Culligan GBE Service manual

CULLIGAN®
Global Electronic (GBE)
Softener & Filter Controller
For Commercial/Industrial Applications
Models from 2008
©2008 Culligan International Company
Cat. No. 01021161
Rev. A 10/16/08
DCO # 010703
Installation,
Operating and
Service
Instructions
Printed in USA

Read this Manual First
Before you operate the Culligan Global Controller, read this manual to become familiar with the device and
its capabilities.
Watch for Special Paragraphs
Please read the special paragraphs in this manual. Examples are shown below.
NOTE A Note provides information or highlights a procedure.
CAUTION
A Caution tells how failing to follow instructions might cause
injury or damage the equipment in some way.
About this Manual
Contents
This manual:
• familiarizes the operator with the equipment
• explains installation and setup procedures
• provides basic programming information
• explains the various modes of operation
• gives specifications and troubleshooting information
TABLE OF CONTENTS ii
i CULLIGAN GLOBAL ELECTRONIC CONTROLLER
This equipment complies with Part 15 of the FCC rules. Any changes or modifications not expressly approved
by the manufacturer could void the user’s authority to operate the equipment. Changes or modifications not
expressly approved by the party responsible for compliance could void the user’s authority to operate
the equipment.
WARNING! Electrical shock hazard! Unplug the unit before removing the cover or accessing any internal control parts.
WARNING! This device complies with part 15 of the FCC rules subject to the two following conditions: 1) This device may
not cause harmful interference 2) this device must accept all interference received including interference that may cause
undesired operation.
CAUTION! To reduce the risk of fire, use only No. 26 AWG or larger telecommunicaitons line cord.
Products manufactured and marketed by Culligan International Company (Culligan) and its affiliates are protected by patents issued or pend-
ing in the United States and other countries. Culligan reserves the right to change the specifications referred to in this literature at any time,
without prior notice. Culligan, AquaSensor, Tripl-Hull, and SoftMinder are trademarks of Culligan International Company or its affiliates.
The product is covered by the following patents:
Softener and/or filter: US 5073255, 5273070, 6457698, 4534867: Israel 095754
Sensor option: US 5699272
Other US and foreign patents pending.

TABLE OF CONTENTS ii
i CULLIGAN GLOBAL ELECTRONIC CONTROLLER
CULLIGAN®
GLOBAL ELECTRONIC (GBE) SOFTENER
& FILTER CONTROLLER
Installation,
Operating and
Service
Instructions
Table of Contents ................Page
Important Safety Information....................................... i
Controller Features..................................................1-2
Operation....................................................................3
Installation ...............................................................4-6
Wiring Schematics.................................................7-17
Circuit Board Layout..............................................7
Transformer ........................................................8-9
Brine Refill Valve .................................................10
Communication Cable .........................................11
Progressive/ Parallel Flow...................................12
Alternating ...........................................................13
Flow Meters .........................................................14
Aqua-Sensor........................................................15
Aux Outputs.........................................................16
Aux Input .............................................................17
Programming.......................................................18-20
Key Pad Operation .............................................19-20
Overview...................................................................21
Commercial Setup....................................................22
First Time Setup..................................................23-27
Customizing the Setup ........................................28-32
Progressive Flow .................................................29
Regeneration .......................................................30
Cycle Times.........................................................31
Regeneration Triggers.........................................32
Installation of Accessories...................................33-45
Aqua-Sensor........................................................33
Beeper Mode .......................................................33
Smart brine Tank Sensor ....................................34
Wireless Remote ............................................35-37
Modem............................................................37-41
Low Meter............................................................41
Progressive Flow ............................................41-42
Brine Reclaim .................................................42-43
Service Phone Number ......................................44
Auxiliary Boards ..................................................46-48
Manual Regeneration ...............................................49
Manual Cycling.........................................................50
System Information .............................................51-52
Error & Alert Codes ..................................................53
Diagnostics / Statistics ........................................54-57
Check Sensors ....................................................55-57
Menu Lockout...........................................................58
Menu Flow Chart.................................................59-62
Appendix A - Meter K-Factors..................................63
Appendix B - Parts & Accessories ..........................64
Appendix C - PLC Output....................................65-68
Appendix D - Control Settings..................................69
Index.........................................................................70

1 CULLIGAN GLOBAL ELECTRONIC CONTROLLER
The Culligan Global Electronic control (GBE) primary function is to
initiate and control the regeneration process via methods that are most
convenient and cost effective for the customer while offering many
operational features and benefits. The controller is designed to operate a
wide range of existing and new softener and filtration valves.
Take control of your system and your productivity
The Culligan Global Electronic Controller (GBE) is an advanced design
engineered to handle regeneration and monitoring of your water
treatment equipment. It offers powerful programming options that
can be used to operate and monitor any softener or filter system. It
also provides sensing capabilities, expanded communications and a
multifunction keypad—all in one simple to use unit.
GBE Controller Features
Advanced Lighted OLED Display
The user is guided through brightly lit graphical menu screens
with clear, multi-line, full text prompts
Membrane Keypad
The keypad uses sealed contacts for programming. No buttons to get dirty
Program Beeper
Emits an audible beep when keys are depressed to help identify
valid (short beep) or invalid (3 short beeps) pushes. Can be
enabled or disabled.
Power Source
Electrical power required is 24 Volt 50/60 Hz AC current. A UL
listed plug-in transformer (120V/24V) is provided.
Time of Day
Displays current time of day in either 12-hour or 24 hour format
Real Time Clock with a 5 Year Battery Back-up
Keeps accurate time even during a power outage. Updates
automatically when the GBE is equipped with optional modem
capability
English or Metric Values
Displays can be set to either English or Metric
Regeneration Interval
Provides the ability to initiate a time clock regeneration based on a number of days (1 to 99) or a specific
day of the week.
Regeneration Start Delay
Allows a user determined number of hours (0-9) to be set for the purpose of increasing the amount of
time between regenerations in a multi unit installation.
Auxiliary Input
Capable of accepting a remote signal from a dry contact device such as an operator push button for the
purpose of initiating a regeneration sequence
Auxiliary Output on Alarm
Capable of sending a signal when an alarm/error is recognized
Expansion Board for Additional Outputs
o Control blocking valves
o Control external solenoids or chemical feeders
•
•
•
•
•
•
•
•
•
•
•
•
Controller Features
Figure 2
Figure 1

CONTROLLER FEATURES 2
Progressive Flow Trip Point
Allows multiple tank systems operating with flow meters to bring tanks on-line or off-line as facility flow
demands increase or decrease
Multiple Unit Communication
A communication cable interconnects multiple units to operate the controller in the Progressive Flow
mode and prohibits them from regenerating at the same time.
Diagnostics
The user can check the operation of sensors, progressive flow communication, motor positions, or an
optional wireless display
Transformer is UL and CUL Listed
RoHS Compliant
Optional GBE Features
Flow Meter/Sensor Input
Supports various types of Hall effect flow sensors using a programmable “K” factor to initiate a
regeneration sequence
AquaSensor Input
Supports the patented digital Culligan AquaSensor technology used to efficiently initiate and control a
regeneration sequence
Telephone Modem
o Calls in reports on regenerations and alarm conditions
o Automatically updates time and date when calling in
o Automatically checks for and installs and firmware updates when calling in
Wireless Remote Display
Displays the current status of the unit. It can be located up to 200 feet away from the GBE controller
(depending on building and interference). The telephone modem can optionally be installed in the remote
display
Smart Brine Tank Probe
This probe monitors conditions inside the brine tank.
o Predicts when more salt is needed
o Detects the presence of a salt bridge
o Detects eductor line plugging
o Signals brine tank overfilling condition
•
•
•
•
•
•
•
•
•
•
Controller Features

Modes of Operation
Time Clock
The controller will initiate a regeneration based upon a time schedule of intervals of days (i.e., every 3 days) or
on a specific day of week schedule (i.e., Mondays, Wednesdays and Saturdays). Because regeneration will
occur at the prescribed schedule regardless of water use, this method is usually the most inefficient method of
water softener operation.
Flow Meter/Sensor
When a flow meter or sensor is connected to the controller circuit board, the controller has the ability to measure
the amount of water treated and initiate a regeneration sequence based upon the gallon capacity of the water
treatment equipment. The controller can delay the regeneration signal until a convenient time of day (known as
a delayed regeneration) or act and initiate the regeneration sequence as soon as the signal is received (known
as immediate regeneration).
When installing an alternating duplex system (one tank on-line, the other in standby), only one flow measuring
device is required to be installed in the common outlet header of the system. Parallel systems (multiple tank sys-
tems, all on-line simultaneously) require one flow device for each mineral tank in the system.
This method is a proven, cost effective means to operate a water softening system.
Aqua-Sensor (Softener use only)
The Aqua-Sensor detects when a softener resin bed has reached its point of exhaustion and, as a result, initiate
a regeneration sequence. This is the most cost-effective method of operation and may be combined with any of
the operational modes previously described.
Progressive Flow
The Progressive Flow mode is used with up to six and as few as two mineral tanks in a system. It allows more
than one tank in a system to either be on-line or off-line depending upon the downstream flow demand. If flow
demand is greater than the flow capability of the tank on-line, another tank can be brought on-line to help satisfy
the excess demand. Once the demand has decreased, the second tank is returned to a standby mode and the
system reverts to just one tank on-line providing treated water.
The progressive flow mode of operation relies on a user programmable set point or Trip Point. The Trip Point
is a unit of flow (gallons or liters) on a per minute basis. Once attained the trip point will cause the second unit
(in multiple resin tank system) to come on-line. Each additional tank in the system will subsequently be brought
on-line as multiples of the trip point are attained. (Example: a 3 tank system with a trip point of 50 gpm will bring
two tanks on-line once the facility flow demands is equal to or greater than the 50 gpm trip point. Should the flow
demand reach 100 gpm or more, the third tank shall be brought on-line.)
Additional tanks shall be returned to stand-by once the facility flow demand is <95% of the trip point for two
tank systems, <95% of 2X the trip point for triplex systems and <95% of 3X the trip point for quad systems, and
remains there for 60 seconds.
Utilizing the progressive flow feature may allow the owner to use smaller units, resulting in the potential for
reduced capital and operation costs.
Differential Pressure (Filters only)
When combined with an optional differential pressure device, the Culligan MVP controller has the ability to
initiate a backwashing sequence when the pressure differential across the media bed reaches a preset amount
(usually 8 to 10 psi).
Operation
Installation 4
3 CULLIGAN GLOBAL ELECTRONIC CONTROLLER

Installation
ELECTRICAL INSTALLATION
CAUTION!
Observe the precautions listed below before electrical installation of your GBE controller.
Failure to do so may cause permanent damage to the controller.
1. Follow the local electrical code requirements.
2. Be sure electrical power is off and disconnected at the source before completing any wiring/cabling
connections.
3. Provide a dedicated 120-volt circuit for the GBE system to ensure maximum electrical protection.
4. DO NOT include the GBE wiring cables in any conduit or raceway containing other 120-volt or higher
circuits.
5. Maintain a distance of at least 10 feet between the GBE controller and any electrical distribution
panels, raceways carrying 300 volts or more, and electrical motors of 1 horsepower or more.
6. Use the cabling provided. Failure to do so may effect performance of the GBE controller adversely.
Note: One transformer is required for each controller in the system. Do not attempt to operate multiple
controllers without a dedicated transformer for each or your system will experience operational
difficulties.
Installation 4
3 CULLIGAN GLOBAL ELECTRONIC CONTROLLER

WIRING PROCEDURES AND DIAGRAMS
Preparation
1. Loosen the screws or latches securing the controller access cover (Figure 3 or 4) on each controller
provided.
2. Using a small screwdriver, loosen all the terminal strip binding screws on the main circuit board that do
not contain wires by turning counterclockwise until the wire clamp has been fully opened (see Figure 5).
Installation
Figure 3
Figure 5
Installation 6
5 CULLIGAN GLOBAL ELECTRONIC CONTROLLER
Figure 4

Installation
Cable Routing
All input and output connections to the circuit board are 24 volt or less.
Although the cables do not have to be run in conduit, it is necessary that long runs of cable be supported or
protected by strapping them to the equipment piping. If conduit will be used to route the shielded cables, three
factors must be considered:
1. DO NOT share the same conduit or raceway with 120 volt or higher circuits.
2. Keep cables at least 6 inches away from 120 volt or higher electrical circuits.
3. GROUND the conduit (if metallic) to a known “earth ground” location.
A series of holes are located on the sides of the controller (see Figure 6 and 7). Strain relief fittings are provided
with the controller enclosure for interconnecting wiring. Install the plastic fittings as needed. Remove the com-
pression nut and rubber sleeve from each fitting. Prior to connection of the cable wires to the circuit board, slide
the compression nut and sleeve over the cable for the wiring connections. When wiring is completed, apply a
small amount of silicone to the rubber sleeve and reassemble. This will assure all wiring is secure and assist
in making the tightening of the fitting easier. Insert the plugs provided to block any holes not used for wiring or
other accessories.
Right Side View
Brine Reclaim Solenoid
(optional)
Input Connection
for Flow Sensor
Output Connection
for Remote
Accessories
Input Connection
for Remote
Accessories
24 Volt Power
Input Connection
Brine Reclaim Solenoid
(optional)
Brine Refill Valve
Blocking Solenoid for
Alternating Operation
Left Side View
Figure 6 Figure 7
Installation 6
5 CULLIGAN GLOBAL ELECTRONIC CONTROLLER

GBE Circuit Board Layout–Front
Keypad connector
Battery
CR2032 (Postitive Side Up)
Schematic
OLED Display
Phone line
connection
(optional)
GBE Circuit Board Layout–Back
Figure 8
Motor position cable
Multiple unit jumper
Communication cable (optional)
Flow meter cable
(optional)
Smart Brine Tank cable (optional)
External regeneration
signal connection (optional)
Motor
connection
Programmable outputs (optional)
Blocking valve
connection (optional)
Power cable
from transformer
Aqua-Sensor
cable (optional)
Future use
Do not connect
anything to these.
Data port
Figure 9
Schematic 8
7 CULLIGAN GLOBAL ELECTRONIC CONTROLLER

CAUTION
Connecting 24V to the 2.5v
connection on the circuit board
will damage the circuit board.
Outputs
The circuit board supports four outputs:
• Motor control (DC Motor)
• Blocking valve (Use Aux Out 4)
• Four programmable auxiliary outputs (Aux Out 1
through 4)
• Controller interface (communication between mul-
tiple controllers) (RS485).
Note: If you are using Aqua-Sensor, you should run the 2.5v wiring now as the cable is run through the same cord grip.
See page 15 for details.
1. Locate the power cord among the controller parts. It has a white connector on one end and two spade connectors on the
other.
2. Locate the cord grip among the parts.
3. To assemble the power cord, first run the cord grip nut over the spade terminal end of the power cord.
4. Next, run the spade terminals through a hole in the side of the controller FROM THE INSIDE. See figure 10.
5. Finally, run the cable through the bottom end of the cord grip, and assemble the grip to the controller wall.
6. Plug the board connector to the board where it says “24v”. The connector has four (4) connections but only two wires are
connected. The other end of the power cord (with spade terminals) should be connected to the two 24VAC terminals on
the transformer (see figure 12).
DO NOT PLUG THE TRANSFORMER INTO THE WALL UNTIL ALL WIRING IS COMPLETED.
Repeat the process for any additional units in the system.
Schematic 8
7 CULLIGAN GLOBAL ELECTRONIC CONTROLLER
Schematic

24V Transformer
The GBE control is powered by a 24V/50VA transformer. If there are multiple controls in the system being
installed, each control will require its own transformer. It is recommended that the transformer be plugged into a
dedicated 120V circuit.
CAUTION
Connecting 24V to the 2.5V connection on the circuit board will damage the circuit board
1. Connect one wire from the 24V cable to the outermost 24VAC transformer screw terminal
(Reference Figure 12). The other end of the wire should be connected to one of the 24V terminals
on the GBE control circuit board (Figure 11) by way of the white connector.
2. Repeat the process for the other 24V power supply wire attaching the second wire to the opposite
terminal on the transformer and next to the other wire connected to the 24V pins on the GBE board.
Schematic
Figure 11
POWER SUPPLY
ONE transformer is required for each Control
Figure 12
2.5VAC Aqua-Sensor
Power Terminals
24VAC Power
Terminals
METAL TABS
Connect to white connector
on main power cord
If using Aqua-Sensor,
plug metal tabs at end
of cord into connector
24V Power Connection
Figure 10
Schematic 10
9 CULLIGAN GLOBAL ELECTRONIC CONTROLLER
Transformer connection

Schematic 10
9 CULLIGAN GLOBAL ELECTRONIC CONTROLLER
Schematic
Brine Refill Valve Wiring
*This only applies to Culligan CSM Softeners.
1. Installation of the solenoid coil and connector
Locate the solenoid coil and connector cord. Assemble it
to the brine refill valve as shown in Figure 13.
2. Installation of the cord grip
Remove the hole plug from the left side of the MVP
controller enclosure. Locate the cord grip fitting and nut.
Assemble them through the open hole and thread the
solenoid coil cord through the cord grip fitting as shown
in Figure 14. Tighten the cord grip onto the cord.
3. Wiring
Wire the valve to Aux Out 2 as shown in the diagram in
Figure 15. The wires can be trimmed to a suitable length.
Solenoid
Coil
Screw Plastic
Spacer
2.5VAC
P9 Power
24VAC
Vlv
Aux1
Sol
P7 Aux2
P8P5
Cam
P1 P10
Snsr
Aqua Meter
P4
Flow In
P2
Aux
LCD
TRIM OFF
GREEN WIRE
BLACK
WHITE
REFILL
SOLENOID
VALVE
CIRCUIT BOARD
MVP
Figure 13
Figure 14
Figure 15

Communication Cable - Multiple Units
NOTE: Disregard this information and proceed to flow sensor schematic (optional) information when installing
single tank configurations.
Multiple units require a communication cable between each unit. Refer to the table below for the cable type, part
number and quantity required. Cables are attached to the RS485 terminal of the circuit board.
Table 2
System
Configuration
Cable Part Number Qty of Cables
required
“Kit” Part Number Qty of blocking
solenoids used.
Duplex Alternating 01016342 1 01016369 2
Duplex Parallel 01016327 1 N/A 0
Triplex Parallel 01016327 2 N/A 0
Duplex Progressive 01016327 1 01016333 2
Triplex Progressive 01016327 2 01016334 3
Multiple units can be set up as progressive flow, alternating or parallel operation. Refer to the instructions and
schematics below and on the following pages for connection to the circuit board.
Most multiple tank configurations will also require blocking valves (with the exception of the Hi-Flo 3e softener).
These are used to hold tanks offline until needed. Based on the chart above, you can determine how many
blocking solenoids are used. These solenoids are included in the alternating and progressive flow kits.
Blocking Solenoid Connection (used on Alternating and Progressive flow systems)
The solenoid valve wiring attaches to the Aux Out 4 output connection on the auxiliary circuit board. See
Figure 16 .
Schematic
Schematic 12
11 CULLIGAN GLOBAL ELECTRONIC CONTROLLER
SOL
Figure 16

Progressive Flow or Parallel Flow
IMPORTANT
Setting the Jumpers for Progressive Flow
For progressive flow to operate properly, the first and last units must
have the jumpers set to pins 1 and 2 (see figure at right). All middle
units should have the jumpers on pins 2 and 3 (see figure at right).
The diagram below (figure 17) shows duplex connections. Repeat the
connections on any additional systems.
Progressive/Parallel Communication Cable 01016327
Schematic 12
11 CULLIGAN GLOBAL ELECTRONIC CONTROLLER
Schematic
To RS 485 Comm Port
on GBE Circuit Board, #1
CABLE 01016327
To RS 485 Comm Port
on GBE Circuit Board, #2
PARALLEL
Additional communication cable
connections are used when there
are 3 or more controls. Connect
end of 2nd-(01016327) cable
to this connector and other end of
cable to RS 485 Comm Port on
3rd GBE Circuit Board.
To Additional Units
(if necessary)
Communication Cable 01016327
Jumper
Location
Figure 17
Flow Meter Flow Meter
Unit 1 Unit 2
Jumper location for
first and last units
(end units).
Jumper location for
middle units.
1 2 3

Schematic
Schematic 14
13 CULLIGAN GLOBAL ELECTRONIC CONTROLLER
To RS 485Comm Port
on GBE Ciruit Board, #1
To Flow Meter Connection
on GBE Circuit Board.
CABLE 01016342
Flow Meter Connector
(from meter).
To Flow Meter Connection
(on GBE Circuit Board).
To RS 485Comm Port
on GBE Ciruit Board, #2
DUPLEX ALTERNATING
Duplex Alternating with Meter option
For triplex, quad, etc alternating, you must use a meter on each unit and connect the same way as
progressive flow.
Duplex Alternating Cable 01016342
Communication Cable 01016342
Figure 18
Unit 1 Unit 2
Flow meter

(optional)
2535 & 2536
Signet
Black
Shield
Red
Black
Green
Red
Paddle Wheel
(optional)
Seametrics
Green
Red
Black
White
SINGLE OR PROGRESSIVE
Bare
Red
Green
Black
Red
Black
Wht/Clear
2" Autrol Turbine Meter
(optional)
Black
White
Red
2"Clack Meter
(optional)
Schematic 14
13 CULLIGAN GLOBAL ELECTRONIC CONTROLLER
Schematic
Flow Sensor Meter Connections (Optional)
The GBE Controller is capable of detecting the signal from a Hall effect sensor device to provide flow rate infor-
mation, totalization and volume based regeneration initiation.
There are several different types of flow measuring devices and differences in the wiring of the devices to the
GBE circuit board do exist. Refer to the drawings below.
For all but duplex alternating, a meter needs to be connected to each circuit board at the location shown below
in the drawing. For duplex alternating meter connection, please refer back to page 13, Duplex Alternating with
meter option.
SEE PAGE 41 FOR PROGRAMMING AND PAGE 63 FOR K FACTORS.
Figure 19
Connector
located at
end of meter
cable
Connector
01010255 included
with controller

2.5V
METAL TABS
Connect to white
connector on main
power cord
24VAC
on TRANSFORMER
Power to circuit
board 2.5VAC
only required
for Aqua-Sensor
installations
Power to circuit
board 24V
Schematic
Schematic 16
15 CULLIGAN GLOBAL ELECTRONIC CONTROLLER
Aqua-Sensor Schematic (Optional)
The Aqua-Sensor device requires a 2.5 VAC power source. This source is provided via two of the posts on the
24VAC/2.5VAC transformer (see figure 20). The two leads from the transformer are run through the same cable
grip as the 24VAC and then must be pushed into the white power connector for connection to the 2.5v power
pins on the GBE circuit board.
The wire connector from the Aqua-Sensor probe is then routed through the included cable grip and plugged into
the Aqua-Sensor terminal on the GBE circuit board. See below.
Aqua-Sensor
If you are going to install an Aqua-Sensor, you can set up the 2.5V power now.
1. Locate the power cord packed with the Aqua-Sensor. It has two spade terminals on one end of the cable
and two metal “slip in” tabs on the other.
2. Locate the cord grip.
3. The cable can be run through the cable grip and wall from either end of the cable. Make sure the end with
the metal tabs goes INSIDE the controller. The spade terminals should be coming out the top end of the
grip.
4. Locate the connector at the end of the power cord. You may have already plugged it into the board.
5. Press the two metal tabs on the end of the power cord into the open slots on the connector. They will con-
nect to the pins labeled “2.5V’ on the Base Board.The other end of the power cord with the spade terminals
should be connected to the two 2.5VAC terminals on the transformer (see figure 20).
CAUTION - Verify wiring from terminals to circuit board are correct before applying power to
control. 24vac power must not be applied to the 2.5 vac terminals of the circuit board.
POWER SUPPLY
ONE transformer is
required for each Control
Figure 20
CAUTION
Connecting 24V to the 2.5V
connection on the circuit board
will damage the circuit board.
2.5V Aqua-Sensor Power Connection
Red
Black
Blue
White

Auxiliary Outputs (Optional)
The Auxiliary Outputs - reference Figure 21) are output triacs that can be programmed to provide power to a
“normally open” (normally no power to auxiliary output until power required) or a “normally closed” contact (user
choice). These 24VAC outputs can be used for energizing a relay coil only. (2.1 Amp maximum power draw)
Refer to the section on Programming (page 46) for additional information on the uses of this feature.
3
4
Schematic 16
15 CULLIGAN GLOBAL ELECTRONIC CONTROLLER
Schematic
Figure 21

Auxiliary Input (Optional)
One auxiliary input is provided for optional signal devices such as remote push buttons, differential pressure
switches, hardness monitors, turbid meters, etc. for the purpose of receiving a regeneration signal.
Select an UN-POWERED contact within the remote device that will close when regeneration is desired. The
duration of the switch closure can be as low as 0 seconds; 6 seconds is the recommended minimum and default
but can be as long as 999 seconds. The contact must automatically open following the start of a regeneration
sequence. Connect this contact to the Aux In terminal shown in Figure 22. The illustration below is an example
of how to use an external source to initiate regeneration.
NC NO
1
POLE
NC NO
2
POLE
C
C
SOL
Regen Signal
EXTERNAL
SOURCE
24V DPDT
RELAY
DUPLEX ALTERNATING WITH EXTERNAL SOURCE
SOL
Communication Cable
01016327
Figure 22
Schematic
Programming 18
17 CULLIGAN GLOBAL ELECTRONIC CONTROLLER
Table of contents
Other Culligan Controllers manuals