hunting (generation, chattering) by noise from outside.
The temperature deviation function is used to setup temperature deviation
to protect the equipment contact, etc.
Temperature Control Example
Point for output ON
Point for output OFF
Setting Temperature 5.0℃, Temperature Deviation: 1.0℃
Current Temperature > Setting Temperature + Temperature Deviation → Output ON
Current Temperature ≤ Setting Temperature → Output OFF

Detailed Temperature Setting
Detailed Temperature Setting
Setting Range UnitFactory ResetSetting Item
Temperature Deviation
Setting Temperature
Sensor Calibration
Temperature Setting
The same as the default temperature settings (See page 14)
Temperature Deviation
The same as the default temperature settings (See page 14)
Sensor Calibration
While there is no problem in the product, if the temperature shown in the
display window and the actual temperature are differed, the function calibrates
the current temperature and adjusts to the actual temperature.
E.g.) Actual Temperature: 20.0℃ / Display Temperature: at 25.0℃
If the sensor calibration value is set at -5.0, the current temperature is
displayed at 20.0℃.
Delay Time Setting
Comp. Delay Time
Factory Reset
Setting Item
Pump Delay Time
Pump Down Time
Setting Range Unit
Sec.
Sec.
Sec.
Comp. Delay Time
If the control target repeats ON/OFF frequently and causes problems:
(Freezer, compressor, etc.)
A function to protect the machine in operation when power is re-applied
or momentary power failure
Setting
Temperature Deviation Comp.
Output Delay Comp. ON
E.g.) Suppose the output delay time is 60 seconds, the delay time is
(60 seconds) from to and the relay will be ON in .

Prevent problems from occurring caused by the operating devices frequently
turn ON/ OFF when the power is unstable or power failure frequently occurs.
Stop Delay
When stopping the system, all the outputs except the pump are turned OFF,
only the pump output is maintained for the delay time, and OFF.
If the compressor is turned OFF when it is in operation, cold water may freeze
cold water and piping caused by cold air, so cycle pump as much as delay
time and all outputs OFF.
solenoid
valve Pump Down Comp.
Stop Delay Comp.
E.g.) Suppose pump down is 10 seconds and Comp. stop delay time is 10
seconds: After the occurrence of solenoid valve OFF section and the
time (10 seconds) from to ), and Comp. OFF after time delay
(10 seconds) from to .
*If pump down is 0 second(s), the Comp. stop delay will occur after COMP
input signal.
Power operation setting
Unit
Sec.
Sec.
Setting Range
Blackout Recovery
Factory Reset
Setting Item
Stop Delay
Pump Delay Time
The same as the Comp. delay time (See page 13)
Pump Down Time
The function to setup the delay time until Comp. output comes to stop after
the solenoid valve is OFF upon the termination of cooling/heating/thermostatic
operation.
When the pump is down, satisfy one condition from time or low pressure input
to stop pump down operation.
solenoid valve
Comp.
Preheating
Anti-freezing
Blackout Recovery
Delay time when power supply or system operation

Before operation, the system is pre-heated as much as the set temperature
The function turns ON the heater output when the temperature is lower by
1.0℃ that the set temperature and when the system reaches the set
temperature, the function turns OFF the heater output.
The function is applied when the pump operation mode is in the manual mode.
Point for output ON
Pre-heat Operation: 4.0℃
Current Temperature < Setting Temperature - 1.0 (℃) → Output ON
Current Temperature ≥ Setting Temperature → Output OFF
System System
E.g.) Suppose stop delay time is 60 seconds, the system is turned OFF at ,
and the output of the SV/COMP in operation will be turned OFF.
And the system will be delayed until the time (60 seconds) of and the
pump relay will be turned OFF.
Pre-heat Operation (Pump Automatic Mode)
Before operation, the system is pre-heated as much as the set temperature
The function turns ON the heater output when the temperature is lower by
1.0℃ that the set temperature and when the system reaches the set
temperature, the function turns OFF the heater output.
The function is applied when the pump operation mode is in the manual mode.
Freeze Prevention (Pump Manual Mode)
Point for output OFF

Exterior Input Setting
Setting Item
Pump Input Time
Pump Input Type
Comp. Input Time
Comp. Input Type
Water Circulation Time
Water Circulation Type
Factor Reset Setting Range Unit
Sec
Sec
Sec
5 Sec.
5 Sec.
5 Sec.
Pump Input Time
The function detects signal of pump input during the setting time or sets
up detection time to set the alarm when not detected.
However, if it is set at '0', pump will not breakdown.
Pump Input Type
Comp. Input Time
The function detects signal of Comp. input during the setting time or sets
up detection time to set the alarm when not detected.
However, if it is set at '0', Comp. will not breakdown.
Comp. Input Type
Water Circulation Time
The function detects signal of the water circulation switch input during the
setting time or sets up detection time to set the alarm when not detected.
However, if it is set at '0', water circulation will not breakdown.
Water Circulation Type
RS485 Communication Setting
Factory Reset
Communication Code No.
Setting RangeSetting Item
Communication Speed
Communication Code No.
To use the RS485 communication, appoint area codes from 1 to 99.
Communication Speed
Controls communication speed.

Equipment Output Test
Setting Item
Valve
Pump
Comp.
Heater
Alarm
Comp. Preparation
Pump Preparation
Stop/On
Setting Range
Equipment Output Test
To test connected operation devices after installation, change the setpoint.
The setpoint will be reset to stop if exit the menu without saving the setpoint.
Current Time Setting
Setting Item Setting Range Unit
YY
MM
DD
Hr.
Min.
Sec.
Other Device Settings
Setting Item Setting Range
Language
Setpoint Reset
Contact number to the installer
Korean / English
Cancel / Reset
_ / 0-9
Language
All menus and the system language can be change between Korean and
English.
Setpoint Reset
The set point changes to the factory reset.
Contact number to the installer
- The function to input contact number to the installer
- The input number will be displayed in the main screen showing date.
※If the contact number is below 11 digits, the blank digit should be filled up
for normal display.
Table of contents
Other Conotec Controllers manuals
Popular Controllers manuals by other brands

Samson
Samson 2357-31 Mounting and operating instructions

Mitsubishi
Mitsubishi MELSEC-L Series user manual

Roland
Roland BRIDGE CAST owner's manual

Sleipner
Sleipner PHC-3 user manual

Webasto
Webasto SmarTemp Control fx Installation and operation instructions

Tetratec Instruments
Tetratec Instruments M16 Operation manual