LEADING THE WAY IN FIRE PROTECTION
VARIOSPEED®5 (SMART SYSTEM) CONTROL PANEL
RESET PROCESS (IF IN DOUBT, ASK)
If the curtain has test / auto key on the front:
1. Ensure the descent path of the curtain is clear
i.e. there are no obstructions. The curtain will fully deploy
during this process.
2. Turn the key to the ‘test’ position and the curtain should
begin to deploy. Wait for the curtain to have deployed to its
fire operational position.
3. Turn the key to the ‘Auto’ position.
4. Firmly press the ‘Reset’ button.
Note: The curtain should begin to retract at this stage.
MK5 CONTROL PANEL
RESET PROCESS (IF IN DOUBT, ASK)
1. Ensure the descent path of the curtain is clear
i.e. there are no obstructions. The curtain
will fully deploy during this process.
2. Remove the incoming ‘ALARM’ cable and
the curtain should begin to deploy*. Wait for the
curtain to have deployed to its fire operational position.
3. Remove the IEC power lead from the
under-side of control panel. This looks like
a ‘kettle lead’.
4. Locate the ‘battery fuse’ on the underside of the bottom right hand side of the control panel. This is
located in the centre of 3 circular, black fuses.
5. The fuse can be removed by applying pressure and twisting anti-clockwise. The fuse will then drop
down slightly.
6. Wait 10 seconds and confirm that the MK5 display screen has lost power and has lost its display.
7. Re-instate the incoming power by re-connecting the IEC power lead (‘kettle lead’).
8. Re-connect the battery fuse by applying pressure and twisting clockwise. Confirm the battery fuse
remains in position and does not drop down.
9. The MK5 will initialise and after 10 seconds should state ‘in MANUAL mode, AUTO press OK’.
10. Press OK. Note: The curtain should begin to retract at this stage.
*If there is no cable connected into ‘Alarm’, remove the cable connected into ‘Detector 1’.