Contrive Quad400 User manual

© 2000 CONTRIVE • B1401|400.EN 0211 1www.contrive.it
AUTOMATIC BURNER CONTROL SYSTEM
The burner control unit Quad400 is suitable for the
control of direct ignition burners up to 350 kW,
pursuant to EN 746-2.
Flame control by means of UV scanner or ionization
rod (even shared with ignition).
Time and cycle are configurable: the same device can
be used to control different types of gas and oil
burners, meeting all relevant requirements.
A led-bar flame signal indicator and an advanced self-
diagnostic system provides the display of either the
cycle status, lockouts and failures.
A traditional electric interface allows remote control:
Thermostat input
Remote reset input
Burner on (dry contact output) or 2nd stage control
Burner lockout (dry contact output)
SAFETY INFORMATION
Read and understand this manual before installing, operating, or servicing this unit. This unit must be installed
according to this manual and local regulations. The drawings may show units without covers or safety shields to
illustrate details. Disconnect power supply and follow all usual safety precautions before carrying out any operation
on the device. Be sure to reinstall covers or shields before operating any devices.
The device is not user serviceable, a faulty device must be put out of order and sent back for servicing.
CONTRIVE manufactures products used as components in a wide variety of industrial systems and equipment. The
selection and application of products remain the responsibility of the equipment manufacturer or end user.
CONTRIVE accepts no responsibility for the way its products are incorporated into the final system design. All
systems or equipment designed to incorporate a product manufactured by CONTRIVE must be supplied to the end
user with appropriate warnings and instructions as to the safe use and operation of that part.
Any warnings provided by CONTRIVE must be promptly provided to the end user.
CONTRIVE guarantees for two years from the date of manufacture of its product to replace, or, at its option, to
repair any product or part thereof (except fuses and with some limitations for tubes and photocells) which is found
defective in material or workmanship or which otherwise fails to conform to the description of its sales order.
CONTRIVE makes no warranty of merchantability or any other warranty express or implied. CONTRIVE assumes no
liability for any personal injury, property damage, losses, or claims arising from misapplication of its products.
CONFORMITY
Gas Equipment Directive (90/396/EEC)
Low Voltage Equipment Directive (73/23/EEC)
Machinery Directive (89/392/EEC)
EMC Directive (89/336/EEC)
EN298 compliant
EN230 compliant
EN746-2 compliant
DVGW type certification No. CE-0085BM0346
Certified by Gosstandart pursuant to GOST-R

© 2000 CONTRIVE • B1401|400.EN 0211 2www.contrive.it
INTERNAL LABEL
Please perform the following tasks after receiving the product:
Inspect the unit for damage. If the product appears damaged upon receipt, contact the shipper immediately.
Verify receipt of the correct power supply voltage option by checking the label.
If you have received the wrong model or the device does not function properly, contact your supplier.
FRONT PANEL
INTERNAL
FITTING SCREWS
1
7
POWER SUPPLY FUSE
FLAME SIGNAL BARGRAPH
2
8
MAIN TERMINAL BOARD
STATUS DISPLAY
3
9
EXPANSION TERMINAL BOARD
RESET / SHUTOFF BUTTON
4
DEVICE DATA
QR CODE
CONFIGURATION
SERIAL NUMBER

© 2000 CONTRIVE • B1401|400.EN 0211 3www.contrive.it
WIRING DIAGRAM
01 POWER SUPPLY PHASE
02 POWER SUPPLY NEUTRAL
03 GROUND
04 TRAXBUS INTERFACE POSITIVE (UNAVAILABLE)
05 TRAXBUS INTERFACE NEGATIVE (UNAVAILABLE)
06 GROUND
07 GAS VALVE (V1)
08 POWER SUPPLY NEUTRAL
09 IGNITION TRANSFORMER OUTPUT
10 POWER SUPPLY NEUTRAL
11 FLAME DETECTOR INPUT (ROD, UV-)
12 GROUND
21 INPUTS COMMON RETURN
22 THERMOSTAT INPUT
23 RESET INPUT
24 BURNER ON CONTACT RETURN
25 BURNER ON CONTACT RETURN
26 BURNER ON CONTACT OR MAIN GAS VALVE (V2)
27 BURNER LOCKOUT CONTACT RETURN
28 BURNER LOCKOUT CONTACT
LEXTERNAL LIMITS
USE POWER, SIGNAL AND CONTROL CABLE SUITABLE FOR THE TYPE OF OPERATION AND COMPLYING WITH ALL REGULATIONS
DO NOT ROUTE CONNECTIONS TOGETHER WITH FREQUENCY CONVERTER CABLES OR CABLES EMITTING STRONG FIELDS
PROVIDE RELIABLE CONNECTION TO PE (PROTECTION EARTH) AND BURNER FRAME, RECOMMENDED WIRE GAUGE > 4 mm2
ALL ELECTRONIC SYSTEMS MUST BE SUPPLIED BY A DEDICATED TRANSFORMER IN A TN-S EARTHING SYSTEM
USE UNSCREENED HIGH-VOLTAGE CABLE FOR IGNITION AND IONIZATION ROD LINES, LAYING CABLES INDIVIDUALLY, AVOIDING
METAL CONDUITS. KEEP HIGH VOLTAGE IGNITION CABLES AS SHORT AS POSSIBLE, AVOIDING LOOPS AND KEEP ALL OTHER
CABLES, ESPECIALLY THOSE OF UV OR IONIZATION ROD, AS FAR APART AS POSSIBLE
OUTPUTS AT TERMINALS 24 25 26 27 ARE SPST UNPROTECTED DRY CONTACTS, LOAD MUST BE WITHIN THE RATED CURRENT
POWER SUPPLY FUSE
The device and following burner loads are protected by means of an embedded POWER SUPPLY FUSE [7]:
TERMINAL 07 : GAS VALVE V1 TERMINAL 09 : IGNITION TRANSFORMER
This fuse must be replaced only with same type and value component: 3,15 A quickblow (5x20mm).
STATUS DISPLAY
The STATUS DISPLAY [4] gives, at any time, a clear indication about the working conditions of both the burner and
the equipment, making it easier to detect any failure occurring in the system or the device.
WARNINGS
SELF-TEST
SELF DIAGNOSIS, EVERY TIME THE UNIT IS
POWERED OR THE BURNER IS STARTED.
CONFIGURATION
UNIT IN CONFIGURATION MODE THROUGH
COMMUNICATION LINK.
LIFETIME EXPIRED
MAINTENANCE REQUIRED AFTER 500.000
IGNITIONS. PUSH AGAIN TO START ANYWAY.

© 2000 CONTRIVE • B1401|400.EN 0211 4www.contrive.it
CYCLE
MANUAL SHUTDOWN
UNIT HAS BEEN PUT OUT OF SERVICE FROM
PUSH BUTTON. PUSH AGAIN TO RESTORE.
IGNITION
1ST SAFETY TIME. BURNER IGNITION TRIAL
WITH PILOT GAS VALVE OPEN.
TIMER SHUTDOWN
BURNER HAS BEEN TURNED OFF BY
OPTIONAL INTERNAL TIMER.
PILOT BURNER ON
PILOT GAS VALVE IS OPEN, BURNER ON
UNTIL SHUTDOWN, LOCKOUT OR FAILURE
THERMOSTAT SHUTDOWN
BURNER HAS BEEN TURNED OFF BY LOCAL
THERMOSTAT AT TERMINAL 22.
POSTCOMBUSTION
WAITING FOR FLAME QUENCHING AFTER
LOCKOUT OR SHUTDOWN REQUEST.
PREPURGE
PURGE OF COMBUSTION CHAMBER OR MIN
TIME FOR ILLEGAL FLAME PROVING.
POSTPURGE
PURGE OF COMBUSTION CHAMBER, SHOWN
TOGETHER WITH ASSOCIATED CODE.
LOCKOUTS
STANDBY
WAITING FOR RESET WHEN PROGRAMMED
FOR STANDBY MODE AT POWER-ON.
FLAME LOSS
FLAME QUENCHING DURING NORMAL
BURNER OPERATION.
ILLEGAL DETECTION
PARASITE FLAME DETECTION DURING PRE-
PURGE, POSTPURGE OR POSTCOMBUSTION.
CONTROL BOARD COM FAILURE
EXPANSION CONTROL BOARD IS MISSING OR
NOT WORKING PROPERLY.
IGNITION FAILURE
NO FLAME DETECTED AT THE END OF
IGNITION TRIAL, 1ST SAFETY TIME.
RESETABLE FAILURES
IGNITION DEVICE FAILURE
IGNITION DEVICE UNPLUGGED, DEFECTIVE
OR NOT WORKING PROPERLY.
MISSING GROUND JOINT | SOFT JUMP
POOR SPARK RETURN PATH (I.E.: BAD
GROUND CONNECTION TO BURNERS HEAD).
GAS VALVE FAILURE
GAS VALVE(S) UNPLUGGED, DEFECTIVE OR
NOT WORKING PROPERLY.
STRONG EMI | CONFIG ERROR
ELECTRO MAGNETIC INTERFERENCE ABOVE
ADMISSIBLE LIMIT, CONFIGURATION ERROR.
OUTPUT RELAYS FAILURE
SHORT CIRCUIT ON OUTPUT RELAY CONTACT
LOADS DISCONNECTED BY SAFETY RELAY.
TIMEBASE FAILURE
MISMATCH BETWEEN 1ST AND 2ND INTERNAL
TIMEBASE GENERATORS.
CONTROL BOARD ERROR
WRONG OPERATION OF CONTROL BOARD,
ILLEGAL COMMAND
SYSTEM WATCHDOG
MICROPROCESSOR ISN’T OPERATING
PROPERLY.
NON RESETABLE FAILURES
PUSH BUTTON FAILURE
PUSH BUTTON FOUND CLOSED AT SELF TEST.
FAILURE OR AVOID PUSHING DURING TEST.
MASTER SAFETY RELAY FAILURE
SHORT CIRCUIT ON SAFETY RELAY CONTACT.
OUTPUT RELAYS WILL DISCONNECT LOADS.
SYSTEM ERROR
PROGRAM ERRORS, CORRUPTION IN
FIRMWARE MEMORY.

© 2000 CONTRIVE • B1401|400.EN 0211 5www.contrive.it
SINGLE STAGE GAS BURNER
When the equipment is used for gas burners, the prescriptions set forth in the European Standard EN298 (including
any further revision) must be completely fulfilled, along with the specific requirements of any National regulation in
force in the Country where the equipment is installed.
Combustion air and optional process limits are controlled by external circuitry.
A complete self test is deployed at power-on and at any reset from lockout, possible failures are reported on the
front panel display. A flame simulation test is carried out during Prepurge.
The gas valve will be activated only if the ignition device is detected (power supply current) during preignition time.
The gas valve remains open during the programmed safety time, if a valid flame signal is detected within the safety
time the valve is kept open: the burner is on and 3 seconds later the contact at terminals 25/26 will be closed.
If no flame is detected the system will lockout and contact at terminals 27/28 will be closed.
Push the front panel button or close the reset input at terminal 23 to reset from lockout (will take place at release).
Flame quenching during burner operation will force the system to lockout, recycle or respark.
There are different options to operate the burner:
switching on/off the power supply;
pressing the front panel button (manual shutdown);
by means of thermostat input (halt);
internal timer (if enabled).
A postcombustion time (max 20 seconds) is allowed after a lockout or shutdown request, followed by pospurge.
The device can stop the burner after programmed auto shutoff time (5m to 20h50m) of continuous operation and
restart again, providing that all the equipment and burner safety tests are successfully performed.
EXTERNAL LIMITS
THERMOSTAT
F
LINE FUSE
RESET INPUT
K
BLOWER POWER RELAY
BURNER LOCKOUT
RT
BLOWER THERMAL PROTECTION
BURNER ON
M
BLOWER MOTOR
DUAL ROD CIRCUIT
PA
LOW AIR PRESSURE SWITCH
UV SENSOR
GAS VALVE
SINGLE ROD CIRCUIT
ALL SAFETY SWITCHES SHOULD BE APPROVED AS LIMIT CONTROLS
THE USE OF ELECTRONIC SWITCHES MAY CAUSE ERRATIC OPERATIONS

© 2000 CONTRIVE • B1401|400.EN 0211 6www.contrive.it
DUAL STAGE GAS BURNER
Contact output at terminal 25/26 can be used to manage a dual stage burner.
First stage intermittent gas valve is connected to terminal 24 (internally connected to terminal 25) and wired to
terminal 7 (gas valve output). This output is kept open once the flame signal is detected.
Second stage gas valve is connected to terminal 26 and powered 3 seconds after pilot burner successfully ignited.
Both valves are turned off when flame quenches or following any lockout or shutdown request.
In the following example the ignition and detection of the first stage is achieved by means of shared rod, an UV
detector could be installed on the 2nd stage of the burner. Both detectors are connected in parallel to same input.
Any lockout will turn on the alarm output at terminal 28.
Push the front panel button or close the reset input at terminal 23 to reset from lockout. The reset will take place
only when the button or contact are released.
Input at terminal 23 is meant for reset purpose only, no action is performed closing this input while burner is
running.
EXTERNAL LIMITS
THERMOSTAT
F
LINE FUSE
RESET INPUT
K
BLOWER POWER RELAY
BURNER LOCKOUT
RT
BLOWER THERMAL PROTECTION
PILOT SINGLE ROD
M
BLOWER MOTOR
MAIN UV SENSOR
PA
LOW AIR PRESSURE SWITCH
PILOT GAS VALVE
MAIN GAS VALVE
ALL SAFETY SWITCHES SHOULD BE APPROVED AS LIMIT CONTROLS
THE USE OF ELECTRONIC SWITCHES MAY CAUSE ERRATIC OPERATIONS

© 2000 CONTRIVE • B1401|400.EN 0211 7www.contrive.it
OIL BURNER
When the equipment is used for oil burners, the prescriptions set forth in the European Standard EN230 (including
any further revision must be completely fulfilled, along with the specific requirements of any National regulation in
force in the Country where the equipment is installed.
Combustion air and optional process limits are controlled by external circuitry.
A complete self test is deployed at power-on and at any reset from lockout, possible failures are reported on the
front panel display. A flame simulation test is carried out during Prepurge.
Ignition device is activated during Prepurge time for oil burners (long preignition).
The fuel valve will be activated only if the ignition device is detected (power supply current) during preignition time.
The fuel valve remains open during the programmed safety time, if a valid flame signal is detected within the safety
time the valve is kept open: the burner is on and 3 seconds later the contact at terminals 25/26 will be closed.
If no flame is detected the system will lockout and contact at terminals 27/28 will be closed.
Push the front panel button or close the reset input at terminal 23 To reset from lockout (will take place at release).
Flame quenching during burner operation will force the system to lockout, recycle or respark.
There are different options to operate the burner:
switching on/off the power supply;
pressing the front panel button (manual shutdown);
by means of thermostat input (halt);
internal timer (if enabled).
A postcombustion time (max 20 seconds) is allowed after a lockout or shutdown request, followed by pospurge.
The device can stop the burner after programmed auto shutoff time (5m to 20h50m) of continuous operation and
restart again, providing that all the equipment and burner safety tests are successfully performed.
EXTERNAL LIMITS
PA
LOW AIR PRESSURE SWITCH
F
LINE FUSE
THERMOSTAT
K
BLOWER POWER RELAY
RESET INPUT
RT
BLOWER THERMAL PROTECTION
BURNER LOCKOUT
M
BLOWER / PUMP MOTOR
BURNER ON
OH
OIL HEATHER
UV SENSOR
OW
OIL THERMOSTAT
FUEL VALVE
QUAD USES UV SCANNER FOR OIL, INCREASING SAFETY AND RELIABILITY
IGNITION DEVICE MUST BE SUITABLE FOR LONG PREIGNITION TIMES

© 2000 CONTRIVE • B1401|400.EN 0211 8www.contrive.it
PARAMETERS
HARDWARE
Q001 POWER SUPPLY VOLTAGE 230 Vac 230
115 Vac 115
F003 PROCESS INPUTS VOLTAGE 230 Vac 2
115 Vac 1
48 Vac 8
24 Vac 4
Q002 ENCLOSURE LIGHT ALUMINIUM N
STANDARD ALUMINIUM A
LOW PROFILE ALUMINIUM B
POLYCARBONATE P
BEHAVIOUR AT POWER ON –LOCKOUT
Q101 START-UP MODE AUTOSTART A
STANDBY S
BEHAVIOUR DURING PREPURGE
Q305 PREPURGE TIME 1” … 001
DEFAULT 1”… 250” 250
BEHAVIOUR DURING IGNITION
Q401 PRE-IGNITION TIME 0,5”
Q402 STARTUP SAFETY TIME 2” … 02
DEFAULT 3”… 25” 25
BEHAVIOUR DURING OPERATION
Q507 OPERATING SAFETY TIME 1” … 01
DEFAULT 1”… 12” 12
Q508 ALLOWED POSTCOMBUSTION TIME < 20”
Q509 AUTO-SHUTOFF TIME 00:05 … 01
20:50 … FA
Q510 AUTO-SHUTOFF MODE OFF –
MANUAL M
AUTOMATIC A
Q512 FLAME LOSS LOCKOUT L
RECYCLE C
RESPARK K
BEHAVIOUR DURING POSTPURGE
Q602 POSTPURGE TIME 1” … 001
DEFAULT 1”… 250” 250
GENERAL SETTINGS
Q801 BURNER TYPE GAS G
OIL O
F809 DEVICE NOTES
F810 DEVICE PASSWORD
Q001 –POWER SUPPLY VOLTAGE
Power supply must be wired at terminal 01 and 02, for burner control unit and
loads (air and gas valves and ignition transformer), both protected by the
embedded fuse.
Optional safety interlock limits could be wired on the main supply phase.
F003 –PROCESS INPUT VOLTAGE
Inputs from external thermostat and remote reset are independent from device
and burner power supply, allowing an isolated interface.
Different voltage options are available.
The use of electronic switches may cause erratic operation

© 2009 CONTRIVE • B1401|400.EN 0211 9www.contrive.it
Q002 –ENCLOSURE
Quad600 is available in 4 different enclosure options. Standard version is N, all other types are available on request.
According to European Standard EN60529 a minimum protection degree IP40 must be guaranteed, raised to IP54 for
open air application.
1 EXTERNAL FITTING HOLES (4) 106 x 186 mm
4.2 mm SELF TAPPING OR M5 THREAD FORMING SCREW
2 BREAKABLE FITTING HOLES (4) 77 x 182 mm
4,0 mm DIAMETER
3 BREAKABLE HOLES FOR WIRING (4) Ø 19,0 mm
SUITABLE FOR PG11 CABLE GLAND
4 BREAKABLE HOLES FOR WIRING (4) Ø 15,5 mm
SUITABLE FOR PG9 CABLE GLANDS
CAST ALLUMINIUM ALLOY EN AB 46100 IP65
OVERALL DIMENSION: 200 x 120 x 71 mm WEIGHT: 1180 g
ELECTROSTATIC POLYESTER POWDER COATING COLOR: GRAY
OPTIONAL FITTING CLAMPS FOR PIPES
VERTICAL MOUNTING OUTSIDE DIAMETER 6 … 76 mm
HORIZONTAL MOUNTING OUTSIDE DIAMETER 6 … 63 mm
N
P
A
B
CAST ALUMINIUM ALLOY
200 x 120 x 92 mm | 1560 g
CAST ALUMINIUM ALLOY
200 x 120 x 71 mm | 1350 g
POLYCARBONATE UL-V0
200 x 120 x 96 mm | 800 g
ALUMINIUM ENCLOSURES MUST BE
CONNECTED TO PROTECTIVE EARTH

© 2009 CONTRIVE • B1401|400.EN 0211 10 www.contrive.it
Q101 –START-UP MODE
At power-on, once the self-test has been successfully completed, the unit waits in
STANDBY mode until a reset operation is performed from local push button or
through a fieldbus remote command. Setting AUTOSTART mode, the cycle starts
automatically, unless the units has been turned off while in lockout.
Q305 –PREPURGE TIME
Set prepurge time in forced draught burners according to EN 676 requirements.
Any air valve and/or butterfly valve controlled by external process must be kept
open during the whole prepurge time.
During this time an illegal flame test is carried out.
Q401 –PRE-IGNITION TIME
The ignition transformer is turned on 500 ms before the gas valve to check the
correct operation before to open the gas.
This is a fixed time and cannot be changed.
Q402 –STARTUP SAFETY TIME
Set the correct time following EN 746-2 (or other relevant) requirements:
Natural draught burners ≤ 70 kW → 10” > 70 kW → 5”
IGNITION POWER ≤33% NOMINAL POWER WITH MAXIMUM OF 350 KW
Forced draught burners ≤ 350 kW → 5” >350kW→3”
IGNITION POWER ≤ 10% NOMINAL POWER WITH MAXIMUM OF 350 KW
Q507 –OPERATING SAFETY TIME
If the flame fails during operation, gas valve is switched off within this safety time
that must be in accordance with relevant application standards (default for EN 298
is 1” and must not exceed 3” including valves closing time for EN 746-2).
F508 –ALLOWED POST-COMBUSTION TIME
The flame signal is allowed for 20” once gas valve has been closed.
Lockout occurs if the flame is detected after the post-combustion time.
Q509 –AUTO SHUT-OFF TIME
An automatic shutoff is performed after the specified time since burner on.
Q510 –AUTO SHUT-OFF MODE
Behavior after an automatic shut-off. In AUTOMATIC mode a complete burner
restart cycle is deployed, performing the test of the whole system, as per Standard
requirements, within 24 hours of continuous operation.
In MANUAL mode the burner waits for reset.

© 2009 CONTRIVE • B1401|400.EN 0211 11 www.contrive.it
Q512 –FLAME LOSS
Determines the behavior at flame loss during normal burner operation.
For burners with occasionally unstable flame signal a single recycle (including
prepurge) or direct respark can be attempted. The setting is to be determined on
the basis of burner capacity and relevant application standard.
Q602 –POSTPURGE TIME
Follow EN 676 requirements to set correct postpurge time in forced draught
burners. Any air valve and/or butterfly valve controlled by external process must
be kept open during the whole postpurge time.
During this time an illegal flame test is carried out.
Q801 –BURNER TYPE
Selecting OIL type burner the ignition device will be activated also during the
prepurge to allow the detection of oil leakage that will be ignited, leading to an
illegal flame detection. Application and settings must be made in accordance to
EN 230 (or other relevant standard) requirements.
A SELF TEST IS PERFORMED IN LESS THAN 1”,
ONCE SUCCESSFULLY COMPLETED THE BURNER
IS READY TO START.
IF THE UNIT HAS BEEN TURNED OFF WHILE IN
LOCKOUT OR PARAMETER Q101 HAS BEEN SET
TO STANDBY, IT WILL BE NECESSARY TO RESET
THE UNIT BY MEANS OF LOCAL PUSH BUTTON.
A FLAME SIMULATION CHECK IS CONDUCTED
DURING WAITING OR PREPURGE TIME.
AFTER THE PRESET WAITING OR PREPURGE
TIME HAS ELAPSED, THE IGNITION DEVICE IS
ACTIVATED AND VERIFIED, THEN THE PILOT
VALVE IS OPEN.
PILOT PROVING PERIOD STARTS IF THE FLAME
IS DETECTED WITHIN THE SAFETY TIME.
IF NO FLAME IS DETECTED DURING THE SAFETY
TIME A FAULT LOCKOUT OCCURS.
FLAME FAILURES DURING OPERATION LEADS
TO LOCKOUT RESTART OR RECYCLE DEPENDING
ON Q512 PARAMETER SETTING.
A SHUTDOWN REQUEST FROM THERMOSTAT
OR LOCAL PUSH BUTTON TURNS OFF THE
BURNER, WAITING FOR ALLOWED POST-
COMBUSTION AND POSTPURGE
AN AUTOMATIC SHUTOFF OF THE BURNER CAN
BE ACTIVATED, AFTER A PRESET TIME OF
BURNER RUNNING. THE BURNER CAN WAIT
FOR A MANUAL RESET OR RESTART IN AUTO-
MATIC MODE.
A SELF TEST IS MADE AT EVERY RESTART. THIS
PARAMETER MAY BE SET IN THIS WAY ONLY IF
THE BURNER CAN RESTART AS INTENDED IN ALL
OPERATING PHASES.
PROGRAM SEQUENCE

© 2009 CONTRIVE • B1401|400.EN 0211 12 www.contrive.it
TECHNICAL DATA
POWER SUPPLY
VOLTAGE 115 or 230 V +10-15%
FREQUENCY 50/60 Hz §1
LINE FUSE 3,15 A QUICKBLOW - 5x20mm
POWER CONSUMPTION 4 VA MAX
POWER DISSIPATION 3 W MAX
LIFECYCLE COUNTER 524288 IGNITIONS
§1 SINEWAVE, QUASI-SINEWAVE, SQUAREWAVE
FLAME DETECTION
MINIMUM IONIZATION CURRENT > 1 A
CURRENT LIMITATION 1 mA
SIGNAL DISPLAY 0…100 A
DETECTOR LINE LENGTH < 30 m
SINGLE ROD LINE LENGTH < 1 m
DETECTOR VOLTAGE 250 Vac
DETECTOR INSULATION > 50 M
ENVIRONMENT
OPERATING TEMPERATURE 0…60 °C
STORAGE TEMPERATURE -20…80 °C
PROTECTION CLASS (EN 69529) IP65
RELATIVE HUMIDITY 90% MAX
MOUNTING POSITION ANY
OUTPUTS
RATED VOLTAGE 250 Vac MAX
SWITCHING VOLTAGE 277 Vac MAX
LOAD CURRENT 3 A MAX
MINIMUM CURRENT 1 mA @ 5 V
BREAKING CAPACITY 750 VA MAX
PROCESS INPUTS
RATED VOLTAGE 230, 115, 48, 24 Vac
CURRENT 5 mA MAX
C O N F I G U R A T I O N
Q002
Q001
Q 8 0 1
Q 1 0 1
Q 3 0 5
Q 4 0 2
Q 5 0 7
Q 6 0 2
Q 5 1 2
Q 5 1 0
F 0 0 3
Q4
N
230
G
A
020
03
01
001
L
-
230
DEFAULT
DEVICE CLASSIFICATION ACCORDING TO EN298
A / B
M / B
L / C / R
L
B
N (B)
DEVICE CLASSIFICATION ACCORDING TO EN230
A / B
I / T / M
L / C / R
L
B
N (B)
CONTRIVE S.r.l. I-24040 SUISIO (Bergamo) via Enrico Fermi 18
ANY ILLUSTRATIONS, PHOTOGRAPHS, OR EXAMPLES USED IN THIS MANUAL ARE PROVIDED AS EXAMPLES ONLY AND MAY NOT APPLY TO ALL PRODUCTS TO
WHICH THIS MANUAL IS APPLICABLE. THE PRODUCTS AND SPECIFICATIONS DESCRIBED IN THIS MANUAL OR THE CONTENT AND PRESENTATION OF THE
MANUAL MAY BE CHANGED WITHOUT NOTICE TO IMPROVE THE PRODUCT AND/OR THE MANUAL.
PRODUCT NAMES, CORPORATE NAMES, OR TITLES USED WITHIN THIS DOCUMENT MAY BE TRADEMARKS OR REGISTERED TRADEMARKS OF OTHER COMPANIES,
AND ARE MENTIONED ONLY IN AN EXPLANATORY MANNER TO THE READERS’ BENEFIT, AND WITHOUT INTENTION TO INFRINGE.
WHILE EVERY EFFORT HAS BEEN MADE TO MAKE SURE THE INFORMATION IN THIS DOCUMENT IS CORRECT, CONTRIVE CAN NOT BE LIABLE FOR ANY DAMAGES
WHATSOEVER FOR LOSS RELATING TO THIS DOCUMENT.
© COPYRIGHT 2009 CONTRIVE SRL ITALY. ALL RIGHT RESERVED.
Table of contents
Other Contrive Control System manuals
Popular Control System manuals by other brands

Pilz
Pilz PNOZmulti installation manual

Altronic
Altronic DE-3000 operating instructions

Galaxy Control Systems
Galaxy Control Systems BIOSCRYPT L-1 Configuration & operation guide

HomeMatic
HomeMatic HM-Cen-3-1 Quick start instructions

Bosch
Bosch rexroth SYDFED 2X Series manual

Auper
Auper Eclipse 784 B Quick user guide