Cyber Power BP72V60ART2U User manual

Copyright © 2018 Cyber Power Systems, Inc.
OVERVIEW
1
The CyberPower extended battery modules (BP36V60ART2U / BP72V60ART2U) support 60A polarized plugs, and are designed for variety of Cyber Power
UPS systems. When combining with the UPS, the EBM provides extended runtime with a 36VDC/72VDC external connection. Additional parallel-connected
EBM provide the UPS for a longer extended runtime operation.
1K/1.5KVA or 2K/3KVA extended battery module
User’s manual Register card
Rackmount left rail Rackmount right rail
Left hanging bracket Right hanging bracket
IEC320 C14 to NEMA 5-15P power cord
Rackmount ears (Stands) (2)
Tie plate (1)
M5X7L black flat head screws (8)
M5X12L black pan head screws (12)
M5X6L silver pan head screws (6)
Plastic washers (8)
Screw hole dust covers (12)
Rubber feet (12)
UNPACKING

Copyright © 2018 Cyber Power Systems, Inc.
HARDWARE INSTALLATION
2
HARDWARE INSTALLATION
These versatile EBM can be mounted in a rackmount or vertical tower
orientation. This is especially important to growing organizations with
changing needs that value having the option to position an EBM on the
floor or in a rackmount system. Please follow the instructions below for
the respective mounting methods.
SAFETY PRECAUTIONS
CAUTION! To prevent the risk of fire or electric shock, only use the
supplied hardware to attach the mounting brackets.
RACKMOUNT INSTALLATION
Step 1: Remove the dust covers
Remove the dust covers *5 pcs from the screw holes.
Step 2: Rackmount ears & hanging brackets installation
Attach two rackmount ears to the EBM using the provided M5X7L*8pcs
screws and tighten two hanging brackets with the M5X6L*6pcs screws.
Step 3: Rackmount rail Installation
The rails adjust to mount in 48-cm (19-inch) wide racks from 52 to
91.5cm (20.5 to 36 inches) deep. Select the proper holes in the rack for
positioning the EBM in the rack. The EBM takes up 2 rack units.
Position the guide screws on the rails into the rear rack square holes to
temporarily support the rails in place. Tighten the front rail screws on the
rack.

Copyright © 2018 Cyber Power Systems, Inc.
HARDWARE INSTALLATION
3
Step 4: Adjust rackmount rails to fit your rack
Adjust the rail depth to match your rack depth. Attach the rackmount rail
to your rack with two screws and two plastic washers at the front of the
rack. (Located in position 1 & position 4) Tighten the M5X12L screws on
the front bracket. Secure the rail to the rear of the rack with two M5X12L
screws and two plastic washers.
Step 5: Place and secure the EBM on the rails
Slide the hanging brackets on the EBM into the rails mounted in the rack
with the front of the unit facing toward you. Secure the EBM to your rack
with four M5X12L*4pcs screws at the front of the rack. (Located in
position 2 & position 5)
How to slide the EBM out from the rack
The EBM will be secured by a safety locking mechanism midway of
pulling it out of the rack. Use both hands to hold the EBM and press the
safety locking tab to pull the EBM out.

Copyright © 2018 Cyber Power Systems, Inc.
HARDWARE INSTALLATION
4
VERTICAL/TOWER INSTALLATION
Step 1: Adhere the rubber feet on the bottom side of base stands
Adhere the protective rubber feet on the bottom side of base stands
(rackmount ears) UPS system and EBM.
Step 2: Attach the base stands and attach the dust covers
Secure the tie plate with the screws (M5X7*4pcs). Tighten the screws
(M5X12*4pcs) of the base stands (rackmount ears) onto the bottom of
the UPS system and EBM. Insert dust covers into the screw holes that
are not being used.
Step 3: Rotate the Multifunction LCD Module
Unscrew the upper panel of the UPS. Separate the upper panel from the
UPS. Gently lift the LCD module out. Rotate it to the tower orientation.
Reinstall it for a tower configuration.
SAFETY PRECAUTIONS
CAUTION! Installation environment should be in a temperature and
humidity controlled indoor area free of conductive contaminants. Do not
install this EBM where excessive moisture or heat is present (Please see
specifications for acceptable temperature and humidity range).
CAUTION! Never install an EBM, or associated wiring or equipment,
during a lightning storm.
CAUTION! Do not work alone under hazardous conditions.
CAUTION! In case of the risk of electric shock, do not remove the top
cover.
CAUTION! The battery can energize hazardous live parts inside even
when the AC input power is disconnected.

Copyright © 2018 Cyber Power Systems, Inc.
5
BASIC OPERATION
EXTENDED BATTERY MODULE FRONT/REAR PANEL DESCRIPTION
1. On-board Replaceable Fuse Cover
Replaceable fuse is accessible from the rear panel.
Service to be performed by qualified personnel only.
2. AC Circuit Breaker
Provides overload and fault protection.
3. AC Output Outlet (IEC320 C13 for optional Fast Charge
function)
Use this outlet to connect to the AC Input Inlet of a
downstream EBM.
4. AC Input Inlet (IEC320 C14 for optional Fast Charge
function)
AC power connectivity to wall receptacle, or AC output
from EBM upstream
5. Input Connector
Use this input connector to daisy chain the next EBM.
Remove the connector cover for access.
6. Output Cable
Use this output cable to connect the EBM to the UPS or to
the next EBM.
7. DC Breaker
Use the DC breaker to disconnect battery output.
BP36V60ART2U / BP72V60ART2U
CONNECTION #1 : UPS WITH ONE EXTENDED BATTERY MODULE
Step 1: Turn off the DC breaker of the EBM.
Step 2: Loosen the two screws to remove the battery cable
retention bracket of the UPS.
Step 3: Use the output cable of the EBM to connect the EBM to
the UPS.
Step 4: Rotate the battery cable retention bracket and tighten
the two screws to fix battery cable.
Step 5: Use a power cord to plug AC input inlet of the EBM
into a wall receptacle.
Step 6: Turn on the DC breaker of the EBM.

Copyright © 2018 Cyber Power Systems, Inc.
BASIC OPERATION
6
CONNECTION #2 : UPS WITH MULTIPLE EXTENDED BATTERY MODULES
Step 1: Connect the 1st EBM to the UPS using the instructions
above.
Step 2: Turn off the DC breaker of the 2nd Battery module.
Step 3: Loosen the two screws to remove the battery cable
retention bracket of the 1st EBM.
Step 4: Use the output cable of the 2nd EBM to connect the 2nd
EBM to the 1st EBM.
Step 5: Rotate the battery cable retention bracket and tighten
the two screws to fix battery cable.
Step 6: Use a power cord to plug AC input inlet of the 2nd EBM
into AC output outlet of the 1st EBM.
Step 7: Turn on the DC breaker of the 2nd Battery module.
Step 8: Set the EBM number to the respective setting to match
the number of installed units. To do this via the LCD
control panel, go to the Configuration Menu, then scroll
to EBM Number setting, select the appropriate number
and Save. This operation can also be done if there is an
RMCARD installed in the UPS, or via PowerPanel®
Business Edition Agent. Please see their respective User
Manuals for instructions.

Copyright © 2018 Cyber Power Systems, Inc.
7
BASIC OPERATION
EXTENDED BATTERY MODULES CONFIGURATION
The UPS can be configured to reflect the correct estimated run-times for the number of EBM installed by using the LCD Control
Panel to select the number of EBM installed.
1. Press the “ENTER” button to activate the “MAIN MENU”.
2. Press the “▲”and “▼”buttons to scroll to the “Configure”option.
3. Press the “ENTER” button to select the “Configure”submenu.
4. Press the “▲”and “▼”buttons to scroll to the “EBM Number”option.
5. Press the “ENTER” button to select the “EBM Number”submenu.
The first configuration number will be displayed on the second column of LCD display.
6. Press the “▲”and “▼”buttons to scroll through the number of attached EBM.
7. Press the “ENTER” button to select the number of EBM installed.
You may be prompted to save the selection, if so press the “ENTER” button to save the setting.
8. Press the “ESC” button to cancel or return to the previous LCD menu.
Configure Submenu
Available Settings
Default Settings
EBM Number
= [0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10]
0

Copyright © 2018 Cyber Power Systems, Inc.
MAINTENANCE
8
Storage
To store your extended battery modules for a long period of time, turning
DC breaker off, cover it and store with the batteries fully charged.
Recharge the battery every three months to ensure battery life.
Battery Replacement
Please read and follow the Safety Instructions before servicing the
battery. Battery replacement should be performed by trained personnel
who are familiar with the procedures and safety precautions. Make a note
of the replacement EBM number.
Safety Precautions
CAUTION! Only use replacement batteries which are certified by
Cyber Power Systems. Use of incorrect battery type is an electrical
hazard that could lead to explosion, fire, electric shock, or short circuit.
CAUTION! Batteries contain an electrical charge that can cause
severe burns. Before servicing batteries, please remove any conductive
materials such as jewelry, chains, wrist watches, and rings.
CAUTION! Do not open or mutilate the batteries. Electrolyte fluid is
harmful to the skin/eyes and may be toxic.
CAUTION! To avoid electric shock, turn off and unplug the EBM from
the wall receptacle before servicing the battery.
CAUTION! Only use tools with insulated handles. Do not lay tools or
metal parts on top of the UPS or battery terminals.
Replacement Batteries
Please refer to the front side of the EBM for the model number of the
correct replacement batteries. For battery procurement, log onto
www.cyberpowersystems.com, or contact your local dealer.
Battery Disposal
Batteries are considered hazardous waste and must be disposed of
properly. Contact your local government for more information about
proper disposal and recycling of batteries. Do not dispose of batteries
in fire.
Cyber Power Systems encourages environmentally sound methods for
disposal and recycling of its UPS products. Please dispose and/or
recycle your UPS and batteries in accordance with local regulations.
Battery Replacement
Step 1: Remove the front panels
Step 2: Remove the retaining screws from
the cable protection cover and then remove
the cover itself
Step 3: Pull the battery tray out slowly and
then put the new battery tray back into the
compartment
Step 4: Fasten back the connectors on the battery retaining
cover. Then insert the battery connectors and tighten the
screws of battery retaining cover
Step 5: Install the front panels, then to execute battery test via the LCD control
panel, go to the Configuration Menu, then scroll to the UPS Diagnostic then
select battery test and Activate, then scroll to Reset ReplaceBAT to reset the
battery replacement date. This operation can also be done via PowerPanel®
Business Edition Agent or RMCARD web interface if it is installed. Please see
their respective User Manuals for detailed instructions.

Copyright © 2018 Cyber Power Systems, Inc.
TECHNICAL SPECIFICATIONS
9
If the Battery module requires further service, please refer to the following information:
1. Call us at (877) 297-6937 or write to us at Cyber Power Systems (USA), Inc., 4241 12th Ave. E., STE 400, Shakopee, MN 55379 or send us an e-mail
message at tech@cpsww.com for instructions.
2. When you contact CyberPower, identify the Product, the Purchase Date, and the item(s) of Connected Equipment. Have information on all applicable
insurance or other resources of recovery/payment that are available to the Initial Customer and Request a Claim Number.
3. You must provide a dated Proof-of-Purchase receipt (or other proof of the original purchase) and provide a description of the defect.
4. Pack and ship the product to CyberPower and, if requested, the item(s) of Connected Equipment, a repair cost estimate for the damage to the Connected
Equipment, and all claim forms that CyberPower provides to you. Show the Claim Number on the shipping label or include it with the product.
You must prepay all shipping costs, you are responsible for packaging and shipment, and you must pay the cost of the repair estimate.
Model
BP36V60ART2U
BP72V60ART2U
Configuration
AC Input Voltage
100~125Vac
DC Output Voltage
36Vdc
72Vdc
DC Output Current
60A
Physical
Dimensions (L x W x H =)
16.9 x 17 x 3.5in. (430 x 433 x 88mm)
23.6 x 17 x 3.5in. (600 x 433 x 88mm)
Net Weight
50.6lbs(23.0Kg)
96.8lbs(44.0Kg)
Battery
Specifications
(6) (12V9AH) (2 x Banks of 3 Batteries)
(12) (12V9AH) (2 x Banks of 6 Batteries)
Replacement Battery Cartridge
(1) RB1290X3L + (1) RB1290X3R
(2) RB1290X6B
Recharge Time 0-90% (Typical)
4 hours
Connector Type
PP45
Sealed, Maintenance Free
Yes
Hot-Swappable
Yes
Built-in Charger
Yes (2A) max.
Environment
Operating Temperature
32℉to 104℉( 0℃to 40℃)
Operating Relative Humidity
0 to 90% Non-Condensing
Safety
Conformance Approvals
CE, UL
RoHS
RoHS Compliant
Warranty
Product Warranty
3-year limited warranty, Free Tech Support
Problem
Possible Cause
Solution
Warning
BAT Disconnected
Missing battery power.
Check battery connector and battery breaker.
Battery Failure
UPS has failed a Battery Test.
1. Check battery connector and battery breaker.
2. Contact technical support to replace the
battery.
Replace Battery
Battery will soon need to be replaced due to
insufficient runtime.
Contact technical support to replace the battery.
Fault
Over Charge
Battery is overcharged.
1. Remove battery connector and check
charger voltage.
2. Contact CyberPower for repair.
Charger Failure
Charger has failed.
TROUBLE SHOOTING
CUSTOMER SERVICE

Copyright © 2018 Cyber Power Systems, Inc.
PRODUCT REGISTRATION
10
CyberPower requests that you complete and return the Warranty Registration Card enclosed with the Product or register the Product at its website
(www.cyberpowersystems.com) to establish that you are the Initial Customer of the Product, and therefore entitled coverage under the Limited Warranty and
the Connected Equipment Guarantee. (Registration is not required for coverage, but note: if you do not register your purchase, you will be required to provide
proof of purchase.)
Read the following terms and conditions carefully before using the CyberPower BP36V60ART2U / BP72V60ART2U. By using the Product you consent to be
bound by and become a party to the terms and conditions of this Limited Warranty and Connected Equipment Guarantee (together referred to as this
“Warranty”). If you do not agree to the terms and conditions of this Warranty, you should return the Product for a full refund prior to using it.
Who is Providing this Warranty?
Cyber Power Systems (USA), Inc. (“CyberPower”) provides this Limited Warranty.
What Does This Warranty Cover?
This warranty covers defects in materials and workmanship in the Product under normal use and conditions. It also covers equipment that was connected to
the Product and damaged because of the failure of the Product.
What is the Period of Coverage?
This warranty covers the Product for three years and connected equipment for as long as you own the Product.
Who Is Covered?
This warranty only covers the original purchaser. Coverage ends if you sell or otherwise transfer the Product.
How Do You Get Warranty Service?
1. Before contacting CyberPower, identify Your Product model number, the Purchase Date, and each item of Connected Equipment.
2. Email us at tech@cpsww.com or Call us at (877) 297-6937.
3. If your product requires warranty service you must provide a copy of your dated purchase receipt or invoice.
How Do You Open A Connected Equipment Claim?
1. Call us at (877) 297-6937 or write to us at Cyber Power Systems (USA), Inc., 4241 12th Ave. E., STE 400, Shakopee, MN 55379, or send us an e-mail
message at claims@cpsww.com for instructions, within 10 days of the occurrence.
2. When you contact CyberPower, identify the Product, the Purchase Date, and the item(s) of Connected Equipment. Have information on all applicable
insurance or other resources of recovery/payment that are available to the Initial Customer and Request a Claim Number.
3. You must provide a dated purchase receipt (or other proof of the original purchase) for the Cyber Power unit and connected equipment. You also need to
provide a description of the damage to your connected equipment.
4. Pack and ship the product to CyberPower and, if requested, the item(s) of Connected Equipment, a repair cost estimate for the damage to the Connected
Equipment, and all claim forms that CyberPower provides to you. Show the Claim Number on the shipping label or include it with the product. You must
prepay all shipping costs, you are responsible for packaging and shipment, and you must pay the cost of the repair estimate.
How Long Do I Have To Make A Claim?
All claims must be made within ten days of the occurrence.
What Will We Do To Correct Problems?
CyberPower will inspect and examine the Product.
If the Product is defective in material or workmanship, CyberPower will repair or replace it at CyberPower's expense, or, if CyberPower is unable to or decides
not to repair or replace the Product (if defective) within a reasonable time, CyberPower will refund to you the full purchase price you paid for the Product
(purchase receipt showing price paid is required).
If it appears that our Product failed to protect any equipment plugged into it, we will also send you forms for making your claim for the connected equipment.
We will repair or replace the equipment that was damaged because of the failure of our Product or pay you the fair market value (NOT REPLACEMENT
COST) of the equipment at of the time of the damage. We will use Orion Blue Book, or another a third-party valuation guide, or eBay, craigslist, or other
source to establish that amount. Our maximum liability is limited to $400,000 for BP36V60ART2U / BP72V60ART2U.
LIMITED WARRANTY AND CONNECTED EQUIPMENT GUARANTEE

Copyright © 2018 Cyber Power Systems, Inc.
LIMITED WARRANTY AND CONNECTED EQUIPMENT GUARNTEE
11
Who Pays For Shipping?
We pay when we send items to you; you pay when you send items to us.
What Are Some Examples Of What This Warranty Does Not Cover?
1. This Warranty does not cover any software that was damaged or needs to be replaced due to the failure of the Product or any data that is lost as a result of
the failure or the restoration of data or records, or the reinstallation of software.
2. This Warranty does not cover or apply to: misuse, modification, operation or storage outside environmental limits of the Product or the equipment
connected to it, nor for damage while in transit or in storage, nor if there has been improper operation or maintenance, or use with items not designed or
intended for use with the Product, such as laser printers, appliances, aquariums, medical or life support devices, etc.
What Other Limitations Apply?
The sole and exclusive remedies of the Initial Customer are those provided by this Warranty.
1. This Warranty does not apply unless the Product and the equipment that was connected to it were connected to properly wired and grounded outlets
(including compliance with electrical and safety codes of the most current electrical code), without the use of any adapters or other connectors.
2. The Product must have been plugged directly into the power source and the equipment connected to the Product must be directly connected to the Product
and not “daisy-chained” together in serial fashion with any extension cords, another Product or device similar to the Product, surge suppressor, or power tap.
Any such installation voids the Limited Warranty.
3. The Product and equipment connected to it must have been used properly in a suitable and proper environment and in conformance with any license,
instruction manual, or warnings provided with the Product and the equipment connected to it.
4. The Product must have been used at all times within the limitations on the Product’s VA capacity.
The Product was designed to eliminate disrupting and damaging effects of momentary (less than 1ms) voltage spikes or impulses from lightning or other
power transients. If it can be shown that a voltage spike lasting longer than 1ms has occurred, the occurrence will be deemed outside the rated capabilities of
the Product and the Limited Warranty is void. CyberPower Does Not Cover or Undertake Any Liability in Any Event for Any of the Following:
1. Loss of or damage to data, records, or software or the restoration of data or records, or the reinstallation of software.
2. Damage from causes other than AC Power Line Transients, spikes, or surges on properly installed, grounded and code-compliant 120 volt power lines in
the United States and Canada; transients, surges or spikes on standard telephone land lines, PBX telephone equipment lines or Base 10T Ethernet lines,
when properly installed and connected. (This exclusion applies, for example, to fluctuations in data transmission or reception, by CATV or RF transmission or
fluctuations, or by transients in such transmission.)
3. Damage from any circumstance described as excluded above with respect to the Product.
4. Damages from fire, flood, wind, rain, rising water, leakage or breakage of plumbing, abuse, misuse or alteration of either the product or the Connected
Equipment.
5. CyberPower excludes any liability for personal injury under the Limited Warranty and Connected Equipment Guarantee. CyberPower excludes any liability
for direct, indirect, special, incidental or consequential damages, whether for damage to or loss of property [EXCEPT FOR (AND ONLY FOR) the specific
limited agreement of CyberPower to provide certain warranty benefits regarding "Connected Equipment" under this Warranty], loss of profits, business
interruption, or loss of information or data. NOTE: Some States or Provinces do not allow the exclusion or limitation of incidental or consequential damages,
so the above limitation may not apply to you.
6. The Product is not for use in high-risk activities or with aquariums. The Product is not designed or intended for use in hazardous environments requiring
fail-safe performance, or for use in any circumstance in which the failure of the Product could lead directly to death, personal injury, or severe physical or
property damage, or that would affect operation or safety of any medical or life support device (collectively, "High Risk Activities"). CyberPower expressly
disclaims any express or implied warranty of fitness for High Risk Activities or with aquariums. CyberPower does not authorize use of any Product in any High
Risk Activities or with Aquariums. ANY SUCH USE IS IMPROPER AND IS A MISUSE OF THE PRODUCT.
Where Can I Get More Information?
The application of the United Nations Convention of Contracts for the International Sale of Goods is expressly excluded.
CyberPower is the warrantor under this Limited Warranty.
For further information please feel free to contact CyberPower at Cyber Power Systems (USA), Inc. 4241 12th Ave E., STE 400, Shakopee, MN 55379; call us
at (877) 297-6937; or send us an e-mail message at [email protected].

Copyright © 2018 Cyber Power Systems, Inc.
CONFORMANCE APPROVALS
12
FCC Notice
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any interference that may cause undesired operation.
WARNING!! This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user
will be required to correct the interference at his own expense. Shielded signal cables must be used with this product to ensure compliance with the Class A
FCC limits.
This document is believed to be accurate, but CyberPower reserves the right to change or correct the contents and does not assume any responsibility for
omissions or errors.
Need Additional Help?
Feel free to contact our Tech Support department with installation, troubleshooting, or general product questions.
CyberPower Technical Support
Phone: 1-877-297-6937
Web: www.cyberpowersystems.com
Address: 4241 12th Avenue E, Suite 400 Shakopee, MN 55379, USA
Hours of Operation:
Monday –Friday, 7:00am –6:00pm (CST)
Entire contents copyright © 2018 Cyber Power Systems, Inc.
All rights reserved. Reproduction in whole or in part without permission is prohibited.
The Class A digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulation.
Cet appareil numerique de la class A respecte toutes les exigencies du Reglement sur le materiel brouilleur du Canada.