Installation Instructions/User Manual
ELCR Series
5 AMP AUTOMATIC LOAD CONTROL RELAY
currentlighting.com/dual-lite
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 1 of 4
Rev 06/06/22
DL_ELCR_INST_R01
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
IMPORTANT SAFEGUARDS
SAVE THESE IMPORTANT SAFETY INSTRUCTIONS
ALL SERVICING SHOULD BE PERFORMED BY QUALIFIED
PERSONNEL
• This product is intended for use with lighting fixtures controlled by an Emergency
panel. Any switching between Backup Power and Utility Power must be done
upstream of device.
• All wiring connections and mounting styles must be in accordance with the
National Electical Code (NEC), National Fire Protection Association (NFPA),
National Electrical Safety Code, state and local codes, and any other regulations
set forth by the local Authority Having Jurisdiction (AHJ).
• Per NFPA 70E, the use of Personal Protective Equipment (PPE) may be required.
Check state and local codes.
• The load’s operating voltage must be the same as the Emergency Power Input
voltage.
• To reduct the risk of electrical shock, fire, and injury to persons:
1. Disconnect all sources of power before servicing,
2. Mount this device in locations and at heights where it will not be readily
accessible to tampering by unauthorized personnel,
3. Do not mount near gas or electric heaters,
4. Do not let any wires touch hot surfaces, and
5. Do not use outdoors
• The use of accessory equipment not recommended by the manufacturer may
cause an unsafe condition.
• Do not use this device for other intended use.
Installation Instructions/User ManualInstallation Instructions/User Manual
ELCR Series
5 AMP AUTOMATIC LOAD CONTROL RELAY ELCR Series
5 AMP AUTOMATIC LOAD CONTROL RELAY
currentlighting.com/dual-lite
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 2 of 4
Rev 06/06/22
DL_ELCR_INST_R01
currentlighting.com/dual-lite
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 3 of 4
Rev 06/06/22
DL_ELCR_INST_R01
Electrical Specifications
Normal Power Supply Voltage
Normal Power Current Draw
Normal Power Operating Frequency
120-277VAC
24mA max
50/60Hz
Emergency Power Supply Voltage
Emergency Power Current Draw
Emergency Power Operating Frequency
120-277Vac
88mA max
50/60Hz
Remote Test Input (Class 2, Dry Contact) ELCTB or other switching method 1,2
Feedback/Dimmer Contact Switching Capability
(Dry Contact Output 1, N/O - N/C) 1A Resistance @ 30Vdc
Relay Contact
SPST 5A Electronic/LED Ballast @ 120-277VVAC
5A Ballast @ 120-277VAC
1: If not using ELCTB Remote Test Button (sold separately), switching methods should be rated for at least 24Vdc. External
voltage should not be supplied to this input. No specific current rating is required.
2: To maintain Class 2, a maximum of 45 total test inputs can be wired in parallel per ELCTB
Mechanical Specifications
Housing UL accepted for use in Plenum
Wire 16” 600V Rated
Operating Temperature -30° to 140° F (-35° to 60° C)
Humidity Range 5 to 95% (noncondensing)
Rated for dry and damp locations only
Approvals UL listed, UL924, C-UL
Installation
ALL INSTALLATIONS AND WIRING SHOULD BE DONE BY QUALIFIED PERSONNEL
Typical Applications
Using Emergency Lighting as Normal Lighting
G
Control
Circuitry
RY
Normal Power
Feedback Status
(Dry Contact Output)
Normal /
Emergency Lighting
Wall
Switch
Automatic
Transfer
Switch
Utility
Hot
Utility
Neutral
Normal
Panel
Emergency
Breaker
Emergency
Neutral
Emergency
Panel
Normal
Breaker
ELCR
Normal
Neutral
Generator
or Inverter
Hot
Generator
or Inverter
Neutral
Blue
White/Blue
* Red
Black
White
Yellow
Violet
Orange
White/Red
White/Violet
Normal Lighting
^Class 2 Remote Test Input (N/O) for
button, controller, or re alarm panel
*The Red wire must be on
the same branch circuit as the
Black wire.
When not using the Remote
Test Input, cap o the White/
Red and White/Violet wires
individually.
To use Remote Test Input, the
Red wire must be de-energized.
Input can also be sent by a controller.
^
Remote TestButton (Model ELCTB)
sold separately
White/Yellow
G
Control
Circuitry
RY
Normal /
Emergency Lighting
Automatic
Transfer
Switch
Utility
Hot
Utility
Neutral
Normal
Panel
Emergency
Breaker
Emergency
Neutral
Emergency
Panel
Normal
ELCR
Normal
Neutral
Normal Lighting
H
N
+
-
Generator
or Inverter
Neutral
Generator
or Inverter
Hot
0-10V
Dimmer
Control
*The Red wire must be on
the same branch circuit as the
Black wire.
When not using the Remote
Test Input, cap o the White/
Red and White/Violet wires
individually.
To use Remote Test Input, the
Red wire must be de-energized.
Input can also be sent by a controller.
Violet
Orange
White/Red
White/Violet
^Class 2 Remote Test Input (N/O) for
button, controller, or re alarm panel
Yellow
Blue
Wht/Blue
Black
White
*Red
^
Remote Test Button (ModelELCTB)
sold separately
Breaker
White/Yellow
Overriding a 0-10Vdc Dimmer
Ballast
Ballast
Channel
Cover
Figure A
Figure B
STEPS
1. Remove all sources of power.
2. Remove ballast channel cover.
3. Mount ELCR as shown in Figures A and B.
4. Wire the ELCR using an illustration from the “Typical
Applications” section on page 3 or similar setups for
dierent application.
5. Before applying power, review the Important Safeguards
at the beginning of this document.
6. Finish installation as required by the NEC, NFPA, state,
local, and other codes. Test the ELCR using the “Test
Procedure” on page 4.
OPERATION
The ELCR will activate an Emergency lighting load automatically upon
the loss of Normal Power. If Normal Power is absent, the status of the
load cannot be overridden. However, if the Normal Power is present,
the Emergency lighting load can be controlled by other means in order
to use it as a Normal Lighting load, depending on the wiring setup.
When used as Normal Lighting, a two second delay will keep the Load
on after Wall Switch is turned o, to perform a Self-Test on the unit.
When Normal Power is present, the N/O status contact will automatically
close. Therefore, when Normal Power is absent, the N/O status contact
will open (perfect for 0-10V dimming controls). The N/C contact will
operate opposite of N/O. A red LED indicates the Emergency Power is
available. A Green LED indicates that Normal Power is present. A Yellow
LED copies the status of the load; if the LED is on, the load is on.
MAINTENANCE
No routine maintenance is required for the
ELCR. Occasionally, this device should be tested
to ensure that it works correctly in accordance
with national and local codes.
Installation Instructions/User Manual
ELCR Series
5 AMP AUTOMATIC LOAD CONTROL RELAY
currentlighting.com/dual-lite
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 4 of 4
Rev 06/06/22
DL_ELCR_INST_R01
Wire Color Description Notes
BLACK Normal Hot N/A
RED Wall Switch Input (Self-
Test Input) Must be from same branch circuit as
Black and White. When switched o, a
two second delay keeps the load on to
test Emergency Power. Does not test
Feedback/Dimmer Output
WHITE Normal Neutral or other
Phase N/A
BLUE Emergency Hot N/A
YELLOW Emergency Hot Switched
to load Switches out the voltage put in on Blue
WHITE/BLUE Emergency Neutral or
other Phase N/A
WHITE/VIOLET Remote test Input
(Class 2, Dry Contact
Input)
When wiring multiple units together,
White/Violet must be a shared common.
Test is performed when Input is CLOSED
WHITE/RED
ORANGE (N/O)
VIOLET (C)
WHITE/YELLOW (N/C)
Feedback / Dimmer
Contact N/O is OPEN when Normal Power is
Absent or Remote test Input is CLOSED.
N/C opposite.
N/O is CLOSED when Normal Power is
Present or Remote Test Input is OPEN.
N/C opposite.
Wall Switch Input does not test this
output.
To test the ELCR periodically, repeat the appropriate Test Procedure above in accordance with national and local codes.
Condition Action
Red LED is OFF • Check Emergency Power Input wiring (Blue & White/Blue
wires) and voltage
Green LED is OFF • Check Normal Power Input wiring (Black and White wires)
and voltage.
Yellow LED is ON but Load
is OFF • Check bulbs and ballast.
• Check Load wiring (Yellow wire and Load’s neutral).
• Verify Load’s operating voltage is the same as the
Emergency Power Input Voltage.
• Replace unit
Load is ON but Yellow LED
is OFF • Replace Unit
Yellow LED and Load do not
turn on when being tested • Check bulbs and ballast
• Check wiring connections if using a remote test option
• Press local test button on the unit
• Replace unit
Yellow LED and Load will not
turn OFF • Verify status of Normal Power Input
• Open Wall Switch Input
• Verify that no test inputs are stuck closed. (i.e. Remote Test
is not closed).
Wiring Discriptions Testing Procedures
Troubleshooting
Four Options to test the ELCR after
Installation
Initial Test for Correct Wiring
Apply Emergency Power to the Emergency Power Input and Normal
Power to the Normal Power Input. (If using the Wall Switch Input, apply
Normal Power to the switch also, but keep the switch OFF/OPEN.)
a. The Red LED (Emergency Power available) should be ON.
b. The Green LED (Normal Power available) should be ON.
c. The Yellow LED (Load Status) should be OFF.
d. The Load should be OFF.
e. The Feedback/Dimmer Contact (N/O) should be CLOSED.
Local Test Button
1. Turn switched circuit OFF. Emergency light should be OFF.
2. Press and hold “Local Test Button”
3. Emergency light should turn ON.
4. Release “Local Test Button” and emergency light should turn OFF.
Remote Test Button
(Model ELCTB - sold separately)
1. Turn switched circuit OFF. Emergency light should be OFF.
2. Press and hold “Remote Test Button”
3. Emergency light should turn ON.
4. Release “Remote Test Button” and emergency light should turn OFF.
Wall Switch
1. Turn ON wall switch if not already on.
2. Emergency light should turn ON.
3. Turn wall switch OFF.
4. Emergency light will remain on for two seconds before turning o.

Popular Relay manuals by other brands

Bticino 3584C manual

Bticino

Bticino 3584C manual

Jung RS8REG operating instructions

Jung

Jung RS8REG operating instructions

Honeywell Farenhyt Series Installation and maintenance instructions

Honeywell

Honeywell Farenhyt Series Installation and maintenance instructions

Siemens SIRIUS 3RF24 AB Series operating instructions

Siemens

Siemens SIRIUS 3RF24 AB Series operating instructions

Pilz PNOZ s4 operating manual

Pilz

Pilz PNOZ s4 operating manual

Siemens SIRIUS 3RF23 0 Series Original operating instructions

Siemens

Siemens SIRIUS 3RF23 0 Series Original operating instructions

MITSUBISHI ELECTRIC ENGINEERING DG2BK1TB Series user manual

MITSUBISHI ELECTRIC ENGINEERING

MITSUBISHI ELECTRIC ENGINEERING DG2BK1TB Series user manual

YASKAWA VARISPEED-616G5 instructions

YASKAWA

YASKAWA VARISPEED-616G5 instructions

Lovato PMV95N***NFC Series user manual

Lovato

Lovato PMV95N***NFC Series user manual

SafeTrust SABRE SA350 install guide

SafeTrust

SafeTrust SABRE SA350 install guide

F&F PP-1P quick start guide

F&F

F&F PP-1P quick start guide

Kyongbo Electric K-PAM 5500 Series user manual

Kyongbo Electric

Kyongbo Electric K-PAM 5500 Series user manual

VAMP 50 Operation and Configuration

VAMP

VAMP 50 Operation and Configuration

Taco SR504-EXP-4 instruction sheet

Taco

Taco SR504-EXP-4 instruction sheet

Schaffner ECOsine FN3416 user manual

Schaffner

Schaffner ECOsine FN3416 user manual

macromatic MDB Series installation instructions

macromatic

macromatic MDB Series installation instructions

COQON UPSPFMB1 manual

COQON

COQON UPSPFMB1 manual

Rockwell Automation Allen-Bradley Guardmaster Minotaur MSR131RTP installation instructions

Rockwell Automation

Rockwell Automation Allen-Bradley Guardmaster Minotaur MSR131RTP installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.