manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Cooper Notification
  6. •
  7. Fire Alarm
  8. •
  9. Cooper Notification HS4 Series User manual

Cooper Notification HS4 Series User manual

Copyright 2009 Cooper Wheelock, Inc. All rights reserved. P84469 L
Sheet 1 of 4
273 Branchport Avenue Thank you for using our products.
Long Branch, NJ 07740 INSTALLATION INSTRUCTIONS
(800) 631-2148 SERIES HS4 MULTI-HIGH-CANDELA FOUR WIRE APPLIANCES
www.cooperwheelock.com (WALL AND CEILING MOUNT)
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
Series HS4-24MCWH and HS4-MCCH Multi-High-Candela Horn Strobes provide two selectable candela settings (135/185 and 115/177 respectively). These models allow
for independent operation of the strobe circuit and the horn circuit. It is the ideal choice for retrofit applications as well as new installations. These models are UL Listed
under Standard 1971 for Signaling Appliances for the Hearing Impaired and UL Standard 464 for Audible Signal Appliances. HS4 models are listed for indoor use only and
can be mounted to double-gang, 4” backbox, 100mm European backbox or SHBB surface backbox (See wiring and mounting information). The HS4-24MCWH appliance is
listed for wall mounting only. HS4-24MCCH appliance is listed for ceiling mounting only. The HS4-Multi-High Candela appliances use a xenon flashtube with solid state
circuitry enclosed in a polycarbonate lens to provide maximum visibility and reliability for effective visible signaling.
The horn portion of the HS4 appliance can be field set to provide either a continuous horn when connected directly to the fire alarm control panel (FACP), or a synchronized
code 3 horn when used in conjunction with the Sync Module (SM), Dual Sync Module (DSM) or Wheelock power supplies. The horn can be field set to provide either high
(HI) dBA, medium (MED) dBA or low (LO) dBA sound output.
NOTE: The Code 3 temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 off and repeat) is specified by ANSI and NFPA 72
for standard emergency evacuation signaling. The Code 3 Horn should be used only for fire evacuation signaling and not for any other purpose.
These models are designed for use with either filtered DC or unfiltered full-wave-rectified (FWR) input voltage. All inputs are polarized for compatibility with standard reverse
polarity supervision of circuit wiring by an FACP.
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING
INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, CANDELA SETTING, INSTALLATION AND/OR OPERATION OF THESE
PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS: Table 1: UL Listed Models and Ratings
Model Regulate
Voltage
(VDC/VRMS)
Voltage Range
Limit Per UL 1971
(VDC/VRMS)
Strobe
Candela
(cd)
HS4-24MCWH 24 16.0-33.0 135/185
HS4-24MCCH 24 16.0-33.0 115/177
Table 2: dBA Sound Output for 24VDC Models
Description
Volume Reverberant Per UL 464
16VDC 24VDC 33VDC
Low 80 83 86
Continuous Horn Medium 85 88 91
High 88 91 93
Low 75 79 82
Code 3 Horn Medium 80 84 86
High 84 87 89
NOTES:
1. The strobe will produce 1 flash per second over the "Regulated Voltage" range.
2. This horn/strobe model meets the required light distribution patterns defined in UL1971.
3. These models are Listed for indoor use with a temperature range of +32°F to +120°F (0°C to +49°C) and maximum humidity of 93% ±2% RH. The effect of shipping
and storage temperatures shall not adversely affect the performance of the appliance when it is stored in the original cartons and not subjected to misuse or abuse.
WARNING: CANDELA SETTING WILL DETERMINE THE CURRENT DRAW OF THE PRODUCT.
Table 3: Current Ratings (Horn Only)
Maximum RMS Current (Amps)
UL Voltage Lo Med Hi
DC 16-33VDC 0.027 0.068 0.110
FWR 16-33VRMS 0.041 0.050 0.094
Table 3A: Current Ratings (Strobe Only)
Maximum RMS Current (Amps)
UL Voltage 115cd 135cd 177cd 185cd
DC 16-33VDC 0.300 0.300 0.420 0.420
FWR 16-33VRMS 0.455 0.455 0.645 0.645
When calculating the total current: Use Tables 3 & 3A to determine the highest value of “RMS Current” for an individual HS4 then multiply the value by the total number of
HS4 Appliances. Be sure to add the currents for any other appliances powered by the same source and to include any required safety factors.
NOTE: The maximum number of strobes on a single notification appliance circuit shall not exceed 50.
CAUTION: These notification appliances are UL Listed as “Regulated”. They are intended to be used with FACPs whose notification circuits are UL Listed as
“Regulated.” These appliances shall not be used on UL Listed “Special Application” notification circuits unless the appliances are identified to be compatible in the installation
instructions of the FACP or unless the FACP is identified to be compatible in this instruction manual.
WARNING: FOR UL APPLICATIONS, THESE APPLIANCES WERE TESTED TO THE REGULATED VOLTAGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS
USING FILTERED DC OR UNFILTERED FULL-WAVE-RECTIFIED VOLTAGE. DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE.
P84469 L
Sheet 2 of 4
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE VOLTAGE DROP FROM
THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPPLIED VOLTAGE TO THE STROBES. THE MAXIMUM WIRE IMPEDANCE BETWEEN STROBES
SHALL NOT EXCEED 35 OHMS.
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND
SECONDARY POWER SOURCES, APPLIANCE CIRCUITS, SM, DSM SYNC MODULES AND WHEELOCK POWER SUPPLIES DOES NOT EXCEED THE POWER
SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING
POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY,
WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
CAUTION: The strobe is not designed to be used on coded systems in which the applied voltage is cycled on and off.
NOTE: The horn circuit is compatible with coded systems only if the unit is wired for independent horn and strobe operation per figure 4.
SOUND OUTPUT (SPL) AND CANDELA SETTINGS:
Figure 1:Showing Location of Candela Selector and Jumper Plugs
R
+ STR -
J3
+ AUD -
TB1
3
J2 C
O
E
D
J1
H
L
M
B
P83511 ( )
AH C1 R5
TOP
CANDELASELECTOR
CANDELA
POINTER
3
J2 C
O
E
D
J1
H
L
M
135 185
MCWH reflector shown.
MCWH: Factory setting is on 185 Candela, Medium dB and Code 3. MCCH: Factory setting is on 177 Candela, Medium dB and Code 3.
WARNING: THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE INSTALLATION. WHEN CHANGING
THE SETTING OF THE CANDELA SELECT SWITCH, MAKE CERTAIN THAT IT “CLICKS” IN PLACE. AFTER CHANGING THE CANDELA SETTING, THE APPLIANCE
MUST BE RETESTED TO VERIFY PROPER OPERATION. IMPROPER SETTING OF THE CANDELA SELECT SWITCH, MAY RESULT IN OPERATION AT THE
WRONG CANDELA, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
WARNING: THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE INSTALLATION. WHEN CHANGING
THE SETTING OF THE CANDELA SELECT SWITCH, MAKE CERTAIN THAT IT “CLICKS” IN PLACE. AFTER CHANGING THE CANDELA SETTING, THE APPLIANCE
MUST BE RETESTED TO VERIFY PROPER OPERATION. IMPROPER SETTING OF THE CANDELA SELECT SWITCH MAY RESULT IN OPERATION AT THE WRONG
CANDELA, WHICH COULD RESULT IN A CURRENT DRAW EXCEEDING THE POWER SUPPLY’S CAPACITY.
CAUTION: If these appliances are operated within 15 inches of a person's ear, they can produce a sound pressure level that exceeds the maximum 120dBA permitted
by ADA and OSHA rules. Exposure to such sound levels can result in damage to a person's hearing.
WARNING: THE HS4 APPLIANCES MUST BE FIELD SET TO THE DESIRED TONE AND dBA SOUND OUTPUT LEVEL BEFORE THEY ARE INSTALLED. THIS IS
DONE BY PROPERLY INSERTING JUMPER PLUGS IN ACCORDANCE WITH THESE INSTRUCTIONS. INCORRECT SETTINGS WILL RESULT IN IMPROPER
PERFORMANCE, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
Figure 2:Jumper Plug Settings for High, Medium, Low dB,
Code 3 Horn and Continuous Horn Setting. •Use needle nose pliers to pull and properly insert the jumper plug.
•No jumper plug is needed for continuous horn setting. However, it is
recommended that the jumper plug be retained in the unit for future use
(if needed) as shown in Figure 2.
•The HS4 must be set for Code 3 horn when used with the sync module.
Refer to instruction sheets for SM (P83123), DSM (P83177) or
Wheelock power supplies for additional information. If the HS4 audible
is connected to a coded system, the continuous horn setting must be
used
J1
HIGH LOW
HC
O
D
E
3 3
E
D
O
C
SETTING
HORN
SETTING
HORN
J1
J2 J2 J2
M
L
H
M
L
H
M
L
MEDIUM
SETTING
HORN CODE3
SETTING
HORN CONTINUOUS
SETTING
* HORN
WIRING AND MOUNTING INFORMATION:
Figure 3: Audible signal and strobe operate independently. Figure 3A: Audible and strobe operate in unison. Shunt wires are supplied.
+ STR -
+ AUD -
TB1
+
FROM FACP OR
PRECEDINGAPPLIANCE
TONEXTAPPLIANCE
OR EOLR.
FROMFIREALARM
CONTROLPANEL(FACP),
PRECEDINGAPPLIANCE
OR SYNC MODULE
TONEXTAPPLIANCE
OR END OF LINE
RESISTOR (EOLR).
-
-
+
+
-
-
+
+ STR - + AUD -
TB1
+
TONEXTAPPLIANCE
OR EOLR
FROMFACP,
PRECEDINGAPPLIANCE
OR SYNC MODULE
-
REDSHUNTWIRE BLACK SHUNT WIRE
-
+
Figure 4:
•HS4 appliances have in-out wiring terminals that accepts two #12 to #18 American Wire Gauge (AWG) wires at each screw terminal. Strip
leads 3/8” inches for connection to screw terminals.
•Break all in-out wire runs on supervised circuit supervision as shown in Figure 4. The polarity shown in the wiring diagrams is for the
operation of the appliances. The polarity is reversed by the FACP during supervision.
P84469 L
Sheet 3 of 4
CAUTION: The following figures (A-D) show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option. If these limits
are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product. Check that the installed
product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed multiconductor cable or 3/4" conduit fittings are used.
Figure A
FLUSH (4" BOX)
#8-32 SCREWS
4" SQ. X 2-1/8"
DEEPBACKBOX
SCREWCOVERS
8 488
AWG#18 AWG#16 AWG#14 AWG#12
MAXIMUMNUMBEROF CONDUCTORS
Figure B
8 888
AWG #18 AWG#16 AWG#14 AWG#12
MAXIMUM NUMBER OF CONDUCTORS
#6-32 SCREWS
SCREWCOVERS
FLUSH (2-GANG BOX)
2-GANGx 3-1/2"
DEEPBACKBOX
Although the limits shown for each mounting option comply with the
National Electrical Code (NEC), Cooper Wheelock recommends use of
the largest backbox option shown and the use of approved stranded
field wires, whenever possible, to provide additional wiring room for easy
installation and minimum stress on the product from wiring.
MOUNTING PROCEDURES:
1. This HS4 model can be flush mounted to a 100mm backbox (Figure
A) or double-gang backbox (Figure B). It can also be surface
mounted to a indoor/outdoor backbox (Figures C & D). Mounting
hardware for each mounting option is supplied.
2. Conduit entrances to the backbox should be selected to provide
sufficient wiring clearance for the installed product. Do not pass
additional wires (used for other than the signaling appliance)
through the backbox. Such additional wires could result in
insufficient wiring space for the signaling appliance.
3. When terminating field wires, do not use more lead length than
required. Excess lead length could result in insufficient wiring space
for the appliance.
4. Use care and proper techniques to position the field wires in the
backbox so that they use minimum space and produce minimum
stress on the product. This is especially important for stiff, heavy
gauge wires and wires with thick insulation or sheathing.
5. Connect field wires to the HS4 terminal block (polarity must be
observed). Bend the field wires up 90°at the connection to the
terminal block.
6. Carefully push the field wires into the backbox by hand. Press the
HS4 to the backbox, verifying that it is seated and aligned correctly.
7. Fasten the HS4 to the backbox using the supplied screws.
Figure C
8 888
AWG#18 AWG#16 AWG#14 AWG#12
MAXIMUMNUMBEROF CONDUCTORS
WOOD SCREWS
#8-18SCREWS
SCREWCOVERS
SURFACEMOUNTING
BACKBOX
(IOB)
Figure D
8 888
AWG#18 AWG#16 AWG#14 AWG#12
MAXIMUM NUMBER OF CONDUCTORS
#8-18 SCREWS
SCREWCOVERS
CONCEALED CONDUIT MOUNTING
BACKBOX
(IOB)
EXISTING
BOXIN WALL
WARNING: THE HS4 APPLIANCE IS A “FIRE ALARM DEVICE – DO NOT PAINT.”
WARNING: WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING PARTITIONS OR OTHER VIEWING OBSTRUCTIONS,
SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT CAN BE SEEN BY ALL INTENDED
VIEWERS, WITH THE INTENSITY, NUMBER, AND TYPE OF STROBES BEING SUFFICIENT TO MAKE SURE THAT THE INTENDED VIEWER IS ALERTED BY
PROPER ILLUMINATION, REGARDLESS OF THE VIEWER'S ORIENTATION. FAILURE TO DO SO COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY
OR DEATH TO YOU AND/OR OTHERS.
The 135, 177 and 185cd settings are Listed for use in sleeping or non-sleeping areas when installed in accordance with appropriate NFPA Standards and the Authority
Having Jurisdiction.
WARNING: IF 135/185 CANDELA STROBES ARE INSTALLED IN SLEEPING AREAS, THEY SHOULD BE WALL MOUNTED AT LEAST 24" BELOW THE CEILING
AS FOLLOWS: (1) THE ON-AXIS (CENTER OF LENS) LIGHT OUTPUT SHOULD BE DIRECTED AT THE EYELIDS OF THE SLEEPING PERSON, E.G. PILLOW END
OF BED, BED HEAD; (2) NO PART OF THE BED SHALL BE MORE THAN SIXTEEN FEET FROM THE STROBE NOTIFICATION APPLIANCE. INSTALLERS MUST
ADVISE OWNERS AND OPERATORS OF BUILDINGS WITH SLEEPING OCCUPANTS, E.G. HOTELS AND MOTELS, TO WARN GUESTS, RESIDENTS AND
EMPLOYEES TO NOT MOVE THE BED LOCATION TO A POSITION VIOLATING POINTS (1) AND (2) ABOVE OR SERIOUS INJURY AND/OR LOSS OF LIFE MAY
OCCUR DURING A FIRE EMERGENCY.
WARNING: A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW, UNDER CERTAIN
CIRCUMSTANCES, MIGHT INDUCE A PHOTO-SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY. STROBE REFLECTIONS IN A GLASS OR MIRRORED
SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE. TO MINIMIZE THIS POSSIBLE HAZARD, COOPER WHEELOCK STRONGLY RECOMMENDS THAT THE
STROBES INSTALLED SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW WHICH EXCEEDS FIVE Hz AT THE OPERATING VOLTAGE
OF THE STROBES. COOPER WHEELOCK ALSO STRONGLY RECOMMENDS THAT THE INTENSITY AND COMPOSITE FLASH RATE OF INSTALLED STROBES
COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS, STANDARDS, REGULATIONS, CODES AND GUIDELINES.
NOTE: NFPA 72/ANSI 117.1 conform to ADAAG Equivalent Facilitation Guidelines in using fewer, higher intensity strobes within the same protected area.
CAUTION: Check the installation instructions of the manufacturers of other equipment used in the system for any guidelines or restrictions on wiring and/or locating
Notification Appliance Circuits (NAC) and notification appliances. Some system communication circuits and/or audio circuits, for example, may require special precautions to
assure electrical noise immunity (e.g. audio crosstalk).
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital appliance, pursuant to Part 15 of the FCC Rules. These limits are designed
to provide reasonable protection against harmful interference in residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more of the following measures: 1) Reorient or relocate the receiving antenna, 2) Increase the
separation between the equipment and receiver, 3) Connect the equipment into an outlet on a circuit different from that to which the receiver is connected, and 4) Consult
the dealer or an experienced radio/TV technician for help.
P84469 L
Sheet 4 of 4
The Series HS4 products and these instructions are copyrighted by Cooper Wheelock and the Series HS4 products contain proprietary, confidential and trade secrets of
Cooper Wheelock. No part of the Series HS4 products and these instructions may be photocopied, printed or reproduced in any form or modified, adapted, changed or
enhanced, or converted to another programming language, or used to create updated, related or derivative works, without the prior written consent of Cooper Wheelock. No
part of the Series HS4 products shall be decomposed, disassembled or reverse engineered.
ANY MATERIAL EXTRAPOLATED FROM THIS DOCUMENT OR FROM COOPER WHEELOCK MANUALS OR OTHER DOCUMENTS DESCRIBING THE PRODUCT
FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS, OR FOR ANY OTHER USE, INCLUDING DESCRIPTION OF THE PRODUCT'S APPLICATION, OPERATION,
INSTALLATION AND TESTING IS USED AT THE SOLE RISK OF THE USER AND COOPER WHEELOCK WILL NOT HAVE ANY LIABILITY FOR SUCH USE.
LIMITED WARRANTY
Cooper Wheelock, Inc. dba Cooper Notification and Cooper Notification, Inc. (each, a “Seller”) products must be used within their published specifications and must be
PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with these instructions at the time of installation and at least twice a
year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing
must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriter’s Laboratories
(UL), National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and
fire standards, guidelines, regulations laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having
jurisdiction (AHJ). Seller products when properly specified, applied, installed, operated, maintained and operationally tested as provided above are warranted against
mechanical and electrical defects for a period of (a) three (3) years from date of manufacture with respect to MEDC and Seller Industrial Signals and Seller Fire and Security
Notification Appliances and Devices, or (b) one (1) year from date of manufacture with respect to Waves and SafePath Voice Evacuation and Mass Notification Systems
(date of manufacture is determined by date code.) Correction of defects by repair or replacement shall be at Seller’s sole discretion and shall constitute fulfillment of all
obligations under this warranty. THE FOREGOING LIMITED WARRANTY SHALL IMMEDIATELY TERMINATE IN THE EVENT ANY PART NOT FURNISHED BY SELLER
IS INSTALLED IN THE PRODUCT. THE FOREGOING LIMITED WARRANTY SPECIFICALLY EXCLUDES ANY SOFTWARE REQUIRED FOR THE OPERATION OF OR
INCLUDED IN A PRODUCT. SELLER MAKES NO REPRESENTATION OR WARRANTY OF ANY OTHER KIND, EXPRESS, IMPLIED OR STATUTORY WHETHER AS
TO MECHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE OR ANY OTHER MATTER.
USERS ARE SOLELY RESPONSIBLE FOR DETERMINING WHETHER A PRODUCT IS SUITABLE FOR THE USER’S PURPOSES, OR WHETHER IT WILL ACHIEVE
THE USER’S INTENDED RESULTS. THERE IS NO WARRANTY AGAINST DAMAGE RESULTING FROM MISAPPLIACATION, IMPROPER SPECIFICATION, ABUSE,
ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND SELLER’S CONTROL.
SELLER DOES NOT WARRANT THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR-FREE OR THAT THE SOFTWARE WILL MEET
ANY OTHER STANDARD OF PERFORMANCE, OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER’S REQUIREMENTS.
SELLER SHALL NOT BE LIABLE FOR ANY DELAYS, BREAKDOWNS, INTERRUPTIONS, LOSS, DESTRUCTION, ALTERATION, OR OTHER PROBLEMS IN THE USE
OF A PRODUCT ARISING OUT OF OR CAUSED BY THE SOFTWARE.
THE LIABILITY OF SELLER ARISING OUT OF THE SUPPLYING OF A PRODUCT, OR ITS USE, WHETHER ON WARRANTIES, NEGLIGENCE, OR OTHERWISE,
SHALL NOT IN ANY CASE EXCEED THE COST OF CORRECTING DEFECTS AS STATED IN THE LIMITED WARRANTY AND UPON EXPIRATION OF THE WARRANTY
PERIOD ALL SUCH LIABILITY SHALL TERMINATE. SELLER IS NOT LIABLE FOR LABOR COSTS INCURRED IN REMOVAL, REINSTALLATION OR REPAIR OF A
PRODUCT BY ANYONE OTHER THAN SELLER OR FOR DAMAGE OF ANY TYPE WHATSOEVER, INCLUDING BUT NOT LIMITED TO, LOSS OF PROFIT OR
INCIDENTAL, INDIRECT, CONSEQUENTIAL, SPECIAL, PUNTIVE OR EXEMPLARY DAMAGES. THE FOREGOING SHALL CONSTITUTE THE SOLE REMEDY OF THE
PURCHASER AND THE EXCLUSIVE LIABILITY OF SELLER.
IN NO CASE WILL SELLER’S LIABILITY EXCEED THE PURCHASE PRICE PAID FOR A PRODUCT.
LIMITATION OF LIABILITY
SELLER’S LIABILITY ON ANY CLAIM OF ANY KIND, INCLUDING NEGLIGENCE AND BREACH OF WARRNTY, FOR ANY LOSS OR DAMAGE RESULTING FROM,
ARISING OUT OF, OR CONNECTED WITH THIS CONTRACT, OR FROM THE MANUFACTURE, SALE, DELIVERY, RESALE, REPAIR OR USE OF ANY PRODUCT
COVERED BY THIS ORDER SHALL BE LIMITED TO THE PRICE APPLICABLE TO THE PRODUCT OR PART THEREOF WHICH GIVES RISE TO THE CLAIM.
SELLER’S LIABILITY ON ANY CLAIM OF ANY KIND SHALL CEASE IMMEDIATELY UPON THE INSTALLATION IN THE PRODUCT OF ANY PART NOT FURNISHED BY
SELLER. IN NO EVENT SHALL SELLER BE LIABLE FOR ANY CLAIM OF ANY KIND UNLESS IT IS PROVEN THAT ITS PRODUCT WAS THE DIRECT CAUSE OF
SUCH CLAIM. FURTHER, IN NO EVENT, INCLUDING IN THE CASE OF A CLAIM OF NEGLIGENCE, SHALL SELLER BE LIABLE FOR INCIDENTAL, INDIRECT,
CONSEQUENTIAL, SPECIAL, PUNITIVE OR EXEMPLARY DAMAGES. SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR
CONSEQUENTIAL DAMAGES, SO THE PRECEDING LIMITATION MAY NOT APPLY TO ALL PURCHASERS.
10/09

This manual suits for next models

2

Other Cooper Notification Fire Alarm manuals

Cooper Notification E70-24MCW Series User manual

Cooper Notification

Cooper Notification E70-24MCW Series User manual

Cooper Notification ET70-24MCCH Series User manual

Cooper Notification

Cooper Notification ET70-24MCCH Series User manual

Cooper Notification Wheelock MPS Series User manual

Cooper Notification

Cooper Notification Wheelock MPS Series User manual

Cooper Notification RSS-24MCC User manual

Cooper Notification

Cooper Notification RSS-24MCC User manual

Cooper Notification ST-C User manual

Cooper Notification

Cooper Notification ST-C User manual

Cooper Notification Eluxa ELCH User manual

Cooper Notification

Cooper Notification Eluxa ELCH User manual

Cooper Notification ET90-24MCWH Series User manual

Cooper Notification

Cooper Notification ET90-24MCWH Series User manual

Cooper Notification E60H-24MCCH User manual

Cooper Notification

Cooper Notification E60H-24MCCH User manual

Cooper Notification RSS-241575W User manual

Cooper Notification

Cooper Notification RSS-241575W User manual

Cooper Notification E70-24MCC Series User manual

Cooper Notification

Cooper Notification E70-24MCC Series User manual

Cooper Notification Wheelock Eluxa ELSTC-B User manual

Cooper Notification

Cooper Notification Wheelock Eluxa ELSTC-B User manual

Cooper Notification RSSR-2415C User manual

Cooper Notification

Cooper Notification RSSR-2415C User manual

Popular Fire Alarm manuals by other brands

Honeywell HW-TG7LAF02 Installation and operating guide

Honeywell

Honeywell HW-TG7LAF02 Installation and operating guide

Simplex SafeLINC 4100 Operator's manual

Simplex

Simplex SafeLINC 4100 Operator's manual

United Technologies Kidde FX-270 Installation sheet

United Technologies

United Technologies Kidde FX-270 Installation sheet

FireClass FC421CP-I Fixing instructions

FireClass

FireClass FC421CP-I Fixing instructions

Jade Bird JBE-2100 manual

Jade Bird

Jade Bird JBE-2100 manual

Eaton BiWire Flexi user manual

Eaton

Eaton BiWire Flexi user manual

Fike 68-140 Installation and maintenance instructions

Fike

Fike 68-140 Installation and maintenance instructions

Zeta Alarm Systems Simplicity Plus 64 installation manual

Zeta Alarm Systems

Zeta Alarm Systems Simplicity Plus 64 installation manual

KILLARK XAL-53 Installation, operation and maintanance

KILLARK

KILLARK XAL-53 Installation, operation and maintanance

Global Fire Equipment ORION EX MINI-REP installation manual

Global Fire Equipment

Global Fire Equipment ORION EX MINI-REP installation manual

olympia electronics nsc BS-1632 manual

olympia electronics

olympia electronics nsc BS-1632 manual

Teknim TFD-1260 Installation & operating guide

Teknim

Teknim TFD-1260 Installation & operating guide

EMS FIRECELL Setup guide

EMS

EMS FIRECELL Setup guide

Gent Xenex 13270-02LB Operating instructions and Log Book

Gent

Gent Xenex 13270-02LB Operating instructions and Log Book

Tyco TIS-BG12LX manual

Tyco

Tyco TIS-BG12LX manual

Teknim TFB-1166 Installation & user manual

Teknim

Teknim TFB-1166 Installation & user manual

Honeywell NOTIFIER ONYX FirstVision Installation and operation manual

Honeywell

Honeywell NOTIFIER ONYX FirstVision Installation and operation manual

Honeywell NOTIFIER NFX-SMT3 Installation and maintenance instructions

Honeywell

Honeywell NOTIFIER NFX-SMT3 Installation and maintenance instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.