Cromtech TG6000DVE User manual

CROMTECH DIESEL GENERATOR
OPERATION MANUAL
DIESEL 6000W GENERATOR
Cromtech Diesel 6000W Generator Manual April 2020.indd 1Cromtech Diesel 6000W Generator Manual April 2020.indd 1 21/4/20 7:25 pm21/4/20 7:25 pm

Pg. 2
Thank you for purchasing a Cromtech Diesel Generator.
This manual provides understanding of the operaon
and maintenance of your generator. Please read this
manual carefully before operang.
For any quesons regarding operaon or maintenance,
please consult your local service agent. Find your local
service agent at www.crommelins.com.au.
IMPORTANT ICONS
Important informaon is disnguished by the nocaons
below. The Safety Alarm Symbol ( !) alerts you to
potenal hazards. Please obey all safety informaon in the
symbol to avoid any possible injury or even death.
!DANGER: Indicates a hazardous situaon which, if not
strictly complied with, will result in substanal property
damage, serious injury or DEATH.
!WARNING: Indicates a hazardous situaon which, if
not strictly complied with, may result in property damage.
!CAUTION: Indicates a hazardous situaon which, if
not strictly complied with, could result in property damage
or injury.
!NOTE: Indicates important informaon to simplify
operaon and understanding.
!WARNING: PLEASE READ AND UNDERSTAND THIS
MANUAL BEFORE OPERATING THE GENERATOR.
!NOTE: We connually seek advancements in product
design and quality. Therefore, there may be minor
discrepancies in actual machine and the printed manual.
Cromtech Diesel 6000W Generator Manual April 2020.indd 2Cromtech Diesel 6000W Generator Manual April 2020.indd 2 21/4/20 7:25 pm21/4/20 7:25 pm

INDEX
Warranty ....................................................................... 4
Safety Warnings ............................................................ 5
TG6000DVE Features ..................................................... 8
Control panel ............................................................ 8
Generator Specicaons .............................................. 9
Operang Checklist ....................................................... 10
Operang area .......................................................... 10
Operang condion .................................................. 10
Check engine oil ........................................................ 11
Check fuel levels ........................................................ 12
Electrical devices ....................................................... 12
Check air cleaner element ........................................ 13
Check generator ........................................................ 13
Connect to electrical devices .................................... 13
Low oil warning system/stop device ............................ 14
Break-in Operaon ........................................................ 14
Maximum capacity ....................................................... 14
Waage reference guide .............................................. 15
Pre-start Instrucons .................................................... 16
Starng the Generator .................................................. 16
Electric start ............................................................. 16
Recoil start (manual start) .......................................... 17
Running the generator .................................................. 17
During operaon ........................................................... 17
Stopping the generator ................................................. 18
AC applicaon ............................................................... 18
Generator overload ...................................................... 19
General Maintenance ................................................... 19
Maintenance schedule .............................................. 19
Air cleaner element ................................................... 20
Fuel lter ................................................................... 20
Adjustments .............................................................. 20
Baery/baery charging ........................................... 20
Electrical Diagram ......................................................... 21
Storage and Transport .................................................. 22
Storage ...................................................................... 22
Long term storage ..................................................... 22
Starng posion ........................................................ 22
Troubleshoong ............................................................ 23
Pg. 3
Cromtech Diesel 6000W Generator Manual April 2020.indd 3Cromtech Diesel 6000W Generator Manual April 2020.indd 3 21/4/20 7:25 pm21/4/20 7:25 pm

WARRANTY
CROMTECH™and CROMMELINS™ are a registered trademark of The
Crommelin Group. Crommelins warrants their goods against defects in
materials and workmanship under normal use and service.
The Crommelin Group warranty does not cover fair wear commensurate
with the age of the product, any damage caused by accident, abuse,
misuse, neglect or failure to observe proper operang instrucons or
proper machinery maintenance as described in the instrucon manual.
It is the owner’s responsibility to regularly maintain a product in
accordance with the owner’s manual and only use the equipment for its
designed purpose.
Our goods come with guarantees that cannot be excluded under the
Australian Consumer Law. You are entled to a replacement or refund
for a major failure and for compensaon for any other reasonably
foreseeable loss or damage. You are also entled to have goods repaired
or replaced if the goods fail to be of acceptable quality and the failure
does not amount to a major failure.
CONSUMER ADVICE
Any claim under these warranes must be made in the warranty period
from the date of purchase of the product.
There are over 185 naonal authorised service/repair agents available,
visit www.crommelins.com.au for their details and locaons.
To make a claim under the warranty, you must return the product
(with proof of purchase) to the closest warranty agent or to the place of
purchase.
Where a failure does not amount to a major failure, Crommelins
Machinery is entled to choose between providing you with a repair,
replacement or refund. To obtain compensaon, you would need to
provide documentary evidence of the loss or damage suered, and
documentary evidence that such loss or damage was a reasonably
foreseeable consequence of a failure by The Crommelins Group to comply
with a consumer guarantee under the Australian Consumer Law.
Crommelins Operaons Pty Ltd trading as The Crommelin Group,
Crommelins Australia and Crommelins Machinery
THE CROMMELIN GROUP:
Phone (08) 9350 5588 Fax (08) 9451 6381
recepon@crommelins.com.au
www.crommelins.com.au
PO Box 352, BENTLEY WA 6982
ABN 11 008 889 656
Pg. 4
Cromtech Diesel 6000W Generator Manual April 2020.indd 4Cromtech Diesel 6000W Generator Manual April 2020.indd 4 21/4/20 7:25 pm21/4/20 7:25 pm

SAFETY WARNINGS
! WARNING: DO NOT Operate this generator unl
you have read ALL safety, operaon, and maintenance
instrucons listed in this manual.
• Failure to follow the instrucons may result in property
damage, INJURY or DEATH.
• The warnings and precauons discussed in this manual
cannot cover all possible condions and situaons that
may occur. It must be understood by the operator that
common sense and cauon are factors which cannot
be built into this product, but must be supplied by the
operator.
! WARNING: Modicaons to any part of the
generator is not allowed and will void your warranty.
! WARNING: This generator is intended for residenal
consumer use only. This generator is not designed for
permanent applicaon.
! WARNING: Before each use, check for loose or
damaged parts, signs of oil or fuel leaks, and any other
condion that may aect proper operaon. Repair or
replace all damaged or defecve parts immediately.
• Locate all operang controls and safety labels.
• Operate only on level surfaces.
• DO NOT expose generator to excessive moisture, dust,
or dirt.
• Keep all safety guards in place and in proper working
order at all mes.
• DO NOT allow any material to block the cooling slots.
• DO NOT allow children or untrained persons to operate
the generang set.
• DO NOT run the generang set unaended. Turn o the
generang set before leaving the area.
Pg. 5
Cromtech Diesel 6000W Generator Manual April 2020.indd 5Cromtech Diesel 6000W Generator Manual April 2020.indd 5 21/4/20 7:25 pm21/4/20 7:25 pm

SAFETY WARNINGS
!DANGER: FIRE OR EXPLOSION - Diesel fuel is
ammable and explosive.
• Fire or explosion can cause severe burns or death.
• Keep ammable items away while handling fuel.
• Fill fuel tank outdoors and in a well-venlated area with
the generator stopped.
• Always wipe o spilled fuel and wait unl the fuel has
dried before starng the generator.
• DO NOT operate the generator with known leaks in the
fuel system.
• Use proper fuel storage and handling procedures. DO
NOT store fuel or other ammable materials nearby.
• Empty the fuel tank before storing or transporng the
generator.
• Keep re exnguisher handy and be prepared if a re
starts.
!DANGER: TOXIC FUMES - The exhaust of the generator
engine contains carbon monoxide, an odourless, colourless,
poison gas. Using engine indoors CAN KILL YOU!
• NEVER use generator inside any building or any kind of
enclosure, EVEN IF doors and windows are open.
• Place the generator in a well-venlated area and
consider wind and air currents when posioning the
generator.
!DANGER: MOVING PARTS - Moving parts can cause
severe injury. Keep hands and feet away.
• DO NOT operate generator with covers, shrouds, or
guards removed.
• DO NOT wear loose-ng clothing, dangling
drawstrings or items that could become caught. Tie up
long hair and remove jewellery.
• NEVER place ngers, hands, or body near the engine
when it is running.
!DANGER: KICKBACK - Rapid retracon of the starter
cord will pull hand and arm towards the engine faster
than you can let go.
• Unintenonal start-up could result in an injury.
Pg. 6
Cromtech Diesel 6000W Generator Manual April 2020.indd 6Cromtech Diesel 6000W Generator Manual April 2020.indd 6 21/4/20 7:25 pm21/4/20 7:25 pm

SAFETY WARNINGS
!WARNING: HOT SURFACE - The running generator
produces heat. Severe burns can occur on contact.
• DO NOT touch generator while operang or just aer
stopping. Avoid contact with hot exhaust gases.
• Maintain at least one metre of clearance on all sides to
ensure adequate cooling.
• Combusble material can catch re on contact.
Maintain at least one metre of clearance from
combusble materials.
!WARNING: ACID (For types equipped with baery) -
Be careful when using any baery.
• Keep away from open ame, heat or spark.
• Baery will exhaust hydrogen while charging.
Only charge a baery in a well venlated place.
• Avoid spilled baery acid. If contact with skin is made,
wash immediately with clean water.
!WARNING: ELECTRICAL SHOCK - This generator
produces powerful voltage and the electricity CAN KILL
YOU.
• To reduce the risk of electrical shock, DO NOT use
electrical cords that are worn, frayed, bare or otherwise
damaged.
• DO NOT touch bare wires or receptacles.
• DO NOT operate generator in wet weather.
Keep the generator dry.
• DO NOT handle generator or electrical cords while
standing in water, while barefoot, or while hands or
feet are wet.
• DO NOT allow unqualied persons or children to
operate or service the generator.
• DO NOT connect this generator directly to a power
supply
Pg. 7
Cromtech Diesel 6000W Generator Manual April 2020.indd 7Cromtech Diesel 6000W Generator Manual April 2020.indd 7 21/4/20 7:25 pm21/4/20 7:25 pm

TG6000DVE FEATURES
CONTROL PANEL
Pg. 8
❶ Fuel cap
❷ Fuel level indicator
❸ Fuel tank
❹ Frame
❺ Decompression Lever
❻ Muer guard
❶ On/O Switch
❷ Power indicator
❸ Volt Frequency Time Meter
❹ AC Reset switch/s
❺ RCD Breaker
❻ 2x 15 Amp Outlets
❼ Earth screw
❼ Air cleaner
❽ Recoil start
❾ Ignion switch
❿ VHT Meter
⓫ Outlets
⓬ Circuit breakers
⓭ Grounding screw
⓮ Rubber mounts
⓯ Alternator
⓰ Oil drain plug
⓱Oil ller cap/dipsck
⓲ Fuel connecting nut
Cromtech Diesel 6000W Generator Manual April 2020.indd 8Cromtech Diesel 6000W Generator Manual April 2020.indd 8 21/4/20 7:25 pm21/4/20 7:25 pm

GENERATOR SPECIFICATIONS
Model TG6000DVE
Max. Output (W) 6000w
Cont. Rated Output (W) 5500w
Rated Voltage 240V / 50Hz
Power Factor 1.0
Engine 9.8hp Cromtech 188FG
Engine Features OHV, air cooled
Displacement 474cc
Fuel Type Diesel
Fuel Tank 12.5L
Oil Capacity 5.5L
Decibels at 1m (db) 95db
Weight (kg) 103.5kg
Packaging (LxWxH) 800x550x640mm
FEATURES
• 2x Outlets (single phase - 15amp IP66 rate)
• RCD Protecon
• AC Overload protecon
• VHT Meter (Volts, Hertz, Time)
• Diesel powered
• Electric start and recoil start
• Fold-out handles
• Low oil alarm, overload alarm, output indicator
• Large 12.5L fuel tank
• 1 Year Cromtech Warranty
Pg. 9
Cromtech Diesel 6000W Generator Manual April 2020.indd 9Cromtech Diesel 6000W Generator Manual April 2020.indd 9 21/4/20 7:25 pm21/4/20 7:25 pm

OPERATING CHECKLIST
1. OPERATING AREA - This generator is for outdoor use.
• Only use OUTSIDE and place the generator in a
well-venlated area.
• Only operate the generator on a at, level surface
and in a clean, dry operang environment.
• Allow one metre clearance on all side of the
generator while operang it outdoors.
• Generators used for construcon sites may be
subject to addional rules and regulaons.
• DO NOT connect generator to power supply.
• When operang wear ear protecon.
! DANGER: TOXIC FUMES - The exhaust of the
generang set contains carbon monoxide, an
odourless, colourless, poison gas.
Using engine indoors CAN KILL YOU.
• NEVER use inside any building or any kind of
enclosure, EVEN IF doors and windows are open.
• Place the generator in a well-venlated area and
carefully consider wind and air currents when
posioning generator.
2. OPERATING CONDITION - Check for loose or damaged
parts, signs of oil or fuel leaks, and any other condion
that may aect proper operaon. Repair or replace all
damaged or defecve parts immediately.
• Remove any excessive dirt or debris, especially
around the muer and recoil starter.
• DO NOT move or p the generator during operaon.
Use generator only for intended uses. If you have
quesons about intended use, ask your local dealer.
! DANGER: Failing to correct problem(s) before
operaon could result in property damage, serious
injury or DEATH.
Pg. 10
Cromtech Diesel 6000W Generator Manual April 2020.indd 10Cromtech Diesel 6000W Generator Manual April 2020.indd 10 21/4/20 7:25 pm21/4/20 7:25 pm

3. CHECK ENGINE OIL
! WARNING: This engine is not lled with oil. Any
aempt to crank or start the engine before it has
been properly lled (with the recommended type and
amount of oil) may result in engine damage and void
your warranty.
1. ENGINE OIL - Place the generator on a level surface
with engine stopped.
• Remove the dipsck and wipe it clean.
• Reinstall dipsck into tube; rest on oil ll neck,
DO NOT thread cap into tube.
2. Remove the dipsck again and check oil level. Level
should be at top of indicator on dipsck.
3. If lower, ll to the upper limit (marked with “H”) of
the dipsck with the recommended oil. Reinsert and
fully ghten the dipsck.
! WARNING: Oil is a major factor aecng
performance and service life of an engine.
Use SAE30 oil.
! CAUTION: LEVEL GROUND - Operate generator
only on levelled surface. The engine is equipped with
a low oil sensor (applicable types) that will automac
stop the engine when the oil level falls below the safe
limit. To avoid the inconvenience of an unexpected
shut-down, ll to the upper limit and check the oil
level regularly.
Pg. 11
Cromtech Diesel 6000W Generator Manual April 2020.indd 11Cromtech Diesel 6000W Generator Manual April 2020.indd 11 21/4/20 7:25 pm21/4/20 7:25 pm

4. CHECK FUEL LEVELS
! CAUTION: Only diesel fuel can be used. The fuel
must be ltered. Fuel should be free of water or dust
as this can result in problems with the fuel injecon
generator and nozzle.
FILLING THE FUEL TANK - With the engine stopped,
check the fuel level gauge. Rell the fuel tank if
necessary.
• Use clean, fresh, regular diesel fuel only.
• DO NOT mix with other fuels.
• Be sure not to ll above the upper limit mark,
always ll to the level indicator, or ll to 25mm
below full level (to allow room for fuel expansion in
hot temperatures).
! DANGER: FIRE OR EXPLOSION - Diesel is
ammable and explosive. A re or explosion can cause
severe burns or death.
• Keep ammable items away while handling diesel
fuel.
• Fill fuel tank outdoors and in a well-venlated area
with the engine stopped.
• Always wipe o spilled fuel and wait unl the fuel
has dried before starng the engine.
• DO NOT operate the engine with known leaks in
the fuel system.
• Use proper fuel storage and handling procedures.
DO NOT store fuel or other ammable materials
nearby.
• Empty the fuel tank before storing or transporng
this engine.
• Keep re exnguisher handy and be prepared if a
re starts.
! CAUTION: To insure easy starng, do not use fuel
le over from the previous season.
5. ELECTRICAL DEVICES
! NOTE: Disconnect all electrical devices from the
generator before starng the engine.
• The generator may be hard to start with electrical
devices connected.
Pg. 12
Cromtech Diesel 6000W Generator Manual April 2020.indd 12Cromtech Diesel 6000W Generator Manual April 2020.indd 12 21/4/20 7:25 pm21/4/20 7:25 pm

6. CHECK AIR CLEANER ELEMENT
! WARNING: Never run the generator without the
air cleaner element as damage to the engine may
occur.
• The air cleaner must be changed when the output
of engine decreases or if the exhaust colour looks
darker than normal. See page 19.
7. CONNECTING ELECTRICAL DEVICES
! NOTE: This generator is ed with an RCD Circuit
Breaker. ALWAYS test RCD switch before every use.
! CAUTION: Do not use any appliance with a
damaged cord or switch.
! NOTE: Allow the engine to stabilise and warm up
for a few minutes aer starng.
! NOTE: Make sure the electrical devices are in their
‘OFF’ posion and the load current is not higher than
the maximum withstanding current of a single socket.
Pg. 13
Cromtech Diesel 6000W Generator Manual April 2020.indd 13Cromtech Diesel 6000W Generator Manual April 2020.indd 13 21/4/20 7:25 pm21/4/20 7:25 pm

LOW OIL WARNING SYSTEM/STOP DEVICE
! NOTE: The device works automacally to stop the
engine when the oil pressure falls below the regulatory
level to prevent engine seizure
• The oil temperature will rise too high if the engine is
operated with insucient oil.
• Too much oil is dangerous as it may cause sudden
excessive engine revs.
• Be sure to check oil is at opmum specied levels.
BREAK-IN OPERATION
! WARNING: While your generator is sll new,
applicaon of heavy loads may shorten the life of the
engine. Follow the break-in procedures during the rst
20-30 hours.
1. Avoid applying any heavy load during break-in period.
2. Change engine oil regularly (Every 20 hours or one
month aer inial use, and every 3 months or 100
hours thereaer).
MAXIMUM CAPACITY
! WARNING: DO NOT overload the generator.
Exceeding the capacity of generator can damage the
generator and/or electrical devices connected to it.
• You must make sure your generator can supply the
rated (running) and surge (starng) was for the
electrical device/s you are powering.
• Follow these simple steps to calculate the running and
starng was necessary for your purposes.
1. Select the electrical device/s you will
be powering
2. Calculate that the total amount of power
you need to run all devices is less than
the rated output of the generator. You
may need to check the items rated (running) was in
their manuals.
3. Idenfy how many surge (starng) was you may need.
Surge waage is the short burst of power needed
to start electric motor-driven appliances such as a
refrigerator or water generator.
Pg. 14
Cromtech Diesel 6000W Generator Manual April 2020.indd 14Cromtech Diesel 6000W Generator Manual April 2020.indd 14 21/4/20 7:25 pm21/4/20 7:25 pm

! CAUTION: If connected devices overheat.
Immediately turn them o and disconnect from the
generator.
! NOTE: AC OVERLOAD RESET BUTTON/S - If the AC
power outlet is overloaded, the AC circuit breaker will cut
out the power to the device. If tripped remove device/
load and reset buon.
• If tripping connues, remove the device and have it
checked by a licensed electrician.
! NOTE: Not all motors can start at the same me, total
surge was can be esmated by adding only the electrical
device(s) with the highest addional surge was to the
total rated was.
WATTAGE REFERENCE GUIDE ONLY
ELECTRICAL EQUIPMENT RATED POWER (W)
Tablet computer 27” 120W
Electric Cooker 1000W
Personal Computer (standard) 250-600W
Refrigerator (standard) 50-200W
Kele 1800W
2.0hp Air Condioner 1800W
Electric Hammer 1000W
Water Generator 800W
Pg. 15
Cromtech Diesel 6000W Generator Manual April 2020.indd 15Cromtech Diesel 6000W Generator Manual April 2020.indd 15 21/4/20 7:25 pm21/4/20 7:25 pm

PRE-START INSTRUCTIONS
! NOTE: When starng the generator for the rst me,
restarng the engine aer it stopped due to fuel shortage
or starng the engine aer fuel lter cleaning. Follow
these steps.
• Always check that there is no air trapped in the fuel
line. Trapped air needs to be cleared before starng.
1. To clear air in the fuel line, loosen the fuel
connecon nut that is between the injecng
generator and fuel line
(See page 8).
2. Ensure the ignion is in the
‘OFF’ posion.
3. Bleed the fuel line by pulling
the recoil starter to start the
ow of fuel.
4. Connue unl there is no air bubbles coming out
and the fuel is owing freely.
5. Tighten fuel connecon nut.
STARTING THE GENERATOR
ELECTRIC STARTING
! NOTE: Always keep the starng key turned to ‘ON’
while the engine is running.
1. The preparaon for starng the engine is the same as
the recoil start.
2. Open the fuel tap to the ‘ON’ posion (Fig 1).
3. Set the engine speed lever to ‘RUN’ posion (Fig 2).
Fig 1.
Engine
speed
lever
Fig 2.
Pg. 16
Cromtech Diesel 6000W Generator Manual April 2020.indd 16Cromtech Diesel 6000W Generator Manual April 2020.indd 16 21/4/20 7:25 pm21/4/20 7:25 pm

Pg. 17
4. Push down the decompression lever (it will return
automacally when the engine is starng).
5. Turn the starng key clockwise to ‘START’ posion.
6. As soon as it starts, release your hand and let the
key automacally return to its inial posion. If the
generator doesn’t start aer 10 seconds, please wait at
least 15 seconds before aempng again.
RECOIL STARTING (MANUAL START)
! NOTE: Rapid retracon of the starter cord will pull hand
and arm towards the engine faster than you can let go.
Unintenonal start-up could result in an injury.
• Never pull out the recoil start when the diesel engine
is running, as damage may occur.
1. Open the fuel tap to the ‘ON’ posion.
2. Set the engine speed lever to ‘RUN’ posion.
3. Set ignion key switch to ‘ON’ posion.
4. Push down the decompression lever (it will return
automacally when the recoil starter is pulled).
5. Pull out the recoil start handle and prepare to start the
generator.
6. Pull the rope to the point where resistance is felt.
Return the recoil handle to the inial posion.
7. Grip the recoil handle rmly and pull quickly and briskly
(Two hands might be needed).
8. Return the recoil gently back to prevent damaging the
starter. Do not allow the handle grip to snap back.
RUNNING THE GENERATOR
! WARNING: Unapproved adjustment will damage
your engine and/or your electrical devices and void your
warranty.
• The speed has been set at the factory and should not
require readjustment. Consult your local authorised
service agent for advice.
• Warm up the engine for about 3 minutes without load
before using generator.
DURING OPERATION
! WARNING: Check for unusual sounds or vibraons
during operaon.
• Check for misring or the engine running rough
• If you noce any above problems, stop the engine and
consult you local service agent.
Cromtech Diesel 6000W Generator Manual April 2020.indd 17Cromtech Diesel 6000W Generator Manual April 2020.indd 17 21/4/20 7:25 pm21/4/20 7:25 pm

STOPPING THE GENERATOR
! WARNING: NEVER stop the engine with electrical
devices connected and the connected devices turned ‘ON’.
1. Turn o all electrical equipment and disconnect all from
the generator.
2. Allow the generator to run at no load for 3 minutes
to stabilize internal temperatures of the engine and
generang set.
3. ELECTRIC START - Switch the ignion switch to the
‘OFF’ posion.
4. Turn the fuel tap to the ‘OFF’ posion
! CAUTION: If the engine connues to run even aer
the speed lever is moved to the ‘STOP’ posion, turn the
fuel tap to the ‘OFF’ posion to stop the engine. DO NOT
stop the engine with the decompression lever.
AC APPLICATION
! NOTICE: Do not run generator for extended periods
with no load or minimal load (e.g. when charging
baeries or powering low waage equipment such as TVs
and Radios). This may cause premature excessive carbon
build up or high oil consumpon. To prevent this, run the
generator periodically with an increased load.
1. Start the engine and make sure the pilot lamp turns on.
If it doesn’t, the lament may be damaged.
2. The speed of the generator must reach rated speed
(lever set to the ‘ON’) before applying load.
3. The generators speed has been factory set at 3000rpm
50Hz.
Engine
speed
lever
Pg. 18
Cromtech Diesel 6000W Generator Manual April 2020.indd 18Cromtech Diesel 6000W Generator Manual April 2020.indd 18 21/4/20 7:25 pm21/4/20 7:25 pm

GENERAL MAINTENANCE
! NOTE: It’s the operator’s responsibility to complete
all scheduled maintenance in a mely manner. Correct
any issue before operang the generang set. Always
follow the inspecon and maintenance recommendaons
and schedules in this manual.
• Before servicing the generator, stop the generator,
disconnect all electric devices and baery (if equipped)
and allow the generator to cool down.
MAINTENANCE SCHEDULE - Follow the service intervals
indicated in the chart below. Service your generator more
frequently when operang in adverse condions.
• Contact your local service agent for parts or engine
maintenance needs.
• See maintenance schedule on next page.
Change lube oil
Pg. 19
GENERATOR OVERLOAD
! CAUTION: If an overloading of the circuit trips the
AC circuit Breaker, reduce the electrical load on the
circuit, wait a few minutes before resuming operaon.
• To reset an overload, shut down and restart the
generator.
Cromtech Diesel 6000W Generator Manual April 2020.indd 19Cromtech Diesel 6000W Generator Manual April 2020.indd 19 21/4/20 7:25 pm21/4/20 7:25 pm

GENERAL MAINTENANCE
CHECK/CHANGE AIR CLEANER ELEMENT
! WARNING: Never run the generator without the air
cleaner element as damage to the engine may occur.
• The air cleaner must be changed when the output of
engine decreases or if the exhaust colour looks darker
than normal.
1. Loosen the wing nut,
detach the cover and
remove the air cleaner
element.
2. Wash in warm water. DO
NOT wash with detergent.
3. Squeeze thoroughly and
dry with a clean cloth.
4. Saturate in clean engine oil. Squeeze in a clean,
absorbent cloth to remove
all excessive oil.
5. Place element back in the
air cleaner and reaach the
cover. Tighten wing nut.
CHECK/CHANGE FUEL FILTER
! WARNING: Change lter regularly to insure maximum
engine output.
• CLEAN FILTER - Every 6 months or 300 hours.
• REPLACE FILTER - Every year or 1000 hours.
ADJUSTMENTS
! WARNING: Tampering with the factory set governor
will damage your generator and void your warranty.
CHECK BATTERY / CHARGING BATTERY
• Before starng check baery for damage. Baery ed
is maintenance-free, check for green light on baery to
ensure it is charged. If baery requires charging use a
compable baery charger. Baery type 12v 36ah.