Speco A1 User manual

Speco Access Control System
Installation Instructions
for 1 Door Systems
Document Number: 100116-SP REV B
Installation Instructions for 1 Door Systems – July, 2019 Page 1

Table of Contents
Notifications...................................................................................................................................................3
Copyright...................................................................................................................................................3
Approvals...................................................................................................................................................3
Notice.........................................................................................................................................................3
Introduction....................................................................................................................................................4
Access Control Overview..........................................................................................................................4
System Overview.......................................................................................................................................4
1 oor System Specifications........................................................................................................................5
Installation of 1 oor Systems.......................................................................................................................6
Installation Check List...............................................................................................................................6
Locating the Controller for Installation.....................................................................................................6
Mounting the 1 oor System.........................................................................................................................7
Controller Features 1 oor Systems..............................................................................................................8
Controller Hardware Identification...........................................................................................................8
Controller Inputs........................................................................................................................................8
Controller Wiring Harnesses.....................................................................................................................9
Input Wiring...............................................................................................................................................9
Controller Outputs & Power Input..........................................................................................................13
Output Wiring Requirements...................................................................................................................13
Powering On and Connecting to a Network.................................................................................................16
Preparing for the Network.......................................................................................................................16
Connecting to the Local Network............................................................................................................17
Adding Clients to Systems......................................................................................................................18
IP Installer................................................................................................................................................19
System Configuration and Programming................................................................................................20
Trouble Shooting..........................................................................................................................................21
Testing, Maintenance and Service................................................................................................................23
Parts List.......................................................................................................................................................23
Contact & Warranty Information..................................................................................................................24
Installation Instructions for 1 Door Systems – July, 2019 Page 2

Notifications
Copyright
Copyright © 2019, all rights reser ed. No part of this document may be reproduced, copied,
adapted or transmitted in any form without written permission from Speco Technologies.
Approvals
This equipment has been tested and found to comply with the limits for a Class A digital de ice,
pursuant to part 15 of the FCC Rules. These limits are designed to pro ide reasonable
protection against harmful interference when the equipment is operated in a commercial
en ironment. This equipment generates and can radiate radio frequency energy and if not
installed and used in accordance with the manual, may cause harmful interference. Operation of
this equipment in a residential area is likely to cause harmful interference in which case the user
will be required to correct the interference at their own expense.
This Access Control System is compliant with Le el I UL 294 listed de ices and must be
installed in a controlled location.
Notice
This manual contains information regarding the basic installation and configuration of the
browser-based Access Control System. It must be read and completely understood before
installation or operation.
It is intended that this unit will be installed by persons trained and qualified to install access
control systems and has the skills and knowledge working with electrical circuits and safety
codes. Important safeguards and instructions in this manual cannot co er all possible situations
and conditions that occur during installation and use and it must be understood that common
sense and caution must be exercised by the person(s) installing, maintaining and operating the
equipment.
Installations must conform to all national and local building and electrical codes.
This manual is for installing 1 Door Systems, Model A1.
Installation Instructions for 1 Door Systems – July, 2019 Page 3

ntroduction
Access Control Overview
Access Control is the selecti e restriction to a place or resource such as a property, building or
room to authorized persons and is a matter of who, where, and when. An access control system
is used to automate access control using credentials, credential readers, electric door locks and
other de ices. Administrators configure the system to determine who is allowed to enter or exit,
where they are allowed to exit or enter, and when they are allowed to enter or exit. When access
is granted, the door is unlocked for a predetermined time and transaction is recorded. When
access is denied, the door remains locked and the attempted access is recorded. Administrators
can then run reports on the recorded transactions to re iew acti ity for selected dates and times.
System Overview
Controller models are a ailable in ariety of configurations starting from 1 Door models that
require a separate power supply to 2 & 4 Door models that include an integrated power supply
for the controller and door lock power. Most models can be upgraded after installation with
enhanced features, such as enhanced reporting or more users, using software license keys. All
controllers include tamper and power fault inputs, in and out readers, request to exit and door
position inputs for each door and auxiliary inputs and outputs. All controllers are designed to be
connected to a network using an Ethernet RJ45 connector and configured using the integrated
web ser er.
Controllers can be configured as either a ser er or a client. All systems require a ser er
controller. Some systems ha e the ability to add additional client controllers to increase the
number of doors, inputs or outputs or control ele ators. The software license key is used by the
controller to determine if it is a ser er or a client. After logging in, the license information about a
can be determined by clicking on the license icon at the bottom of the web page.
Certain models offer a mobile APP that can be used to setup and configure, iew logs, lock and
unlock doors and acti ate threat le els. In addition, some systems also offers a cloud ser ice
that pro ides a portal where a users or dealer can log into and manage one or many systems
securely.
Client controllers communicate with the ser er controller ia the local area network and are
configured through the ser er using a web browser on a PC connected to the network. Once the
ser er or client controller is configured, they will function without a network connection or the
PC. The network and PC is only required for setup, configuration and reporting.
Installation Instructions for 1 Door Systems – July, 2019 Page 4

1 Door System Specifications
General Specifications
Processor Quad Core Cortex, 1.5 GHz
Memory 1GB DDR3 & 8 GB eMMc
Operating System Embedded Linux
Transactions > 45 per Second
Power Requirements (excluding door locks) Regulated 12VDC @ 2A, Class 2 (not supplied)
Operating Temperature 50ºF to 95ºF (10ºC to 35ºC)
Enclosure Size (W x H x D) 3.2 x 3.0 x 1.3 in (81 x 78 x 32 mm)
Model A1
Standby Power Requirement 350mA @ 12V
Number of Doors 2 Total, One In & One Reader
Readers (Wiegand) 2 Total, One In & One Out Reader
Reader Power 300 mA @ 12V Max per Reader
600 mA @ 12V Max per System
Request to Exit (REX) Input 1
Door Position (status) Input 1
Auxiliary Input 1
Tamper Digital Input 1
Power Fault Digital Input 1
Door Lock Output 1 Form C Relay, 24V @ 1.0A
Auxiliary Output 1 Form C Relay, 24V @ 1.0A
UL294 7th Edition Rating
Destructi e Attack Line Security Endurance Standby Power
Single Point
Locking De ice
with Key Locks
Le el I Le el I Le el IV Le el I Le el I
Installation Instructions for 1 Door Systems – July, 2019 Page 5

nstallation of 1 Door Systems
nstallation Check List
The list below pro ides a logical sequence for installing a system. This list cannot co er all
possible situations and conditions that occur during installation and use and it must be
understood that common sense and caution must be exercised by the person(s) installing,
maintaining and operating the equipment.
✔Calculate the systems power requirement by adding up the power required
for each de ice connected to the system to make sure the required power
can be pro ided by the system.
✔Mount the controller in an enclosure that is located in a secure, controlled
location
✔Connect the inputs and outputs and tamper switch
✔Connect the readers
✔Connect the door lock and auxiliary output
✔Connect power to the controller using a dedicated 12 VDC, 2 AMP UL294B
listed power supply. Connect the power supply to an unswitched, grounded
outlet
✔Obtain an IP address, Subnet Mask, DNS and other information from the
network administrator
✔Configure the controller's network settings
✔Connect the controller to the local area network
✔Add optional license keys to upgrade features
Locating the Controller for nstallation
Choose a centrally located, secure, clean and dry area near an AC power source. A oid
mounting the controller within 6 feet of any equipment that may generate electrical interference.
NOTICE: The power supply used or the controller must only
be connected to an unswitched, grounded, 115 VAC outlet. I
an unswitched outlet is not available or within 6 eet o the
controller mounting location, have a licensed electrician install
an outlet per local codes. All wiring must be in accordance with
the National Electrical Code, NPFA 70 and all local codes. For
UL installations, t e maximum Et ernet, Input and Output
cable lengt is 98.5 feet (30 meters).
NOTE: This device complies with Part 15 o the FCC Rules.
Operation is subject to the ollowing two conditions: (1) this
device may not cause harm ul inter erence and (2) this device
must accept any inter erence received, including inter erence
that may cause undesired operation.
Installation Instructions for 1 Door Systems – July, 2019 Page 6

Mounting the 1 Door System
Using the pro ided mounting bracket, the 1 door controller can be mounted ertically or
horizontally in a UL listed enclosure with an integrated tamper switch, that is located in a secure
location. The aluminum heat sink should face away from the mounting surface with a minimum
of 1 inch (25.4 mm) of clearance abo e the heat sink. The temperature in the mounting location
must be within the system's specified limits. When running wires through knockouts in
enclosures, install bushings or conduit connectors as needed to protect wires from damage.
1. Run all wires to the controller's location and label the wires according to their use.
2. Locate the enclosure for the 1 door controller on the wall and le el. Mark the mounting
holes on the wall and remo e the enclosure and install anchors appropriate for the type
of wall and mounting conditions.
3. DO NOT DR LL the mounting holes while the enclosure is in place on the wall. Dust and
debris from drilling will contaminate and damage the electronics.
4. Partially insert mounting screws into the top two mounting holes and hang the enclosure
on the screws. Check for le el, insert the lower screws and tighten all four mounting
screws.
5. Using the pro ided mounting bracket as a template, locate the bracket in the enclosure
and mark the location of the mounting screws. The key holes in the bracket are sized for
#6 pan head self tapping screws. Drill the holes for the mounting screws and partly
thread the screws into the holes. Clean any debris from drilling to pre ent damage to the
electronics. Place the controller into the mounting bracket and hang on the mounting
screws. Check for le el and tighten the mounting screws.
6. Run the wires through the knockout holes and connect to the appropriate terminals (see
following sections of the manual for wiring details).
7. Connect the tamper switch to the controller's tamper inputs.
NOTICE: This equipment includes electronic components that
are sensitive to static electricity. Make sure to discharge by
touching an earth ground be ore handling this equipment.
NOTE: When locating the controller, choose a centrally located,
secure, clean and dry area. Avoid mounting the controller within
6 ee (2 meters) o any equipment that generates electrical
inter erence.
Installation Instructions for 1 Door Systems – July, 2019 Page 7
1 Door
Controller
#6 Mounting
Screw
#6 Mounting
Screw
1 Door
Controller
Mounting
Bracket

Controller Features 1 Door Systems
The following shows the controller's features and wiring components.
Controller Hardware dentification
1 DOOR CONTROLLER LAYOUT
Controller nputs
Controllers can monitor door position, request to exit and auxiliary (general purpose) inputs. All
inputs are assigned default states that can be modified as needed through the user interface.
The table below shows the default state for each of the inputs.
nput Type Default State
Door Position (status) Inputs Disabled
Request to Exit Inputs Normally Open, Momentary, Unsuper ised
Auxiliary Inputs Normally Open, Momentary, Unsuper ised
Tamper Normally Open, Momentary, Unsuper ised
Power Fault Normally Open, Momentary, Unsuper ised
nput Circuit Configurations
The table below shows the different input configurations. These types can be independently
configured for each input by the user.
Supervised Unsupervised
Normally Open Normally Open
Note: Use 1K Ohm Resistor
Normally Closed Normally Closed
Installation Instructions for 1 Door Systems – July, 2019 Page 8
POWER
HARNESS
CONNECTOR
READER
HARNESS
CONNECTOR
HEAT SINK
ETHERNET
*HARDWARE
RESET
*IP RESET
*FACTORY
DEFAULT
*SD CARD
*controller shown
with co er remo ed
USB – FOR
FACTORY USE
ONLY

Controller Wiring Harnesses
The controller is pro ided with two plug-in wiring harnesses for connecting field
wiring. The harnesses are color coded and marked with labels to indicate the
proper connection for field wiring.
The Minimum Cable Specifications or the wiring o inputs is
22 AWG Belden or equivalent with a maximum distance o 98.5
eet (30 meters).
NOTE: All wiring shall con orm with the National Electrical
Code, NPFA70 and local building codes.
nput Wiring
All inputs may be configured for normally open or normally closed contacts. Door position,
request to exit and auxiliary inputs may also be configured with for super ision to detect if wiring
to the contact is broken or cut. Wires must not be routed in parallel wit or in t e same
conduit wit any ig voltage AC wiring.
14 Pin Reader Harness
nput Power
PIN Color Description
1RED +12 VDC Power for In & Out Readers
3BLUE LED, In & Out Readers
5ORANGE Buzzer, In & Out Readers
7GREEN D0, In Reader
9WH TE D1, In Reader
11 GREEN D0, Out Reader
13 WH TE D1, In Reader
2BLACK Ground, In & Out Readers
Door nputs
14 PURPLE Door Position Input
12 BLACK Ground
10 YELLOW Request to Exit Input
System nputs
8GRAY AUX Input
6BROWN Tamper
4GRAY Power Fault
12 BLACK Ground
Installation Instructions for 1 Door Systems – July, 2019 Page 9

Request to Exit (REX) nput
A REX input acti ated the door output to unlock a door. A REX de ice can be a press to exit
button, motion detector or other de ice mounted on the secured side of an entrance. REX
features may be modified in De ice Settings for Doors and can be set to normally open (NO),
normally closed (NC) or monitored using either a series or parallel resistor. For applications
where a manual unlocking de ice is used, such as a exit bar, REX acti ating the door output can
be disabled.
Request to Exit Wiring
1. Disconnect power from the controller.
2. Determine if your REX de ice is normally open or
normally closed (refer to the instructions pro ided
by the REX manufacturer).
3. Connect the REX de ice as shown.
4. After power is applied to the controller, make sure
to configure the controller in De ice Settings for Doors and select the appropriate REX
input type.
5. After power is applied to the controller, erify the input is properly working.
Door Position nput
Monitors if the door is open or closed. The door switch (typically a magnetic reed switch, not
pro ided) will change state when the door is opened or closed. To use this feature, it must be
enabled in De ice Settings for Doors. It can be set to normally open (NO), normally closed (NC)
or monitored using either a series or parallel resistor.
Door Position Wiring
1. Disconnect power from the controller.
2. Determine if your door position switch is normally
open or normally closed (refer to the instructions
pro ided by the switch manufacturer).
3. Connect the door position switch as shown.
4. After power is applied to the controller, make sure to
configure the controller to use the door position
switch in De ice Settings for Doors and select the
appropriate door contact type.
5. After power is applied to the controller, erify the input is properly working.
Auxiliary nputs
Auxiliary inputs are used for general purposes and can be connected to de ices such as alarms,
detectors and de ices that ha e a switched output. These inputs can be set to normally open
(NO), normally closed (NC) or monitored using either a series or parallel resistor and these
features may be modified in De ice Settings for Aux Inputs.
Auxiliary inputs must be programmed to produce a defined action, such as acti ating an
auxiliary output, using E ent Actions.
Installation Instructions for 1 Door Systems – July, 2019 Page 10

Auxiliary nput Wiring
1. Disconnect power from the controller.
2. Determine if de ice you are connecting to the
Auxiliary input is normally open or normally
closed (refer to the instructions pro ided by the
de ice manufacturer).
3. Connect the de ice to the Auxiliary wires as shown.
4. After power is applied to the controller, make sure to configure the controller in De ice
Settings for Doors and select the appropriate Auxiliary input type.
5. After power is applied to the controller, erify the input is properly working.
Tamper
The tamper input may be used to monitor access to the access control system and must be
used for UL installations. This input can be set to normally open (NO) or normally closed (NC) in
De ice Settings for Controllers. Typically a tamper switch is mounted inside the enclosure
containing the access control system in such a way that when the enclosure is opened, the
switch is acti ated.
The access control system can be programmed using E ent Actions to perform a system
backup, acti ate an auxiliary output or send an email notification when a tamper input is
detected.
Tamper nput Wiring
1. Disconnect power from the controller.
2. Determine if de ice you are connecting to the
Tamper input is normally open or normally closed
(refer to the instructions pro ided by the de ice manufacturer).
3. Connect the de ice to the Tamper wires as shown.
4. After power is applied to the controller, make sure to configure the controller in De ice
Settings for Controllers and select the appropriate Tamper input type.
5. After power is applied to the controller, erify the input is properly working.
Power Fault
The power input may be used to monitor the power supply connected to the access control
system. This input can be set to normally open (NO) or normally closed (NC) in De ice Settings
for Controllers. Typically power supplies designed for access control will ha e a switched output
that is acti ated when main power is lost and changed to battery backup.
The access control system can be programmed using E ent Actions to perform a system
backup, acti ate an auxiliary output or send an email notification when a power input is
detected.
Installation Instructions for 1 Door Systems – July, 2019 Page 11

Power Fault nput Wiring
1. Disconnect power from the controller.
2. Determine if de ice you are connecting to the
Power Fault input is normally open or normally
closed (refer to the instructions pro ided by the
de ice manufacturer).
3. Connect the de ice to the Power Fault wires as shown.
4. After power is applied to the controller, make sure to configure the controller in De ice
Settings for Controllers and select the appropriate Power Fault input type.
5. After power is applied to the controller, erify the input is properly working.
Readers
The controller can be connected to Wiegand type readers or keypads. Each door on the
controller supports a primary (entrance) In Reader and a secondary (exit) Out Reader.
The maximum power a ailable through the controller for an indi idual reader is 300mA @
12VDC with a combined maxim for the controller of 600mA. Exceeding t e maximum power
for an individual reader or for t e controller may damage t e controller, void t e warranty
and will cause erratic operation. Refer to the manufacture's documentation to determine the
reader's power requirements. Wires must not be routed in parallel wit or in t e same
conduit wit any ig voltage AC wiring.
The Minimum Cable Specifications or readers is a Belden shielded, twisted,
6 conductor plus ground cable, 22 AWG.
For UL installations, t e maximum cable lengt is 98.5 feet (30 meters).
Note: Use UL294 listed readers or all installations such as HID ProxPoint Plus
or similar. All wiring shall con orm with the National Electrical Code, NPFA70
and local building codes.
Installation Instructions for 1 Door Systems – July, 2019 Page 12

Reader Wiring
1. Disconnect power from the controller.
2. Connect the color coded wires from the reader to the
appropriate wires on the reader 14 pin harness as
shown. Refer to manufacturer's instructions for exact
color codes for each connection.
3. Remo e excess shield from the reader cable to
pre ent interference with the controller's electronics or
other electrical circuits. Tape off any exposed shield
with electrical tape.
4. Reader shields must be grounded per the manufacturer's requirements.
5. Make sure to properly ground the reader shield.
6. After power is applied to the controller, erify the reader is properly working.
n & Out Reader Wiring
14 Pin
Reader
Harness
Color Description Typical N Reader
Wire Color
Typical Out Reader
Wire Color
12 Black Ground Black Black
13 White Out Reader, D1 X White
11 Green Out Reader, D0 X Green
9White In Reader, D1 White X
7Green In Reader, D0 Green X
5Orange Buzzer Control Blue Blue
3Blue LED Control Brown Brown
1Red 12 VDC Red Red
Controller Outputs & Power nput
The controller has door output and auxiliary output relays that may be acti ated in response to
reader acti ity, time schedules or e ent actions. The outputs are assigned default features that
can be configured in De ice Settings for Doors or Auxiliary Outputs. The table below shows the
default state for each type of output.
Output Default State Default Response
Door Output Not Energized, Single Pulse 3 second acti ation time in response to
alid access credentials
Auxiliary Output Not Energized, Single Pulse None. Must be configured in De ice
Settings or E ent Actions
Output Wiring Requirements
The wire used must be of the proper gauge for the load current and distance from the controller
to the load. Wires must not be routed in parallel wit or in t e same conduit wit any ig
voltage AC wiring and all wiring shall conform with the National Electrical Code, NPFA70 and
local building codes. Use a minimum size of UL listed 18 AWG to a maximum distance of 98.5
feet (30 meters).
Installation Instructions for 1 Door Systems – July, 2019 Page 13

10 Position Power Harness
nput Power
PIN Color Description
10 BLACK Ground
9RED +12 VDC @ 2A
Door Output
7GREEN Normally Closed Dry Relay Contact
5BLUE Common Relay Contact
3GRAY Normally Open Dry Relay Contact
Auxiliary Output
8GREEN Normally Closed Dry Relay Contact
6WH TE Common Relay Contact
4GRAY Normally Open Dry Relay Contact
2BLACK Ground
1BLACK Ground
Power 12 VDC & GND
The Power Input requires a dedicated Class 2, 12 VDC power supply. For UL installations, only
use a UL294 listed supply such as a Linear 12VDC/24W PIP that has an indicator light that is
illuminated when AC power is present with a rating of 12 VDC @ 2A.
NOTICE: A 12 VDC power supply must be used. Incorrect voltage
will damage the product and void the warranty.
CABLE SPECIFICATIONS: Use a minimum size o UL listed 18
AWG, 2 conductor at a maximum distance o 4 eet (1.2 meters).
NOTE: Power supplies must be plugged into a dedicated
receptacle that is not controlled by a switch.
Power Wiring
1. Connect the power supply +12V and -12V terminals to 10
pin power harness as shown.
2. Power should only be applied to the system when all
connections are secured and tested, and when instructed
to apply power.
NOTE: W en 12V power is applied to t e controller, a blinking LED indicator next to t e
14 pin reader arness will be visible.
Installation Instructions for 1 Door Systems – July, 2019 Page 14

Door outputs can be configured to operate in a fail safe or fail secure mode. Connect the door
locking de ice to the door output connector as shown below. Refer to the manufacturer's
specifications to determine the correct operating oltage, current and configuration. Use a power
supply dedicated for door lock use.
Fail Secure DC Door Strike
Without power, the door strike is locked.
Fail Safe DC Door Strike
Without power, the door strike is unlocked.
Fail Secure AC Door Strike
Without power, the door strike is locked.
Installation Instructions for 1 Door Systems – July, 2019 Page 15

Powering On and Connecting to a Network
Controllers must be located in a secure area and connected to a network that is protected by a
security system (firewall, etc.). Before connecting the controller to the network, obtain the
following information from you network administrator. Note: a Static IP address should be used
when the controller is con igured as a server controller. Client controllers may use DHCP.
✔IP address
✔Subnet Mask
✔Gateway
✔DNS 1 and DNS 2
Preparing for the Network
In most cases, the controllers IP address will ha e to be changed to allow the controller to be
recognized by the local network. The controller's IP address is changed as follows.
1. Connect a programming computer directly to the Ethernet port of the controller. A
standard CAT-5 cable is used for direct connection. A crosso er cable is not required.
2. Assign a static IP address to the computer of 192.168.0.10. For instructions on how to
change the static IP address of a Windows computer isit:
https://support.microsoft.com/en-us/help/15089/windows-change-tcp-ip-settings
3. The factory default IP address of the controller is 192.168.0.250. Open a web browser,
such as Google Chrome, and enter the default IP address into the address bar.
TIP: As an alternative to directly connecting a cable, the provided IP
Installer utility can be used to change the controller's IP address. See the
section below on how to use the utility.
4. The controller's login page is displayed as shown. To login enter the
default User ID: admin and default PW: admin
5. Controllers can be licensed as a ser er or a client.
After first time login, the license page is displayed. To
get a license key, first click on the Edit button. On the
next page, click on A, the Get License Key for a
SERVER or click on B, the Get Client Key for a
CL ENT. Click OK to confirm and the license key will
be auto populated. Finish by clicking C, Apply
License Key and the controller will restart.
NOTE: The controller needs to access the Internet to obtain a license key.
6. When the controller is licensed for a ser er, after logging in, the system configuration
Wizard is started. The Wizard is a guide that can be used to collect the basic information
required to set up a system. The network settings can be configured in the Wizard or by
browsing to the Network Configuration page as shown.
Installation Instructions for 1 Door Systems – July, 2019 Page 16

Wizard Starting Page
7. The network configurations may be accessed through the Sitemap by first clicking the
icon at the bottom of the page, then clicking IP Address under Network Settings.
Accessing the Site Map
8. After entering the network information, click Sa e & Reboot and the controller will reboot.
Typically rebooting will take less than 2 minutes.
Network Settings Page
8. After disconnecting the programming computer, the controller is ready for the local
network.
NOTE: System data may be lost i the controller is powered down
without per orming Save & Reboot.
Connecting to the Local Network
Plug the Ethernet cable into the port on the controller and connect to the local area network as
shown below. If the network connection is functioning properly the LAN LED's on the controller
will blink. Computers connected to the local network will be able to access the system using the
IP address of the controller.
The Minimum Cable Specifications network connection is CAT 5 or better with an RJ-45
connector, wired straight through to a network switch or router.
Note: For UL installations, the maximum Ethernet cable length is 98.5 eet (30 meters).
Installation Instructions for 1 Door Systems – July, 2019 Page 17

NOTE: LAN connection is only required or monitoring, reporting and con iguration.
Once the system is con igured, it will operate without a LAN connection.
Adding Clients to Systems
Some systems ha e the ability to add additional controllers to increase the number of doors,
inputs or outputs or control ele ators. Clients are configured through the system's ser er, but
must first be linked to the ser er.
Setting the Client's Network
1. Connect a programming PC directly to the controller as described in the section
Preparing for the Network.
2. Login using the default ID: admin and default PW: admin
3. After login, the client's network page is displayed. Click Edit.
4. Change the IP address of the client controller. It is recommended to set this to DHCP.
5. Enter the IP address of the ser er controller and the ser er's port number (the default
port number is 20000).
6. Enter the password and click Sa e.
Installation Instructions for 1 Door Systems – July, 2019 Page 18

Linking the Client to the Server
1. Login to the system's ser er.
2. After logging in, browse to the Site Management and select Client Management.
3. The client will appear in the client management list. Click on the button to connect
the client to the ser er.
Client Management
P nstaller
IP Installer is a Microsoft Windows® PC utility that is on the USB thumb dri e shipped with all
systems. This utility can be used to locate a controller on the local area network. It also pro ides
a method of changing the IP address of a ser er or client controller and is an alternati e to
directly connecting clients. To use IP Installer, follow the steps below.
1. Locate IP Installer on the USB thumb dri e and install it on a Windows PC that is
connected to the local network that will be used by the ser er and client controllers.
2. Connect all of the controllers to
local network.
3. Run IP Installer. If you PC has
multiple network adapters,
select the adapter in the
Network Card list box that is
connected to the local network
used by the controllers, and
click Scan to locate the
controllers. When controllers
are located, they will be listed
in IP Installer.
4. In this example, a ser er controller is located at 192.168.0.200 and client controller is
located at 192.168.0.250. The client's IP address can be changed and the client can be
assigned to a ser er by first clicking on the client in the list,
then click the Set Network button.
5. In the IP Setting popup, change the client's IP to static IP
address or to a DHCP. Note that ser ers must be set to static
IP address.
6. In the IP Setting popup, change the client's Ser er Info. In this
example, the Ser er IP is 192.168.0.200 and the Ser er Port
is 20000.
7. Enter the IP Installer password 1234 and click OK. This will
update the client's IP address settings and assign it to a
ser er. When the network changes are complete, the client
will appear in the list with the new settings.
Installation Instructions for 1 Door Systems – July, 2019 Page 19

System Configuration and Programming
The controller is programmed and managed using a web browser on any computer connected
to the local area network. The controller's basic settings can be programmed using the Wizard
tool. The Wizard tool helps ensure that required settings are configured for normal operation.
For specific programming instructions, refer to the Users Programming Guide,
Part Number 100104-SP.
Installation Instructions for 1 Door Systems – July, 2019 Page 20
Other manuals for A1
1
Table of contents
Popular Control System manuals by other brands

Taramps Electronics
Taramps Electronics SMART 3 instruction manual

Lamtec
Lamtec FMS Series Quick Reference for End User

Siemens
Siemens SINUMERIK 828D Turning Connection instructions

Mitsubishi Electric
Mitsubishi Electric AE-200A Instruction book

Siemens
Siemens SIMATIC PCS 7 Operation and maintenance

Safe Barriers
Safe Barriers Defender 100LDS installation manual

EUCHNER
EUCHNER MSM-1-R-CKS2-FLX Series operating instructions

GCS
GCS CYSCAN Installation and maintenance guide

Elstat
Elstat EMS-55 Technical instruction manual

Halytech
Halytech microSpider meterwatch installation guide

Airzone
Airzone UNO PACK installation manual

Honeywell
Honeywell Excel 500 installation instructions